background image

UPS OPERATING MANUAL 

MANUEL DE FONCTIONNEMENT DE L'ASI

 

MANUALE OPERATIVO UPS

KEOR HPE

 60÷160 kVA 

Summary of Contents for BSK93

Page 1: ...UPS OPERATING MANUAL MANUEL DE FONCTIONNEMENT DE L ASI MANUALE OPERATIVO UPS KEOR HPE 60 160 kVA ...

Page 2: ...plémentaires peuvent être nécessaires pour éviter les perturbations Catégorie ASI C3 conformément á la norme IEC 62040 2 Questo prodotto è destinato ad applicazioni commerciali e industriali del secondo ambiente durante l installazione può essere necessario introdurre alcune limitazioni ed adottare misure aggiuntive per prevenire i disturbi Classe UPS C3 in accordo alla norma CEI 62040 2 ELECTROMA...

Page 3: ......

Page 4: ...L MANUEL DE FONCTIONNEMENT DE L ASI MANUALE OPERATIVO UPS Index of sections Indice delle sezioni Code Codice 1 WARNINGS AND GENERAL INFORMATION AVERTISSEMENTS ET INFORMATIONS GÉNÉRALES AVVERTENZE E INFORMAZIONI GENERALI OMB81275 2 INSTALLATION AND START UP INSTALLATION ET DÉMARRAGE DE L ASI INSTALLAZIONE ED AVVIAMENTO OML46086 3 UPS USER MANUAL Manuel de l utilisateur de l ASI UTILIZZO DELL UPS OM...

Page 5: ......

Page 6: ...ND GENERAL INFORMATION AVERTISSEMENTS ET INFORMATIONS GÉNÉRALES AVVERTENZE E INFORMAZIONI GENERALI Index Sommaire Indice ENGLISH LANGUAGE 3 1 CONVENTIONS USED 4 2 DOCUMENTATION NOTES 5 3 FACTORY WARRANTY 6 4 LIMITATION OF LIABILITY 8 LANGUE FRANÇAIS 9 1 CONVENTIONS UTILISEES 10 2 REMARQUES RELATIVES A LA DOCUMENTATION 11 3 GARANTIE USINE 12 4 LIMITATION DE RESPONSABILITÉ 14 LINGUA ITALIANA 15 5 CO...

Page 7: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali 2 OMB81275 REV B ...

Page 8: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali OMB81275 REV B 3 ENGLISH LANGUAGE ...

Page 9: ...n so as to minimize the risks to persons and property HAZARD HAZARD statements contain characteristics and basic instructions for the safety of persons Non compliance with such indications may cause serious injury or death WARNING WARNING statements contain characteristics and basic instructions for the safety of persons Non compliance with such indications may cause injury CAUTION CAUTION stateme...

Page 10: ...is manual and any other supporting technical documentation relating to the product must be stored and made accessible to personnel in the immediate vicinity of the UPS Further information In the event that the information provided in this manual is not sufficiently exhaustive please contact the manufacturer of the device whose details are available in the Contacts section ...

Page 11: ...e or in case our technicians incur extra time and or costs due to the site inaccessibility or due to work interruptions required by the customer such costs will be invoiced in accordance with the service conditions in use in the country of installation Modes required a In the event of a fault covered by the warranty the customer shall notify Legrand in writing of the occurred fault providing a sho...

Page 12: ...nal factors such as dirt fire flooding failed operation of the air conditioning system etc Non compliance with applicable safety standards Force majeure e g lightning surges natural disasters fire acts of war riots etc Fall or displacement due to incorrect installation Ordinary wear caused by proper and continuous use of the device b Protective devices inside the units fuses and dischargers are al...

Page 13: ... use is considered improper and therefore hazardous The manufacturer cannot be held responsible for possible damage arising from improper erroneous or unreasonable usage Legrand assumes responsibility for the equipment in its original configuration Any intervention that alters the structure or the operating cycle of the equipment must be carried out and authorized directly by Legrand Legrand will ...

Page 14: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali OMB81275 REV B 9 LANGUE FRANÇAIS ...

Page 15: ... Les indications DANGER contiennent des caractéristiques et des instructions de base destinées à assurer la sécurité des personnes Le non respect de ces indications peut entraîner des blessures graves voire la mort AVERTISSEMENT Les indications AVERTISSEMENT contiennent des caractéristiques et des instructions de base destinées à assurer la sécurité des personnes Le non respect de ces indications ...

Page 16: ...mentation Ce manuel ainsi que les autres documentations techniques relatives à ce produit doivent être stockés et mis à disposition du personnel à proximité immédiate de l UPS Autres informations Si les informations fournies dans le présent manuel ne sont pas suffisamment complètes veuillez contacter le fabricant de l appareil dont les coordonnées sont indiquées dans la section Contacts ...

Page 17: ...ande effectuée par erreur ou si nos techniciens interviennent plus longtemps que prévu et ou encourent des frais supplémentaires en raison de l inaccessibilité du site ou d interruptions de travail demandées par le client les coûts correspondants seront facturés conformément aux conditions d intervention en vigueur dans le pays d installation Documents requis a Si le client constate un défaut couv...

Page 18: ... la climatisation etc Du non respect des normes de sécurité en vigueur D un événement de force majeure par ex orage surtensions catastrophe naturelle incendie guerre émeute etc D une chute ou d un déplacement dû à une installation incorrecte De l usure ordinaire résultant de l utilisation correcte et continue de l appareil b Les dispositifs de protection inclus dans les unités fusibles et décharge...

Page 19: ...tilisation sera considérée comme inappropriée et dangereuse Le fabricant ne saurait être tenu responsable des éventuels dommages résultant d une utilisation inappropriée incorrecte ou déraisonnable Legrand est responsable de l équipement dans sa configuration d origine Toute intervention modifiant la structure ou le cycle de fonctionnement de l équipement devra être réalisée et autorisée directeme...

Page 20: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali OMB81275 REV B 15 LINGUA ITALIANA ...

Page 21: ...imizzare i rischi per persone e cose PERICOLO Le indicazioni di PERICOLO riportano caratteristiche e istruzioni fondamentali per la sicurezza delle persone L inosservanza di tali indicazioni può causare lesioni gravi o morte AVVERTIMENTO Le indicazioni di AVVERTIMENTO riportano caratteristiche e istruzioni fondamentali per la sicurezza delle persone L inosservanza di tali indicazioni può causare l...

Page 22: ...nuale e tutta la restante documentazione tecnica di supporto al prodotto devono essere conservati e possibilmente resi accessibili al personale nelle immediate vicinanze dell UPS Informazioni aggiuntive Nel caso le informazioni riportate nel presente manuale non fossero abbastanza esaurienti si prega di contattare il costruttore del dispositivo i cui dettagli sono disponibili alla sezione Contatti...

Page 23: ...ell eventualità in cui i nostri tecnici dovessero incorrere in tempo e o spese aggiuntive a causa di inaccessibilità del sito o sospensioni del lavoro richieste da parte del cliente tali oneri verranno fatturati in accordo alle condizioni di assistenza in uso nel paese di installazione Modalità richieste a In caso di guasto coperto da garanzia il cliente dovrà informare per scritto la Legrand del ...

Page 24: ...menti mancato funzionamento dell impianto di condizionamento etc mancato rispetto delle norme di sicurezza pertinenti forza maggiore per es fulmini sovratensioni calamità naturali incendi atti di guerra sommosse etc cadute o spostamenti dovuti ad installazione non corretta normale usura causata da un uso proprio e continuativo dell apparecchio b Sono inoltre esclusi dalla garanzia i dispositivi di...

Page 25: ...epita Ogni altro uso è da considerarsi improprio e quindi pericoloso Il Costruttore non può essere considerato responsabile per eventuali danni causati da usi impropri erronei ed irragionevoli Legrand si ritiene responsabile della macchina nella sua configurazione originale Qualsiasi intervento che alteri la struttura o il ciclo di funzionamento della macchina deve essere eseguito ed autorizzato d...

