3 Check and start operation
3-4 Interpreting beeps and displays
BU150R
48
(2) When "Power" switch is "OFF"
No
Status
indicator
Power
supply
output
lamp
Battery
mode
lamp
Battery
replacement
lamp
Beep Charging
Description
Solution
10
None (ON)
AC input voltage
and AC input
frequency are too
high.
Use within the
AC input
voltage/frequen
cy range
described in the
specifications.
11
None (ON)
AC input frequency
is too high.
12
None (ON)
AC input voltage is
too low and AC
input frequency is
too high.
13
None (ON)
AC input voltage is
too high.
14
None (ON)
AC input voltage is
too low.
15
None (ON)
AC input voltage is
too high and AC
input frequency is
too low.
16
None (ON)
AC input frequency
is too low.
17
None (ON)
AC input voltage
and AC input
frequency are both
too low.
Summary of Contents for BU150R
Page 22: ...2 Installation and connection 2 1 Installation BU150R 22 Incorrect Positions...
Page 92: ...7 How to use option cards 7 3 SNMP Web card BU150R 92 7 3 SNMP Web card LAN 10 100...
Page 102: ...10 References 10 2 Dimensions BU150R 102 Stand for vertical layput 200 200 70 50 70 50...
Page 103: ...10 References 10 2 Dimensions BU150R 103 10 Rubber feet 23 25 405 50 40 358 40 3...
Page 104: ...10 References 10 2 Dimensions BU150R 104 Using Ear brackets 44 5 22 0 13 5 455 25 465...