![background image](http://html.mh-extra.com/html/omron/cp1e-e-d-series/cp1e-e-d-series_user-manual_742511213.webp)
8-45
8 Using Expansion Units and Expansion I/O Units
CP1E CPU Unit Hardware User’s Manual(W479)
8-3 An
alog
I/O U
n
its
8
8-3
-2 C
P
1W-
M
AD42/CP1W-
M
A
D
44 Analog I/O
Units
Analog Output Signal Ranges
−
10 to 10 V
The hexadecimal values E890 to 1770 (
−
6000 to 6000) correspond to an analog voltage range of
−
10
to 10 V. The entire output range is
−
11 to 11 V. Specify a negative voltage as a two’s complement.
0 to 10 V
The hexadecimal values 0000 to 2EE0 (0 to 12000) correspond to an analog voltage range of 0 to
10 V. The entire output range is
−
0.5 to 10.5 V. Specify a negative voltage as a two’s complement.
1 to 5 V
The hexadecimal values 0000 to 2EE0 (0 to 12000) correspond to an analog voltage range of 1 to
5 V. The entire output range is 0.8 to 5.2 V.
0 V
10 V
11 V
−
11 V
−
10 V
E890
(
−
6000)
E638
(
−
6600)
19C8
(6600)
1770
(6000)
0000 (0)
8000
7FFF
Conversion Data
Hexadecimal (Decimal)
0 V
10 V
10.5 V
−
0.5 V
FDA8
(
−
600)
3138
(12600)
2EE0
(12000)
0000 (0)
8000
7FFF
Conversion Data
Hexadecimal (Decimal)
1 V
5 V
5.2 V
0.8 V
3138
(12600)
2EE0
(12000)
0 V
7FFF
FDA8
(
−
600)
8000
Conversion Data
Hexadecimal (Decimal)
Summary of Contents for CP1E-E**D Series