Page 26: ...ML46086 REV I 1 INSTALLATION AND START UP OF KEOR HPE UPS 60 160 KVA INSTALLATION ET DÉMARRAGE DE L ASI KEOR HPE 60 160 KVA INSTALLAZIONE E AVVIAMENTO UPS KEOR HPE 60 160 KVA Rev Descrizione Description Data Date Emesso Issued Approvato Approved Lingua Language Pagina Page di Pag of Pag I VR 11 2020 18 02 2020 R Soldani F Berti E F I 1 141 Codice Code OML46086 ...

Page 27: ...tion 16 2 3 6 Operation 17 2 3 7 Maintenance 18 2 3 8 Storage 19 2 4 ENVIRONMENTAL PROTECTION 19 2 4 1 ISO 14001 certification 19 2 4 2 Recycling of packing materials 19 2 4 3 Device disposal 19 3 INSTALLATION 20 3 1 RECEIPT OF THE UPS 20 3 1 1 Storage 20 3 2 HANDLING OF THE UPS 21 3 3 POSITIONING AND INSTALLATION 22 3 3 1 Base plan static load and weights 23 3 3 2 Overall dimensions clearances an...

Page 28: ...erator auxiliary contact 43 4 6 PROVISION FOR COLD START FUNCTION 43 4 7 SERIAL INTERFACES AND EXTERNAL CONNECTIONS 44 4 8 RELAY CARD CONNECTION OPTIONAL 45 5 STARTUP AND SHUTDOWN 46 5 1 PRELIMINARY CHECKS 46 5 2 START UP PROCEDURE 47 5 3 BASIC TROUBLESHOOTING 49 5 4 SHUT DOWN PROCEDURE 49 5 5 SWITCHING PROCEDURE TO MANUAL BYPASS 50 5 6 RESTART FROM MANUAL BYPASS 51 LANGUE FRANÇAIS 53 1 PORTEE 55 ...

Page 29: ...ATTERIES 72 4 RACCORDEMENT ELECTRIQUE 73 4 1 RACCORDEMENT DES CÂBLES D ALIMENTATION 74 4 2 DISPOSITIF DE PROTECTION CONTRE LE BACKFEED 76 4 3 BORNIERS 79 4 4 BATTERIES 80 4 4 1 Emplacement et conexion des batteries 81 4 4 1 1 7 9 11Ah 12V installation KEOR HPE 60 80 kVA 82 4 4 1 2 12 14Ah 12V battery installation KEOR HPE 60 80 kVA 84 4 5 RACCORDEMENT DES CABLES AUXILIAIRES 86 4 5 1 By pass manuel...

Page 30: ...one 103 2 3 4 Installazione 104 2 3 5 Collegamento elettrico 105 2 3 6 Funzionamento 106 2 3 7 Manutenzione 107 2 3 8 Immagazzinamento 108 2 4 TUTELA AMBIENTALE 108 2 4 1 Certificazione ISO 14001 108 2 4 2 Riciclaggio dei materiali di imballaggio 108 2 4 3 Smaltimento del dispositivo 108 3 INSTALLAZIONE 109 3 1 RICEZIONE DELL UPS 109 3 1 1 Immagazzinamento 109 3 2 MOVIMENTAZIONE DELL UPS 110 3 3 P...

Page 31: ...USILIARI 131 4 5 1 Bypass manuale esterno 131 4 5 2 Selettore NORMALE BYPASS esterno 131 4 5 3 Contatto ausiliario sezionatore uscita UPS esterno 132 4 5 4 Spegnimento remoto EPO 132 4 5 5 Contatto ausiliario sezionatore di batteria 132 4 5 6 Contatto ausiliario Generatore Diesel 132 4 6 PREDISPOSIZIONE PER COLD START 132 4 7 INTERFACCE SERIALI 133 4 8 COLLEGAMENTO SCHEDA RELÈ OPZIONALE 134 5 AVVI...

Page 32: ... front view 39 Picture 14 Trays 12 14Ah 12V battery lateral view 40 Picture 15 One raw 12 14Ah 12V battery top view 40 Picture 16 12 14Ah 12V battery connection tray top view 41 Picture 17 12 14Ah 12V battery connection tray front view 41 Picture 18 Auxiliary terminals of KEOR HPE 60 160 kVA 42 Picture 19 Position of the serial interfaces of KEOR HPE 60 160 kVA 44 Picture 20 Relay card terminals 4...

Page 33: ...ombro 113 Figura 5 Distanze di rispetto 113 Figura 6 Schema unifilare KEOR HPE 60 80kVA con collegamento al dispositivo esterno 122 Figura 6a Schema unifilare KEOR HPE 100kVA con collegamento al dispositivo esterno 122 Figura 6b Schema unifilare KEOR HPE 125 160kVA con collegamento al dispositivo esterno 123 Figura 7 Morsettiera KEOR HPE 60 80 kVA 124 Figura 8 Morsettiera KEOR HPE 100 125 160 kVA ...

Page 34: ...Installation and start up of KEOR HPE UPS 60 160 kVA Installation et démarrage de l ASI KEOR HPE 60 160 kVA Installazione e avviamento KEOR HPE UPS 60 160 kVA OML46086 REV I 9 ENGLISH LANGUAGE ...

Page 35: ...Installation and start up of KEOR HPE UPS 60 160 kVA Installation et démarrage de l ASI KEOR HPE 60 160 kVA Installazione e avviamento KEOR HPE UPS 60 160 kVA 10 OML46086 REV I ...

Page 36: ...E 60 kVA BSM46 KEOR HPE 80 kVA BSK93 KEOR HPE 100 kVA BSM47 KEOR HPE 125 kVA BSM48 KEOR HPE 160 kVA Storing documentation This manual and any other supporting technical documentation relating to the product must be stored and made accessible to personnel in the immediate vicinity of the UPS Further information In the event that the information provided in this manual is not sufficiently exhaustive...

Page 37: ...me to read the following manual The purpose of this manual is to give a short description of the parts composing the UPS and to guide the installer or the user through the installation of the unit in its using environment The installer or the user must read and correctly perform the instructions included in the present manual with particular reference to the requirements regarding safety in compli...

Page 38: ...KEOR HPE UPS 60 160 kVA is provided with an identification plate containing the operation ratings The plate is fixed in the inside of the UPS door Picture 1 Rating plate of KEOR HPE 60 160 kVA Check the technical characteristics Before carrying out any installation or start up operation on the UPS make sure its technical characteristics are compatible with the AC supply line and with the output lo...

Page 39: ...t regarding safety Such training and qualification shall be considered as such only when certified by the manufacturer 2 3 3 Transport and handling Avoid bending or deforming the components and altering the insulation distances while transporting and handling the product Undistributed weight The weight of the UPS is not uniformly distributed Pay attention when lifting Please inspect the device bef...

Page 40: ...tilation grates Never expose the device to direct sunlight or place it near a source of heat Special environmental conditions The UPS is designed for normal climatic and environmental operating conditions as defined in the technical specification altitude ambient operating temperature relative humidity and environmental transport and storage conditions It is necessary to implement specific protect...

Page 41: ...fication plate correspond to the AC power system and to the actual electrical consumption of all of the equipment connected Check the conformity to the Standards The UPS must be installed in compliance with the standards in force in the country of installation IT system The UPS is also designed to be connected to an IT power distribution system All the electrical connections must be carried out by...

Page 42: ...installations to which the UPS systems belong must comply with all the current safety standards technical equipment and accident prevention regulations The device can be started operated and disconnected only by authorized personnel The settings can only be changed using the original interface software Injury hazard due to electric shock During operation the UPS converts power characterized by hig...

