background image

DRAGON POWER 1-L

1 KVA - 3 KVA

USER MANUAL

Summary of Contents for DP1OL-3KTRL-120

Page 1: ...DRAGON POWER 1 L 1 KVA 3 KVA USER MANUAL ...

Page 2: ...watches ringsor similar metal objects B Use insulatedtools C Wear rubbershoesandgloves D Donot place metal tools or similarparts on the battery E Disconnectthe load fromthe batteries before removingthe battery connectionterminal 4 Please do not expose the battery to the fire for avoiding explosion and endangering the safety of life 5 Non professionalsshould not open or damage the battery because t...

Page 3: ...splay 6 3 2Functionof button 7 3 3UPS workingstatustable of LCDdisplay 8 3 4Parameter query 9 3 5Functionsetting 10 4 Warningcode faultcodeandsolution 13 4 1Warningcodeandsolution 13 4 2Fault codeandsolution 14 4 3Commonfaultsandtrouble shooting 16 5 Controlandcommunication 17 5 1SNMP Card 17 5 2DryContact 17 5 3EPO 18 6 Battery Maintenance Repair 19 ...

Page 4: ...ps It continuously adjusts and filters the input voltage When the power supply is interrupted itwill providethe backuppowerfromthe backupbattery without timeinterruption In case of overload or inverter failure the UPS switches to the bypassstate and be powered by the mains If theoverloadiscleared the UPS willautomaticallyswitchbackto the inverterpower supplystate 1 1 Symbol SymbolsandMeanings Symb...

Page 5: ...puterinterface Smart slot optional Externalbattery connection USB Input over currentprotection ACINPUT Outputsocket EPO Battery interface Battery breaker optional Maintenance bypassswitch optional Output breaker optional ...

Page 6: ...re sine wave Overload time Linemode 10min 102 110 load 1min 110 130 load 10s 130 150 load Battery mode 1min 102 110 load 10s 110 130 load 30s 130 150 load Efficiency Line Mode 94 Battery Mode 93 ECOMode 98 Battery Type Sealed lead acid maintenancefree Voltage 96VDC Battery Number 12V9Ah 8pcs ChargingCurrent 1A ChargingMode Two Threeperiod charging Management Intelligent port RS232 USBport SNMP car...

Page 7: ...only inanambient temperature range of0 40 32 104 Install it in a clean environment free from moisture flammableliquids gasesand corrosivesubstance ThisUPS containsnouser serviceablepartsexcepttheinternal battery pack TheUPS ON OFF pushbuttons donot electrically isolate internal parts Under no circumstanceattempt to gain accessinternally due to the riskof electric shockor burn Donot continue to use...

Page 8: ...dstatusmonitoring connectthe communicationcable one end to the USB RS232port and the other to the communicationport of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor UPS statusthroughPC TheUPS isequippedwith intelligent slotperfect foreither SNMP or AS400card When installing either SNMP or AS400cardin the UPS it will provide advancedcommunicationa...

Page 9: ...mation Thebattery capacity 0 25 26 50 51 75 76 100 isdisplayed separately andthe battery iconflasheswhen the battery is low or not connected Other information AC Battery Bypass Inverter Outputworking Fan status LEDwill always be onwhen the fan is normal andflashes when the fan fails Setting icon when entering the setting menu the icon will light up and the icon isnot shownin the other cases ECOfun...

Page 10: ...heckingand mute function Testing in ACMode pressthe two buttons at the same time for 2secondsabove to test the battery Mute in Battery Mode Alarm TestingMode presstwo buttons at the sametime for 2 secondsabove to erase alarms presstwobuttonsagainfor2secondsaboveto recover alarms Functionsetting confirmationkey Functionsetting press the key more than 2 secondsto enter the function setting page afte...

Page 11: ...ion When the ACinput isout of limited rangeor shutoff the UPS will turn to Battery Mode Thebatteries supplythe inverter and have beepevery 4seconds BypassMode LCDdisplaycontent Instruction When theACinputkeepsnormal start thebypassmodeand closethe UPS on the panel TheUPS will turn to BypassMode and have beep every 2 minutes Error Condition LCDdisplaycontent Instruction When the UPS hasfaults or al...

Page 12: ...alarm information by default When UPS keepsnormal working the homepagedefault display will show the output voltage and frequency information Press right button more than 2sec LCDwill turn to the pollingmode Every 2 secthe shown displaywill turn pages Press longtime LCDwill exitthepollingmode LCDDisplay1 UPS input outputvoltage LCDDisplay2 UPS input output frequency LCDDisplay3 Battery voltageand c...

