3 Check and start operation
3-1 The name and function for the operation and display
BU150R
36
●
Auto startup setting after recovery from power failure ("Setting" switch 2)
Factory setting: OFF
OFF : Automatically starts when power is restored.
After a power failure occurs and the unit shuts down using the shutdown software or
contact signal(BS signal), the unit automatically starts and begins to output when the
commercial power is restored.
ON: Does not automatically start when power is restored.
After the unit is shut down with the UPS monitoring software or contact signal (BS
signal), it does not start up when commercial power is restored. Startup is performed
by turning the "Power" switch OFF once, and then back ON again.
●
Setting for whether or not to perform test once every 4 weeks ("Setting"
switch 3)
Factory setting: OFF
OFF: The self-diagnostic test is automatically executed once every 4 weeks.
ON
:
Does not perform the auto test once every 4 weeks.
Use this setting to disable Battery Mode for the regularly performed test.
●
Auto startup mode setting ("Setting" switch 4)
Factory setting: OFF
OFF: Mode A
After UPS stopped, the UPS is automatically started immediately when "ON" is
detected for the AC input.
ON: Mode B
After UPS stopped, the UPS is automatically started in the AC input's "OFF to ON"
timing that is detected.
(Definition of AC input OFF: When AC input is OFF for 1 second or more)
Summary of Contents for BU150R
Page 22: ...2 Installation and connection 2 1 Installation BU150R 22 Incorrect Positions...
Page 92: ...7 How to use option cards 7 3 SNMP Web card BU150R 92 7 3 SNMP Web card LAN 10 100...
Page 102: ...10 References 10 2 Dimensions BU150R 102 Stand for vertical layput 200 200 70 50 70 50...
Page 103: ...10 References 10 2 Dimensions BU150R 103 10 Rubber feet 23 25 405 50 40 358 40 3...
Page 104: ...10 References 10 2 Dimensions BU150R 104 Using Ear brackets 44 5 22 0 13 5 455 25 465...