Page 43: ...ter shutdown and disconnection from the supply sources due to the internal capacitors which discharge slowly Thus we recommend to wait at least 5 minutes before opening the device doors Injury hazard due to electric shock Any operation must be carried out only when voltage is absent and in compliance with safety directives Make sure the battery circuit breaker that may be placed near the battery h...

Page 44: ...emperature variations bad ventilation conductive or radiant heat from other sources fungus insects vermin 2 4 ENVIRONMENTAL PROTECTION 2 4 1 ISO 14001 certification Legrand is particularly sensitive to the environmental impact of its products That is why the UPS has been manufactured with cutting edge eco design criteria ISO 14001 certification Special care was taken in using fully recyclable mate...

Page 45: ...eed to be returned to the manufacturer please use the original package Danger to persons due to transport damages Mechanical damage to the electrical components constitutes a serious danger to persons and property In case of doubt regarding the non integrity of the package or of the product contained therein contact the manufacturer before carrying out the installation and or the start up 3 1 1 St...

Page 46: ...upright position During loading and unloading operations always respect the indications regarding the device barycentre marked on the package Before positioning the UPS in order to avoid risks of turnover it s recommended to move the system on the wood pallet on which the UPS is fixed Before the positioning in the final location remove the UPS from the pallet To handle the UPS remove the lower fro...

Page 47: ...ronmental conditions in the place of installation in compliance with the current legislation please refer to the Overall dimensions minimum distances from the walls and ventilation section Special environmental conditions It is necessary to implement specific protective measures in case of unusual environmental conditions harmful smoke dust abrasive dust humidity vapour salt air bad weather or dri...

Page 48: ...icture 3 Base plan The supporting base of the UPS must be designed to carry the UPS weight and to ensure its steady and safe support Its carrying capacity must be adequate to the static loads indicated in the table below Power kVA 60 80 100 125 160 Weight w o batteries kg 250 300 320 360 380 Static load w o batteries kg m2 490 590 630 710 750 Weight with batteries kg 800 850 Static load with batte...

Page 49: ...llation et démarrage de l ASI KEOR HPE 60 160 kVA Installazione e avviamento KEOR HPE UPS 60 160 kVA 24 OML46086 REV I 3 3 2 Overall dimensions clearances and ventilation INLET AIR OPENINGS OUTLET AIR OPENINGS Picture 4 Overall dimensions Picture 5 Clearances ...

Page 50: ...ces from the walls for all of the UPS sizes the same installation conditions apply as indicated in the table below UPS with internal batteries A mm B mm C mm D mm Recommended clearances 50 1200 600 600 Minimum clearances 0 1200 600 400 UPS with external battery cabinet A mm B mm C mm D mm Recommended clearances 50 1200 400 600 Minimum clearances 0 1200 0 400 The table below shows the air volume re...

Page 51: ...snow hail etc NO Water with an origin other than rain NO Ice formation NO Classification of biological conditions EN 60721 3 3 Environmental parameter Class 3B1 3B2 3B3 a Flora NO Presence of mildew fungus etc Presence of mildew fungus etc b Fauna NO Presence of rodents and other animals that are harmful to products excluding termites Presence of rodents and other animals that are harmful to produ...

Page 52: ...strictly monitored and regulated clean spaces category X Places where atmosphere is permanently monitored X Places located in rural and urban regions where industrial activities are few and where traffic is moderate X Places located in urban regions with industrial activities and or considerable traffic X Places in proximity to industrial sources with chemical emissions X Places located in industr...

Page 53: ...stallation instructions For battery installation please respect EN62040 1 strictly and follow the installation manual of the UPS To obtain the battery life indicated by the battery manufacturer the operating temperature must remain between 0 and 25 C However although the battery can operate up to 40 C there will be a significant reduction of the battery life To avoid the formation of any kind of p...

Page 54: ...ctions in compliance with the local standards Cables must be selected bearing in mind technical financial and safety aspects The selection and the sizing of cables from a technical viewpoint depend on the voltage on the current absorbed by the UPS on the bypass line and on the batteries on the ambient temperature and on the voltage drop Finally the kind of cable laying must be taken into particula...

Page 55: ...ing the UPS to the mains 4 1 CONNECTION OF THE POWER CABLES For the electric connection of the KEOR HPE UPS 60 160 kVA connect the following cables DC supply from the battery if the battery is external AC supply from the rectifier and bypass supply mains AC output to the loads Injury hazard due to electric shock Very high voltages are present at the ends of the cables coming from the battery Isola...

Page 56: ... can house two parallel conductors provided they are terminated with pin connectors The sections given in the table above are indicative only The cables have been designed according to the standard CEI UNEL35024 1 using the following data 70 C rated PVC copper cables ambient temperature equal to 40 C maximum length of the cables equal to 30 m voltage drop 0 5 cables laid in cavities of structures ...

Page 57: ...tion using a MCCB equipped with a shunt trip coil and connected to UPS applying the wiring diagram principle described in Figure 6 6a 6b In case of backfeed failure detected by the UPS the UPS will send a signal to trip the MCCB to isolate the UPS in order to protect the upstream distribution circuits The installer shall apply the following warning label on all primary power isolator that supplies...

Page 58: ...émarrage de l ASI KEOR HPE 60 160 kVA Installazione e avviamento KEOR HPE UPS 60 160 kVA OML46086 REV I 33 Picture 6 Single Line Diagram KEOR HPE 60 80kVA with connection to external device Picture 6a Single Line Diagram KEOR HPE 100kVA with connection to external device ...

Page 59: ...EOR HPE UPS 60 160 kVA Installation et démarrage de l ASI KEOR HPE 60 160 kVA Installazione e avviamento KEOR HPE UPS 60 160 kVA 34 OML46086 REV I Picture 6b Single Line Diagram KEOR HPE 125 160kVA with connection to external device ...

Page 60: ... Installazione e avviamento KEOR HPE UPS 60 160 kVA OML46086 REV I 35 4 3 TERMINAL BOARDS The KEOR HPE UPS 60 160 kVA is provided with terminal boards for the connection of power cables and of auxiliary connections Picture 7 Terminal board KEOR HPE 60 80 kVA Picture 8 Terminal board KEOR HPE 100 125 160 kVA ...

Page 61: ... The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply circuit Batteries installation For battery installation please respect the prescriptions of the EN62040 1 standard paragraph 7 6 To obtain the battery life indicated by the battery manufacturer the operating te...

Page 62: ...ith original type CAUTION do not dispose of batteries in fire The battery may explode CAUTION do not open or mutilate batteries Released electrolyte is harmful to the skin and eyes It may be toxic CAUTION do not dump the exhausted batteries in the environment 4 4 1 Battery connection and positioning Battery voltage After the battery installation before closing BCB check the battery voltage on the ...

Page 63: ...0 160 kVA 38 OML46086 REV I 4 4 1 1 7 9 11Ah 12V installation KEOR HPE 60 80 kVA 1 Remove the six screws to open the left right lateral cover and access the battery trays total trays are 6 and each contain three rows of 10 batteries see picture 10 11 Picture 10 Trays 7 9 11Ah 12V battery lateral view Picture 11 One raw 7 9 11Ah 12V battery top view ...

Page 64: ... 39 2 Install the batteries received in a separate packages and install it in accordance with the picture 12 and picture 13 Picture 12 7 9 11Ah 12V battery connection tray top view Picture 13 7 9 11Ah 12V battery connection tray front view 3 After the connection re insert the battery trays on the internal of UPS 4 Put back and fix the left right cover with the four screws ...

Page 65: ...L46086 REV I 4 4 1 2 12 14Ah 12V battery installation KEOR HPE 60 80 kVA 1 Remove the six screws to open the left right lateral cover and access the battery trays total trays are 6 and each contain two rows of 7 batteries and one rows of 6 batteries see picture 14 15 Picture 14 Trays 12 14Ah 12V battery lateral view Picture 15 One raw 12 14Ah 12V battery top view ...