Page 13: ...confirmation button 0 5 2sec thenfinish the OPUsetting Thenumberbyleft sideofOPUwill keeplightingon no flashing 4 Press functional setting button over 2 sec quit the settingpageandbacktothe homepage Ornooperation waitingmorethan 30sec thepagewill comebacktohome pageautomatically Note When the output voltage settingwith 110V the output needsto decreaseto 90 of ratedpower 02 Otherfunctionalsetting 0...

Page 14: ...V load 50 02 3 EconomicOperation Mode LCDDisplay Setting ECOisOFF bydefault canbe set as ONto improve the efficiency ofsystemoperation Note For the modelswith PF 1 OFFbydefault andunableto set 02 4 Emergencyshutdown EPO LCDDisplay Setting When EP isset to ON the EPOoption appearson the function settingpage Emergencyshutdowncanbesetasclosedoropen totrigger thedefault isopentotrigger Note After EPO ...

Page 15: ...hargerCurrent CHG LCDDisplay Setting When EP is set to ON the CHGoption appearson the functional settingpage the chargingcurrent canbeset 1 12Aoptional default 1A Noted if UPS built inbatteries the charger current default 1A andcantbechanged 02 7 InputNeutral andLivecablereversealarmfunction LCDDisplay Setting The input neutral and live cable reverse alarm mode is closedby default can chooseto ope...

Page 16: ...eutral andthe live cables 2 Checkthe groundcable connection 8 Battery over voltage UPS detects highbattery voltage Checkthat the battery quantity setting isconsistentwith the actual battery quantity 9 Chargerfailure Abnormalchargerhardware Contactthe supplier 10 Over temperature alarm 1 Fanfault 2 Air ductof UPS rear panel is blocked 3 Overload 4 NTCsensorabnormal or connectionabnormal 5 Power com...

Page 17: ...anel of the UPS is blocked 3 Overload 4 NTCsensorabnormality or abnormalwiring 5 Power componentIGBT is damaged 1 Please checkthe rectifier fan 2 Clean the obstacles onthe air ductof the rear panelof the UPS 3 Checktheloads 4 If all of above do not work please contact the supplier 8 Battery relay short circuit Relay RL1 RL3hardware damaged Please contact the supplier 9 Bus relay soft starting fail...

Page 18: ...ifthe voltagehasbeen reduced 67 Chargingover voltageor battery connection reversed 1 Hardware error 2 Number of battery wrong 3 Wiring wrong 1 Checkwhether the battery wiring or battery number meetsthe requirements 2 If no anyabnormal please contact the supplier 68 Unknown machinemodel Software versionerror 1 Restart the machine 2 If no anyabnormal please contact the supplier 72 Chargerover curren...

Page 19: ...load Remove all loadsand restart the machine 5 With city electricity butno city electricity indication Mains voltage or frequencyover UPS inputrange Useamulti metertocheck whether the input voltageand the input frequency meetsthe requirements 6 The battery dischargetime is lower than the standard time Thepower of batteries hasbeenused Changenew battery Thebatteries were not Chargethe batteries mor...

Page 20: ...B9 PhoenixDescription UPS fault 1 9 Openfromcommonconnection UPS isabnormal Closed UPS is normal General 2 7 Openfromcommonconnection UPS iswarning Closed UPS is normal GND 3 2 Internal GND usedtoconnect external power supply12 24Vdc Remoted shutdown 4 4 Input port Used with external power supply If connected to power supply UPS transfer to bypass UPS shutdownif bypassis abnormal Common connection...

Page 21: ... 4 5 9 8 7 Battery low UPS is on Utility fail UPS fail General alarm Remote shutdown GND VCC 5 3EPO Theremote EPO islocated onthe rear panel of UPS Its normal closed if its open it will active EPO function the UPS will shutdownoutput ...

Page 22: ...gtime shouldnotbeless than12hours In normalcircumstances service life of the battery is 3 5years if the battery isfoundto be in poor condition it must bereplaced in advance When replacingthe battery it mustbe done byaprofessional When replacingthe battery followthe principleof quantityandmodelconsistent The battery shouldnot be replacedindividually andwhen it replaced asa whole shouldbe accordingt...

Page 23: ...www lbspower com Español English ...