3 Check and start operation
3-5 UPS operation mode settings
BU150R
54
7. Dry contact test (BL/TR/BU/WB/BS/remote)
Four types of output signal can be forcibly turned ON.
The ON/OFF state of two types of input signal can be checked with the status indicator
and the beeper.
8. Expansion unit count setting
The number of expansion batteries "BUM150RA" to be connected is set.
Be sure to set this when using expansion batteries.
If the setting is not made correctly, it may cause a drop in backup time.
Setting range : 0 - 6 ( Default setting : 0 )
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Battery Low signal (BL)
Trouble signal (TR)
Backup signal (BU)
Deteriorated battery signal
(WB)
Backup power supply stop
signal (BS)
Remote ON/OFF signal
Beep
Output signal
Input signal
While the signal is being input, these status
indications blink and the beep sounds.
Signal input/output test start
Signal output test
Contact signal is forced to turn ON.
Signal input test
While the signal is being input,
the status indicator blinks and
the beep sounds.
Signal input/output test end
Summary of Contents for BU150R
Page 22: ...2 Installation and connection 2 1 Installation BU150R 22 Incorrect Positions...
Page 92: ...7 How to use option cards 7 3 SNMP Web card BU150R 92 7 3 SNMP Web card LAN 10 100...
Page 102: ...10 References 10 2 Dimensions BU150R 102 Stand for vertical layput 200 200 70 50 70 50...
Page 103: ...10 References 10 2 Dimensions BU150R 103 10 Rubber feet 23 25 405 50 40 358 40 3...
Page 104: ...10 References 10 2 Dimensions BU150R 104 Using Ear brackets 44 5 22 0 13 5 455 25 465...