Page 66: ...I 41 2 Install the batteries received in a separate packages and install it in accordance with the picture 16 and picture 17 Picture 16 12 14Ah 12V battery connection tray top view Picture 17 12 14Ah 12V battery connection tray front view 3 After the connection re insert the battery trays on the internal of UPS 4 Put back and fix the left right cover with the four screws ...

Page 67: ...liary contacts of the external switches MBCB BCB and OCB if provided must be mandatorily connected to the UPS Picture 18 Auxiliary terminals of KEOR HPE 60 160 kVA 4 5 1 External manual bypass Auxiliary contact of the external Manual Bypass Switch if provided on terminals X10 1 2 A normally open contact is required when the contact is closed see Manual Bypass procedure the microprocessor will acqu...

Page 68: ...nals 7 8 4 5 5 Battery auxiliary contact Battery auxiliary contact on terminals X10 9 10 This auxiliary contact is necessary to indicate the position of the isolator open closed 4 5 6 Diesel Generator auxiliary contact Auxiliary contact from the Diesel Generator on terminals X10 11 12 A normally open contact must be used the contact must close when the diesel generator is operating The microproces...

Page 69: ...ASS SELECTOR SNMP OPTIONAL it is used for the external transmission of data via LAN COMMON BATTERY it is used for the communication between in common battery configuration RS232 USB it is used for connection to the proprietary programming and control software MODBUS OPTIONAL it is used for the transmission of data to the outside via MODBUS RTU protocol RS485 THERMAL PROBE it is used to acquire the...

Page 70: ...tus M1 Led Pins Status in normal operation Name Status in normal operation RL1 Alarm A30 COMMON ALARM Not energized if alarm is present 2 3 Closed DL1 On 1 2 Open RL2 Alarm A1 MAINS FAULT Not energized if alarm is present 5 6 Closed DL2 On 4 5 Open RL3 Alarm A9 BATTERY AUT END Not energized if alarm is present 8 9 Closed DL3 On 7 8 Open RL4 Alarm A13 INV OUT OF TOL Not energized if alarm is presen...

Page 71: ...ts section External isolators All the procedures that follow make reference to the external isolator BCB and are only valid if such device is installed externally and its auxiliary contacts properly wired to the UPS terminals 5 1 PRELIMINARY CHECKS Before starting up the unit make sure that all installation and electric connection works have been performed professionally all power and control cabl...

Page 72: ...minals on board the UPS This will allow the control logic to acquire the status of the switches and guide the operator during the start up and manual bypass procedures No LCD DISPLAY ACTION OPERATING CHECKS 1 BLANK Close RCB After operating switch RCB the pre charging phase of the capacitive bank will start The control logic will be started and the front panel is activated 2 BOOT LOADER BOOT phase...

Page 73: ... START UP PLEASE WAIT The control logic checks that all the bypass parameters voltage phase rotation frequency are correct LED 2 is lit green bypass voltage present 11 BATTERY START UP CLOSE BCB Close BCB 12 BATTERY START UP PLEASE WAIT The control logic checks the closing of the circuit breaker to go to the following step Led 4 lit green 13 UPS START UP CLOSE OCB Close OCB 14 START UP END PLEASE ...

Page 74: ...ep 2 the unit shows the alarm A15 Byp fault Make sure the switch SBCB is closed Check the protection fuses of the static bypass switch they are inside the unit Check the phase rotation of the bypass voltage Make sure voltage and frequency are within tolerance 4 After step 3 the unit shows the alarm A7 BCB open Make sure you have closed the battery circuit breaker the circuit breaker or the fuse ho...

Page 75: ...annot be guaranteed to the loads No ACTION LCD DISPLAY OPERATING CHECKS 1 Move the bypass selector SW to BYPASS A30 GENERAL ALARM The load is transferred to the bypass line LED 5 off LED 6 lit orange 2 Close MBCB A30 GENERAL ALARM The inverter is switched off The load is supplied by the input mains through the manual bypass switch The static bypass switch is still closed Led 8 lit orange 3 Open BC...

Page 76: ...the start up conditions are good for restart Led 1 lit green Led 8 lit orange 5 RECTIFIER START UP WAIT PLEASE The IGBT rectifier bridge starts to modulate VDC voltage reaches the nominal value LED 3 is lit green DC voltage present 6 START UP FROM MBCB CLOSE SBCB Close SBCB 7 BYPASS START UP WAIT PLEASE The microprocessor checks that all the bypass parameters voltage phase rotation frequency are w...

Page 77: ...PE UPS 60 160 kVA 52 OML46086 REV I 12 START UP FROM MBCB MOVE BYP SWITCH Move the selector NORMAL BYPASS to NORMAL The load is transferred to the inverter Led 5 lit green 13 START UP END WAIT PLEASE The microprocessor checks that all the output parameters voltage current frequency are within the tolerance limits 14 UPS MODEL OUTPUT VOLTAGE ...

Page 78: ...Installation and start up of KEOR HPE UPS 60 160 kVA Installation et démarrage de l ASI KEOR HPE 60 160 kVA Installazione e avviamento KEOR HPE UPS 60 160 kVA OML46086 REV I 53 LANGUE FRANÇAIS ...

Page 79: ...Installation and start up of KEOR HPE UPS 60 160 kVA Installation et démarrage de l ASI KEOR HPE 60 160 kVA Installazione e avviamento KEOR HPE UPS 60 160 kVA 54 OML46086 REV I ...

Page 80: ...essous BLS46 KEOR HPE 60 kVA BSM46 KEOR HPE 80 kVA BSK93 KEOR HPE 100 kVA BSM47 KEOR HPE 125 kVA BSM48 KEOR HPE 160 kVA Ce manuel ainsi que les autres documentations techniques relatives à ce produit doivent être stockés et mis à disposition du personnel à proximité immédiate de l ASI Si les informations fournies dans le présent manuel ne sont pas suffisamment complètes veuillez contacter le fabri...

Page 81: ... suggérons de lire attentivement le présentmanuel L objectif de ce manuel est de vous fournir une brève description des éléments composant l ASI et de vous guider dans l installation de l unité dans son environnement d utilisation L installateur ou l utilisateur devra lire et respecter les instructions fournies dans le présent manuel en particulier les exigences relatives à la sécurité conformémen...

Page 82: ...VA est fourni avec une plaque signalétique indiquant ses valeurs nominales de fonctionnement Cette plaque est apposée sur la face intérieure de la porte Illustration 1 Plaque signalétique de l ASI KERO HPE 60 160 kVA Avant toute opération d installation ou de démarrage de l ASI assurez vous que ses caractéristiques techniques sont compatibles avec l alimentation CA et les charges en sortie Vérifie...

Page 83: ...tégralité de ce manuel en particulier les exigences relatives à la sécurité La formation et les qualifications du personnel ne seront considérées comme valides que si elles ont été certifiées par le fabricant 2 3 3 Transport et manutention Évitez de tordre ou de déformer les composants ainsi que de modifier les distances d isolement lors du transport et de la manutention du produit Le poids d un A...

Page 84: ... placé à proximité d une source de chaleur L ASI est conçu pour des conditions de fonctionnement environnementales et climatiques normales telles que définies dans les caractéristiques techniques altitude température ambiante de fonctionnement humidité relative et conditions environnementales de transport et de stockage Il est nécessaire de mettre en œuvre des mesures de protection spécifiques en ...

Page 85: ...ndent au système d alimentation CA et à la consommation électrique réelle de tous les équipements raccordés L ASI doit être installé conformément à la réglementation nationale en vigueur L ASI est également conçu pour être raccordé sur un système d alimentation inormatique Tous les raccordements électriques doivent être réalisés par un personnel autorisé Avant tout raccordement de l appareil vérif...

