3 Check and start operation
3-3 Start and stop procedures and basic operation
BU150R
43
3
3-3 Start and stop procedures and basic operation
3-3-1 Start and stop procedures
For cautions when operating the UPS, including start and stop, refer to "Caution (for use)"
shown in the "Safety precautions" of the beginning of this manual.
■
Start procedure
Turn on the "Power" switch of the UPS.
・
Output begins in Bypass Operation a few seconds after the switch is activated. (Status
indicator "
")
・
The status indicator displays "
", and the self-diagnostic test is performed in Battery
Mode for about 15 seconds. If the battery voltage is low, the self-diagnostic test is not
performed. It is automatically executed after the battery is charged (approximately 8
hours). When the self-diagnostic test finishes successfully, switching to AC output from
commercial power is performed and normal operation starts.
・
When the self-diagnosis test finishes normally, the unit enters the normal operating state
through inverter operation.
・
When the self-diagnostic test is not performed, AC output begins immediately inverter
operation.
Status indicator
Beep
Power supply output receptacles
None
Outputs power (connected devices are
powered)
・
During operation, the battery is charged automatically.
AC input
7 seg.
Power supply SW
Power supply
output lamp
Operating mode
Output
ON
OFF
ON
OFF
ON
OFF
Commercial
Power Battery
Commercial
Power Battery
<Note>
D-1: Display the latest UPS fault mode
(If there is no record for UPS fault, UPS display the
Startup
preparation
a few
seconds
Bypass
operation
a few
seconds
Self-diagnostic
test
about
15 sec.
Inverter
operation
D-1
1 sec.
Summary of Contents for BU150R
Page 22: ...2 Installation and connection 2 1 Installation BU150R 22 Incorrect Positions...
Page 92: ...7 How to use option cards 7 3 SNMP Web card BU150R 92 7 3 SNMP Web card LAN 10 100...
Page 102: ...10 References 10 2 Dimensions BU150R 102 Stand for vertical layput 200 200 70 50 70 50...
Page 103: ...10 References 10 2 Dimensions BU150R 103 10 Rubber feet 23 25 405 50 40 358 40 3...
Page 104: ...10 References 10 2 Dimensions BU150R 104 Using Ear brackets 44 5 22 0 13 5 455 25 465...