5 Installation and Wiring
5-2
CP1E CPU Unit Hardware User’s Manual(W479)
5-1
Fail-safe Circuits
This section describes the fail-safe circuits that must be set up outside the CP1E.
Always set up safety circuits outside of the PLC to prevent dangerous conditions in the event of errors
in the CP1E CPU Unit or external power supply.
In particular, be careful of the following points.
If the PLC’s power supply is turned ON after the controlled system’s power supply, outputs in Units
such as DC Output Units may momentarily not function properly.
To prevent any malfunction, add an external circuit that prevents the power supply to the controlled sys-
tem from going ON before the power supply to the PLC itself.
When any of the following errors occur, PLC operation (program execution) will stop and all outputs
from the Units will be turned OFF.
•
A CPU error (watchdog timer error) or CPU on standby
•
A fatal error (memory error, I/O bus error, too many I/O points error, program error, cycle time
exceeded error, or FALS error)
Be sure to add any circuits necessary outside of the PLC to ensure the safety of the system in the event
of an error that stops PLC operation.
It is possible for an output to remain ON due to a malfunction in the internal circuitry of the Output Unit,
such as a relay or transistor malfunction. Always add any circuits necessary outside of the PLC to
ensure the safety of the system in the event that an output fails to go OFF.
When the PLC controls operation such as the clockwise and counterclockwise operation of a motor and
if there is any possibility of an accident or mechanical damage due to faulty PLC operation, provide an
external interlock such as the one shown below to prevent both the forward and reverse outputs from
turning ON at the same time.
Example:
Timing of Supplying Power to the PLC and the Controlled System
Safety Circuit for Errors (Outputs Turned OFF)
Safety Circuit after a Malfunction (When an Output Remains ON)
External Interlock Circuits
A circuit like the one shown in the dia-
gram on the left is required to prevent
outputs MC1 and MC2 from both being
ON at the same time even if both PLC
outputs CIO 100.00 and CIO 100.01
are both ON.
CP1E
Interlock Circuits
MC2
100.00
MC1
100.01
MC1
MC2
Motor
clockwise
operation
Motor
counterclock
wise operation
Summary of Contents for CP1E-E**D Series
Page 3: ......
Page 66: ...2 Basic System Configuration and Devices 2 22 CP1E CPU Unit Hardware User s Manual W479...
Page 318: ...Appendices A 54 CP1E CPU Unit Hardware User s Manual W479...
Page 322: ...Index 4 CP1E CPU Unit Hardware User s Manual W479...
Page 324: ...Revision 2 CP1E CPU Unit Hardware User s Manual W479...
Page 325: ......