Page 86: ...rmes de sécurité en vigueur réglementations relatives aux équipements techniques et à la prévention des accidents L appareil ne peut être mis en marche utilisé et déconnecté que par un personnel autorisé Lorsqu il fonctionne l ASI convertit des puissances caractérisées par des tensions et courants élevés Toutes les portes et tous les capots doivent rester fermés La batterie fournie avec l ASI cont...

Page 87: ...ion des sources d alimentation du fait de la décharge lente des condensateurs internes Nous recommandons par conséquent de patienter au moins 5 minutes avant d ouvrir les portes de l appareil Toute opération doit être réalisée uniquement en l absence de tension et dans le respect des directives de sécurité Assurez vous que le disjoncteur de la batterie qui peut se trouver à proximité de celle ci e...

Page 88: ...mauvaise ventilation chaleur conduite ou rayonnante en provenance d autres sources moisissures insectes nuisibles 2 4 PROTECTION DE L ENVIRONNEMENT 2 4 1 Certification ISO 14001 Legrand est particulièrement sensible à l impact de ses produits sur l environnement C est pourquoi l ASI est fabriqué en tenant compte de critères d éco conception de pointe certification ISO 14001 Une attention spéciale ...

Page 89: ...emballaged origine Les dommages mécaniques subis par les composants électriques constituent un grave danger pour les personnes et les biens En cas de doute concernant l intégrité de l emballage ou du produit contactez le fabricant avant toute installation et ou démarrage 3 1 1 Stockage L emballage protège normalement l appareil de l humidité et des éventuels dommages pouvant se produire pendant le...

Page 90: ... déchargement respectez toujours les indications concernant le barycentre de l appareil qui figurent surl emballage Avant de positionner l onduleur et afin d éviter les risques de bascules il est recommandé de déplacer le système sur la palette de bois sur lequel l onduleur est fixé Avant le positionnement dans l emplacement final retirer l onduleur de la palette Pour manipuler l onduleur supprime...

Page 91: ...nstallation qui doivent être conformes à la législation en vigueur veuillez vous reporter à la section Ventilation Il est nécessaire de mettre en œuvre des mesures de protection spécifiques en cas de conditions environnementales inhabituelles fumées dangereuses poussières poussières abrasives humidité vapeur air à forte teneur en sel mauvaises conditions météorologiques ou aspersion d eau mélange ...

Page 92: ...tion 3 Plan de base Le sol soutenant l ASI doit être conçue pour supporter le poids de l ASI et assurer un maintien sûr et stable Sa capacité de soutien doit correspondre aux charges statiques indiquées dans le tableau ci dessous Puissance kVA 60 80 100 125 160 Poids des batteries kg 250 300 320 360 380 Charge statique sans les batteries kg m2 490 590 630 710 750 Poids avec les batteries kg 800 85...

Page 93: ...e de l ASI KEOR HPE 60 160 kVA Installazione e avviamento KEOR HPE UPS 60 160 kVA 68 OML46086 REV I 3 3 2 Dimensions totales dégagement minimum et ventilation OVERTURES D ENTRÉE D AIR OVERTURES DE SORTIE D AIR Illustration 4 Dimensions globales Illustration 5 Dégagement minimum ...

Page 94: ...les mêmes conditions d installation telles qu indiquées dans le tableau ci dessous s appliquent quelle que soit la taille de l ASI ASI avec batteries internes A mm B mm C mm D mm Dégagements recommandés 50 1200 600 600 Dégagement minimum 0 1200 600 400 ASI avec batteries externes A mm B mm C mm D mm Dégagements recommandés 50 1200 400 600 Dégagement minimum 0 1200 0 400 La table ci dessous indique...

Page 95: ... provenant d une source autre que la pluie NON Formation de glace NON Classification des conditions biologiques EN 60721 3 3 Agent d environnement Classe 3B1 3B2 3B3 a Flore NON Présence de moisissures champignons etc Présence de moisissures champignons etc b Faune NON Présence de rongeurs et d autres animaux nuisibles aux produits hors termites Présence de rongeurs et d autres animaux nuisibles a...

Page 96: ...eillée et régulée de manière stricte catégorie des espaces propres X Sites sur lesquels l atmosphère est surveillée en permanence X Sites situés dans des régions rurales et urbaines présentant une faible activité industrielle et un trafic modéré X Sites situés dans des régions urbaines présentant une activité industrielle et ou un trafic important X Sites à proximité de sources industrielles d émi...

Page 97: ...a terre Pour l installation de la batterie respecter strictement la norme EN62040 1 2 et suivez le manuel d installation de l ASI Pour obtenir la durée de vie de la batterie indiquée par le fabricant de la batterie la température de fonctionnement doit rester comprise entre 0 et 25 C Cependant bien que la batterie puisse fonctionner jusqu à 40 C il y aura une réduction significative de la durée de...

Page 98: ...e technique dépendent de la tension du courant absorbé par l ASI de la ligne de by pass et des batteries de la température ambiante et de la chute de tension Enfin la façon de poser les câbles doit également faire l objet d une attention particulière Pour plus d explications concernant le choix et le dimensionnement des câbles reportez vous aux normes CEI concernées en particulier la norme CEI 64 ...

Page 99: ...ATION Pour le raccordement électrique de l ASI KEOR HPE 60 160 kVA les câbles suivants doivent être raccordés Alimentation CC depuis la batterie Alimentation CA depuis le secteur avec redresseur et by pass Sortie CA vers les charges Les câbles doivent être protégés contre les courts circuits et les courants de fuite à la terre Les points de raccordement doivent être scellés hermétiquement afin d é...

Page 100: ...calcul selon chaque installation Les sections données dans le tableau ci dessus sont à titre indicatif uniquement Les câbles ont été conçus conformément à la norme CEI UNEL35024 1 en utilisant les données suivantes câbles en cuivre PVC cotés 70 C température ambiante égale à 40 C longueur maximale des câbles égale à 30 m chute de tension 0 5 câbles placés dans les cavités de structures ou chemins ...

Page 101: ...lenchement à émission raccordé à l ASI suivant le schéma de principe décrit Illustration 6 6a 6b En cas de défaut de retour de tension de l ASI l ASI enverra un signal de déclenchement au disjoncteur pour isoler l ASI et ainsi protéger les circuits de distribution amont L installateur doit appliquer le marquage d avertissement suivant sur tous les isolateurs alimentant l ASI qui sont installés à d...

Page 102: ...e avviamento KEOR HPE UPS 60 160 kVA OML46086 REV I 77 Illustration 6 Diagramme à une ligne KEOR HPE 60 80kVA avec connexion à un périphérique externe Illustration 6a Diagramme à une ligne KEOR HPE 100kVA avec connexion à un périphérique externe Câbles non fournis par le constructeur Câbles non fournis par le constructeur ...

Page 103: ...tallation et démarrage de l ASI KEOR HPE 60 160 kVA Installazione e avviamento KEOR HPE UPS 60 160 kVA 78 OML46086 REV I Illustration 6b Diagramme à une ligne KEOR HPE 125 160kVA avec connexion à un périphérique externe Câbles non fournis par le constructeur ...

Page 104: ... UPS 60 160 kVA OML46086 REV I 79 4 3 BORNIERS L ASI KEOR HPE 60 160 kVA est fourni avec des borniers permettant le raccordement des câbles d alimentation et les raccordements auxiliaires Illustration 7 Borniers KEOR HPE 60 80 kVA Illustration 8 Borniers KEOR HPE 100 125 160 kVA ENTRÉE REDRESSEUR SORTIE DE L ASI ENTRÉE DRESSEUR SORTIE DE L ASI ...

Page 105: ...de telles mises à la terre sont supprimées durant l installation ou la maintenance appliquable aux équipements et alimentations à base de batteries ne nécessitant pas d avoir un circuit d alimentation relié à la terre Pour l installation de la batterie respecter strictement la norme EN62040 1 2 et suivez le manuel d installation de l ASI Pour obtenir la durée de vie de la batterie indiquée par le ...

