![background image](http://html.mh-extra.com/html/omron/cp1e-e-d-series/cp1e-e-d-series_user-manual_742511247.webp)
8-79
8 Using Expansion Units and Expansion I/O Units
CP1E CPU Unit Hardware User’s Manual(W479)
8-4 T
e
mp
eratu
re
S
e
nsor U
n
its
8
8-4
-2 CP1W-T
S003 Tempe
ratur
e S
e
nsor
Units
(4) Programming Example
The following programming example shows how to store the input data of CP1W-TS003 (4
inputs) in D0 to D3, and W10.00 to W10.03 turn ON at the time of open-circuit detection.
•
DIP Switch Setting
•
Wiring Diagram
SW1
OFF
K
SW2
OFF
°C
SW3
NC
SW4
OFF
Thermocouple
SW5
ON
Analog
SW6
ON
1 to 5V/4 to 20mA
None
CP1W-TS003
Temperature Sensor Unit
Temperature unit setting: OFF(ºC)
Input range setting
Input 0: Thermocouple K(CIO2)
Input 1: Thermocouple K(CIO3)
Input 2: Thermocouple K(CIO4)
Input 3: Analog input 1 to 5V(CIO5)
CP1E
Input word
addresses
Output word
addresses
CIO 0
CIO 1
CIO 100
CIO 101
CIO 2
CIO 3
CIO 4
CIO 5
Temperature input 0
LOOP0
−
LOOP0+
NC
LOOP1
−
LOOP1+
NC
I IN2
I IN3
Temperature input 1
Temperature
input 2
LOOP2+
V IN2
LOOP3+
V IN3
LOOP2
−
COM2
LOOP3
−
COM3
Cold junction
compensator
Analog
device
with
voltage
output
Analog
input 3
(1 to 5 V)
Summary of Contents for CP1E-E**D Series
Page 3: ......
Page 66: ...2 Basic System Configuration and Devices 2 22 CP1E CPU Unit Hardware User s Manual W479...
Page 318: ...Appendices A 54 CP1E CPU Unit Hardware User s Manual W479...
Page 322: ...Index 4 CP1E CPU Unit Hardware User s Manual W479...
Page 324: ...Revision 2 CP1E CPU Unit Hardware User s Manual W479...
Page 325: ......