4 Maintenance and Inspection
4-3 Replacing the fan
BU150R
75
4
3.
While pressing up on the tip of the fan connector (
①
), pull it toward you to
disconnect it. (
②
)
4.
Insert the new fan connector until it clicks into place.
・
Replacement fan : Model BUF150R
5.
Insert the fan into the UPS unit. Place the fan guard (
①
) and fix the fan guard and
the fan together with four screws (
②
).
* Make sure the cable does not become pinned under the fan's cover.
* Fix so that the label on the fan unit faces the back side.
①
②
②
Fix the fan guard and the fan
together with four screws
①
Insert the fan into
the UPS unit