Page 106: ...N ne pas mettre les batteries au feu La batterie peutexploser ATTENTION ne pas ouvrir ou dégrader les batteries L electrolyte libéré est nocif pour la peau et les yeux ATTENTION ne pas décharger les batteries dansl environnement 4 4 1 Emplacement et conexion des batteries Après l installation de la batterie avant de fermer le BCB vérifier la tension de la batterie sur le disjoncteur du BCB Dans le...

Page 107: ...ouvrir le couvercle latéral gauche droit et accéder aux bacs à batterie Les plateaux totaux sont 6 et contiennent chacun trois rangées de 10 batteries voir illustration 10 et 11 Illustration 10 Plateau 7 9 11Ah 12V vue latérale de la batterie Illustration 11 Un range 7 9 11Ah 12V batterie vue de dessus PLATEAU 1 Rangées 1 to 3 PLATEAU 2 Rangées 4 to 6 PLATEAU 3 Rangées 7 to 9 PLATEAU 4 Rangées 10 ...

Page 108: ...vec les quatre vis AU FUSIBLE DE LA BATTERIE NèGATIF AU FUSIBLE DE LA BATTERIE NèGATIF AU FUSIBLE DE LA BATTERIE NèGATIF BATTERIE NEUTRE BATTERIE NEUTRE BATTERIE NEUTRE BATTERIE NEUTRE BATTERIE NEUTRE BATTERIE NEUTRE AU FUSIBLE DE LA BATTERIE POSITIF AU FUSIBLE DE LA BATTERIE POSITIF AU FUSIBLE DE LA BATTERIE POSITIF AU FUSIBLE DE LA BATTERIE NèGATIF AU FUSIBLE DE LA BATTERIE NèGATIF AU FUSIBLE DE...

Page 109: ...pour ouvrir le couvercle latéral gauche droit et accéder aux bacs à batterie Les plateaux totaux sont 6 et contiennent chacun trois rangées de 7 batteries voir illustration 14 et 15 Illustration 14 Plateau 12 14Ah 12V vue latérale de la batterie Illustration 15 Un range 12 14Ah 12V batterie vue de dessus PLATEAU 1 Rangées 1 to 3 PLATEAU 2 Rangées 4 to 6 PLATEAU 3 Rangées 7 to 9 PLATEAU 4 Rangées 1...

Page 110: ...tre vis AU FUSIBLE DE LA BATTERIE NèGATIF AU FUSIBLE DE LA BATTERIE NèGATIF AU FUSIBLE DE LA BATTERIE POSITIF AU FUSIBLE DE LA BATTERIE POSITIF BATTERIE NEUTRE BATTERIE NEUTRE BATTERIE NEUTRE BATTERIE NEUTRE LIEN D INTERCONNEXION LIEN D INTERCONNEXION LIEN D INTERCONNEXION LIEN D INTERCONNEXION PLATEAU 3 PLATEAU 1 PLATEAU 4 PLATEAU 6 PLATEAU 2 PLATEAU 5 PLATEAU PLATEAU PLATEAU PLATEAU PLATEAU AU F...

Page 111: ...B BCB et OCB lorsqu ils ne sont pas fournis sur la carte doivent être obligatoirement connectés à l ASI Illustration 18 Bornes auxiliaires du KEOR HPE 60 160 kVA 4 5 1 By pass manuel externe Contact auxiliaire du commutateur de by pass manuel externe sur les bornes X10 1 2 Un contact normalement ouvert est exigé à la fermeture du contact voir Procédure de by pass manuel le microprocesseur détecte ...

Page 112: ...les bornes 7 8 4 5 5 Contact auxiliaire de batterie Contat auxiliaire de batterie bornes X10 9 10 Ce contact auxiliaire est nécessaire pour indiquer la position de l isolateur ouvert fermé 4 5 6 Contact auxiliaire du Groupe electrogène Contact auxiliaire du Groupe electrogène des bornes X10 11 12 Un contact normalement ouvert doit être utilisé le contact doit être fermé quand le groupe electrogène...

Page 113: ...BYPASS SELECTEUR SNMP OPTIONNEL utilisé pour les transmission externes de données viaLAN COMMON BATTERY utilisé pour la communication entre des ASI en COMMON BATTERY RS232 USB il est utilisé pour la connexion de la programmation exclusive et le lgiciel de contrôle MODBUS OPTIONNEL utilisé pour la transmission de données vers l extérieur via le protocole MODBUS RUT RS485 SONDE THERMIQUE utilisé pou...

Page 114: ...Statuts en fonctionnement normal Nom Statuts en fonctionnement normal RL1 Alarme A30 ALARME GENERALE Hors tension si alarme présente 2 3 Fermé DL1 On 1 2 Ouvert RL2 Alarme A1 DEFAUT SECTEUR Hors tension si alarme présente 5 6 Fermé DL2 On 4 5 Ouvert RL3 Allarme A9 FIN AUTONOMIE BATTERIE Hors tension si alarme présente 8 9 Fermé DL3 On 7 8 Ouvert RL4 Alarme A13 ONDULEUR EN DEHORS DES TOLERANCES Hor...

Page 115: ... dispositifs sont installés en externe et leurs contacts auxiliaires proprement connectés au bornier de l ASI 5 1 VERIFICATIONS PRELIMINAIRES Avant de démarrer l unité assurez vous que tous les travaux d installation et de raccordement électrique ont été réalisés de manière professionnelle tous les câbles d alimentation et de commande sont correctement raccordés et serrés sur les borniers correspo...

Page 116: ...que de commande d acquérir l état des commutateurs et de guider l opérateur lors des procédures de mise en route et de bypass manuel No AFFICHEUR LCD ACTION VÉRIFICATIONS DE FONCTIONNEMENT 1 VIDE Fermer le RCB Quelques secondes après la fermeture du disjoncteur d entrée RCB la phase de pré charge de la banque de condensateurs commence La logique de contrôle démarre et le panneau avant est activé 2...

Page 117: ...S START UP CLOSE SBCB Démarrage du by pass Fermer le SBCB Fermer le SBCB 10 BYPASS START UP WAIT PLEASE Démarrage du by pass Veuillez patienter La logique de contrôle vérifie que tous les paramètres du by pass tension rotation de phases fréquence sont corrects La LED 2 est allumée en vert tension by pass présente 11 BATTERY START UP CLOSE BCB Démarrage de la batterie Fermer le BCB Fermer BCB 12 BA...

Page 118: ...émarrage et affiche un ou plusieurs messages d alarme Vérifiez les alarmes indiquées à l écran et résolvez lesproblèmes Fermez RCB et essayez de redémarrer l ASI 3 Après l étape n 2 l unité affiche l alarme A15 Byp fault Défaut duby pass Assurez vous que le commutateur SBCB soit fermé Vérifiez les fusibles de protection du commutateur de by pass statique qui se trouvent à l intérieur de l unité Vé...

Page 119: ...D VÉRIFICATIONS DE FONCTIONNEMENT 1 Ouvrir OCB A30 GENERAL ALARM L alimentation de la charge est coupée La LED 7est éteinte 2 Ouvrir BCB A30 GENERAL ALARM La batterie est déconnectée du redresseur La LED 4 est rouge clignotante 3 Ouvrir SBCB A30 GENERAL ALARM L alimentation du bypass est déconnectée La LED 2 est éteinte 4 Ouvrir S2 A30 GENERAL ALARM Redresseur et onduleur sont coupés 5 BLANK Fin d...

Page 120: ...e sélecteur de by pass SW sur BYPASS A30 GENERAL ALARM A30 Alarme générale La charge est transférée sur la ligne de by pass La LED 5 est éteinte la LED 6 est allumée en orange 2 Fermer MBCB A30 GENERAL ALARM A30 Alarme générale L onduleur est arrêté La charge est alimentée par le secteur via le commutateur de by pass manuel Le commutateur de by pass statique reste fermé La LED 8 est allumée en ora...

Page 121: ... Toutes les LED du panneau avant sont éteintes 4 UPS START UP WAIT PLEASE Démarrage de l ASI Veuillez patienter Le redresseur est alimenté et la tension CC atteint sa valeur nominale Toutes les LED du panneau avant sont allumées Le microprocesseur vérifie que toutes les conditions de démarrage sont bonnes pour le redémarrage La LED 1 est allumée en vert La LED 8 est allumée en orange 5 RECTIFIER S...

Page 122: ...BCB Ouvrir MBCB La charge est alimentée par le commutateur de by pass statique et l onduleur peut être démarré La LED 8 est éteinte 11 INVERTER START WAIT PLEASE Démarrage de l onduleur Veuillez patienter La modulation du pont de l onduleur démarre La tension CA atteint sa valeur nominale Le microprocesseur vérifie la synchronisation avec la ligne de by pass 12 START UP FROM MBCB MOVE BYP SWITCH D...

Page 123: ...Installation and start up of KEOR HPE UPS 60 160 kVA Installation et démarrage de l ASI KEOR HPE 60 160 kVA Installazione e avviamento KEOR HPE UPS 60 160 kVA 98 OML46086 REV I LINGUA ITALIANA ...

Page 124: ...Installation and start up of KEOR HPE UPS 60 160 kVA Installation et démarrage de l ASI KEOR HPE 60 160 kVA Installazione e avviamento KEOR HPE UPS 60 160 kVA OML46086 REV I 99 ...

Page 125: ... KEOR HPE 80 kVA BSK93 KEOR HPE 100 kVA BSM47 KEOR HPE 125 kVA BSM48 KEOR HPE 160 kVA Conservazione della documentazione Questo manuale e tutta la restante documentazione tecnica di supporto al prodotto devono essere conservati e possibilmente resi accessibili al personale nelle immediate vicinanze dell UPS Informazioni aggiuntive Nel caso le informazioni riportate nel presente manuale non fossero...

Page 126: ...are il tempo per la lettura del seguente manuale Lo scopo di questo manuale è di descrivere brevemente le parti che compongono l UPS e di guidare l installatore o l utente ad una corretta installazione dell apparato nell ambiente di utilizzo L installatore o l utente dovrà leggere ed eseguire correttamente quanto dichiarato nel presente manuale con particolare riguardo alle richieste relative alla...

Page 127: ... una targhetta di identificazione che riporta i dati nominali di funzionamento La targhetta è fissata nella parte interna della porta frontale Figura 1 Targhetta caratteristiche KEOR HPE 60 160 kVA Verificare le caratteristiche tecniche Prima di effettuare qualsiasi operazione di installazione e avviamento del dispositivo verificare che le caratteristiche tecniche siano compatibili con la rete di ...

Page 128: ...o da considerarsi tali solo se certificati dall azienda produttrice 2 3 3 Trasporto e movimentazione Durante il trasporto e la movimentazione del prodotto prestare la massima attenzione al fine di evitare di piegare o deformare le parti componenti e di modificare le distanze di isolamento Peso non distribuito Il peso dell UPS non è uniformemente distribuito Prestare particolare attenzione nel soll...

Page 129: ...on sottoporre il dispositivo all esposizione diretta dei raggi solari e non posizionarlo in prossimità di una fonte di calore Condizioni ambientali particolari L UPS è progettato per sopportare condizioni climatiche ed ambientali di esercizio normali come indicato nella specifica tecnica altitudine temperatura ambiente d esercizio umidità relativa condizioni ambientali di trasporto e stoccaggio Si...

Page 130: ...trica di alimentazione ed al consumo elettrico reale della totalità delle apparecchiature collegate Verificare la conformità alle normative L UPS deve essere installato conformemente alle normative vigenti nel paese di installazione Sistema IT L apparecchiatura è stata progettata anche per essere collegata ad un sistema di distribuzione dell alimentazione IT Tutti i collegamenti elettrici devono e...

Page 131: ... parte gli UPS devono seguire tutte le norme vigenti riguardanti la sicurezza equipaggiamenti tecnici e regolamenti antinfortunistici Il dispositivo deve essere avviato manovrato e disconnesso solamente da parte di personale autorizzato Le tarature possono essere modificate solo utilizzando il software di interfaccia originale Pericolo di lesioni a seguito shock elettrico Durante il funzionamento ...

Page 132: ...l eventuale disconnessione dalle sorgenti di alimentazione a causa dei condensatori interni che si scaricano lentamente Si consiglia quindi di attendere almeno 5 minuti prima di aprire le porte del dispositivo Pericolo di lesioni a seguito shock elettrico Eventuali interventi devono essere effettuati solamente in assenza di tensione e nel rispetto delle direttive sulla sicurezza Accertarsi di aver...

Page 133: ...ione calore condotto o irradiato proveniente da altre fonti funghi insetti nocivi parassiti 2 4 TUTELA AMBIENTALE 2 4 1 Certificazione ISO 14001 Legrand è particolarmente sensibile all impatto ambientale dei propri prodotti per questo motivo l UPS è stato realizzato seguendo i più moderni criteri di eco progettazione certificazione ISO 14001 E stata prestata particolare attenzione nell utilizzo di...

Page 134: ...l costruttore si prega di utilizzare l imballaggio originale Pericolo per le persone a seguito di danni da trasporto Il danneggiamento meccanico dei componenti elettrici costituisce un grave pericolo per persone e cose Qualora si abbia il dubbio di una non completa integrità dell imballo o del prodotto entro ad esso contenuto contattare l azienda produttrice prima di effettuare l installazione e o...

Page 135: ...a Durante le manovre di carico e scarico rispettare sempre le indicazioni relative al baricentro del dispositivo contrassegnato sull imballaggio Per gli spostamenti dell UPS prima del posizionamento finale si consiglia di non rimuoverlo dal pancale in legno sul quale è fissato per evitare eventuali rischi di ribaltamento Prima del posizionamento rimuovere l UPS dal pancale togliendo le staffe di f...

Page 136: ... condizioni ambientali nel luogo di installazione in accordo alle normative correnti fare riferimento alla sezione Dimensioni di ingombro distanze minime dalle pareti e ventilazione Condizioni ambientali particolari Si rende necessario mettere in atto misure di protezione specifiche in caso di condizioni ambientali insolite fumi nocivi polveri polvere abrasiva umidità vapore aria salina intemperie...

Page 137: ... di base La base di appoggio dell UPS deve essere progettata per sopportare il peso del dispositivo e per garantirne il supporto saldo e sicuro La capacità portante deve essere conforme ai carichi statici indicati nella tabella seguente Potenza kVA 60 80 100 125 160 Peso senza batterie kg 250 300 320 360 380 Carico statico senza batterie kg m2 490 590 630 710 750 Peso con batterie kg 800 850 Caric...

Page 138: ...e de l ASI KEOR HPE 60 160 kVA Installazione e avviamento KEOR HPE UPS 60 160 kVA OML46086 REV I 113 3 3 2 Dimensioni di ingombro distanze minime dalle pareti e ventilazione APERTURE INGRESSO ARIA USCITA INGRESSO ARIA Figura 4 Dimensioni di ingombro Figura 5 Distanze di rispetto ...

Page 139: ... le stesse condizioni di installazione per quanto riguarda le distanze minime dalle pareti come indicate nella tabella seguente UPS con batterie interne A mm B mm C mm D mm Distanze raccomandate 50 1200 600 600 Distanze minime 0 1200 600 400 UPS con batterie esterne A mm B mm C mm D mm Distanze raccomandate 50 1200 400 600 Distanze minime 0 1200 0 400 La tabella seguente mostra il volume d aria ri...

Page 140: ... origine diversa dalla pioggia NO Formazione di ghiaccio NO Classificazione delle condizioni biologiche EN 60721 3 3 Parametro ambientale Classe 3B1 3B2 3B3 c Flora NO Presenza di muffa funghi ecc Presenza di muffa funghi ecc d Fauna NO Presenza di roditori e altri animali dannosi ai prodotti escludendo le termiti Presenza di roditori e altri animali dannosi ai prodotti includendo le termiti Class...

Page 141: ...era strettamente monitorata e controllata categoria camera pulita X Luoghi con atmosfera continuamente controllata X Luoghi posti in zone rurali e urbane dove sono modeste le attività industriali e il traffico è moderato X Luoghi in zone urbane con attività industriali e o grande traffico X Luoghi posti in prossimità di sorgenti industriali con emissioni chimiche X Luoghi posti all interno di inst...

Page 142: ... a terra Seguire le istruzioni d installazione Per l installazione delle batterie attenersi rigorosamente alle EN62040 1 inoltre dovrà essere seguito il manuale di installazione dell UPS Per ottenere una durata di vita della batteria pari a quella indicata dal costruttore la temperatura di esercizio deve essere compresa fra 0 e 25 C La batteria può comunque operare fino a 40 C con forte riduzione ...

Page 143: ...tta tenendo in considerazione gli aspetti tecnici economici e di sicurezza La scelta e il dimensionamento dei cavi dal punto di vista tecnico è funzione della tensione della corrente assorbita dall UPS dalla rete bypass e dalle batterie della temperatura ambiente e della caduta di tensione infine si deve tenere in particolare considerazione il tipo di posa del cavo Ulteriori chiarimenti sulla scel...

Page 144: ...a rete 4 1 COLLEGAMENTO CONDUTTORI DI POTENZA Per il collegamento elettrico dell UPS KEOR HPE 60 160 kVA è necessario allacciare i seguenti conduttori Alimentazione DC da batteria se la batteria è esterna Alimentazione AC dalla rete di alimentazione raddrizzatore e bypass Uscita AC verso i carichi Pericolo di lesioni a seguito shock elettrico Sono presenti tensioni molto elevate ai capi dei cavi p...

Page 145: ...arallelo che siano terminati con capocorda a puntale Le sezioni dei cavi indicate nella tabella precedente sono indicative I cavi sono stati dimensionati in accordo alla norma CEI UNEL35024 1 utilizzando i seguenti dati cavi unipolari in rame con isolamento in PVC e temperatura massima di 70 C temperatura ambiente pari a 40 C massima lunghezza dei cavi pari a 30 m caduta di tensione 0 5 posa dei c...

Page 146: ...otato di una bobina a lancio di corrente e collegata all UPS secondo lo schema elettrico riportato in Figura 6 In caso di guasto di backfeed rilevato dall UPS l UPS invierà alla bobina un segnale di 230 Vac impulsivo che farà trippare il MCCB quindi isolerà l UPS al fine di proteggere i circuiti di distribuzione a monte dell UPS L installatore deve applicare la seguente etichetta su tutti i dispos...

Page 147: ...marrage de l ASI KEOR HPE 60 160 kVA Installazione e avviamento KEOR HPE UPS 60 160 kVA 122 OML46086 REV I Figura 6 Schema unifilare KEOR HPE 60 80kVA con collegamento al dispositivo esterno Figura 6a Schema unifilare KEOR HPE 100kVA con collegamento al dispositivo esterno ...

Page 148: ...OR HPE UPS 60 160 kVA Installation et démarrage de l ASI KEOR HPE 60 160 kVA Installazione e avviamento KEOR HPE UPS 60 160 kVA OML46086 REV I 123 Figura 6b Schema unifilare KEOR HPE 125 160kVA con collegamento al dispositivo esterno ...

Page 149: ...nstallazione e avviamento KEOR HPE UPS 60 160 kVA 124 OML46086 REV I 4 3 MORSETTIERE L UPS KEOR HPE 60 160 kVA è provvisto di morsettiere per l allacciamento dei cavi di potenza e delle connessioni ausiliarie Figura 7 Morsettiera KEOR HPE 60 80 kVA Figura 8 Morsettiera KEOR HPE 100 125 160 kVA INGRESSO BYPASS ...

Page 150: ...una scossa elettrica La probabilità può essere ridotta se i collegamenti di terra vengono interrotti durante l installazione e la manutenzione applicabile ad apparecchiature e ad alimentazioni a batteria poste a distanza prive di circuito di alimentazione messo a terra Installazione batterie Per l installazione delle batterie attenersi rigorosamente alle EN62040 1 paragrafo 7 6 Per ottenere una du...

Page 151: ...IONE non avvicinare la batteria a sorgenti di calore La batteria potrebbe esplodere ATTENZIONE non aprire il contenitore delle batterie L elettrolito rilasciato è pericoloso per la pelle e per gli occhi Può essere tossico ATTENZIONE non gettare le batterie esauste nell ambiente 4 4 1 Connessione batterie interne Tensione di batteria Dopo l installazione delle batterie senza chiudere BCB controllar...

Page 152: ...46086 REV I 127 4 4 1 1 Installazione batterie 7 9 11Ah 12V KEOR HPE 60 80kVA 1 Rimuovere le sei viti per aprire il pannello laterale destro sinistro e accedere ai vassoi batterie Totale vassoi 6 e ognuno è composto da tre file di batterie Fig 10 11 Figura 10 Vassoi batterie 7 9 11Ah 12V vista laterale Figura 11 Fila singola batterie 7 9 11Ah 12V vista dall alto ...

Page 153: ...re the batterie ricevute in imballo separato come da figure 12 e 13 Figura 12 7 9 11Ah 12V connessione vassoi batterie vista dall alto Figura 13 7 9 11Ah 12V connessione vassoi batterie vista frontale 3 Dopo aver effttuato tutte le connessioni reinserire i vassoi batterie all interno dell UPS 4 Richiudere e fissare il laterale destro sinistro con le quattro viti utilizzate in precedenza ...

Page 154: ...L46086 REV I 129 4 4 1 2 Installazione batterie 12 14Ah 12V KEOR HPE 60 80kVA 1 Rimuovere le sei viti per aprire il pannello laterale destro sinistro e accedere ai vassoi batterie Totale vassoi 6 e ognuno è composto da tre file di batterie Fig 14 15 Figura 14 Vassoi batterie 12 14Ah 12V vista laterale Figura 15 Fila singola batterie 12 14Ah 12V vista dall alto ...

Page 155: ...are le batterie ricevute in imballo separato come da figure 16 e 17 Figura 16 12 14Ah 12V connessione vassoi batterie vista dall alto Figura 17 12 14Ah 12V connessione vassoi batterie vista frontale 3 Dopo aver effettuato tutte le connessioni reinserire i vassoi batterie all interno dell UPS 4 Richiudere e fissare il laterale destro sinistro con le quattro viti utilizzate in precedenza ...

Page 156: ...esel I cavi ausiliari sono connessi ad una morsettiera dedicata con morsetti per cavo fino a 4 mm2 Contatti ausiliari OCB MBCB BCB I contatti ausiliari degli interruttori MBCB BCB e OCB esterni se previsti devono obbligatoriamente essere collegati all UPS Figura 18 Morsetti ausiliari KEOR HPE 60 160 kVA 4 5 1 Bypass manuale esterno Contatto ausiliario dell interruttore di bypass manuale esterno se...

Page 157: ... di inverter e di bypass si aprono togliendo alimentazione ai carichi Nel caso il pulsante di arresto di emergenza esterno non sia previsto cortocircuitare i morsetti 7 8 4 5 5 Contatto ausiliario sezionatore di batteria Contatto ausiliario del sezionatore di Batteria morsetti X10 9 10 Contatto ausiliario necessario per l indicazione della posizione del sezionatore aperto chiuso 4 5 6 Contatto aus...

Page 158: ...er la trasmissione dei dati all esterno via LAN BATTERIA UNICA utilizzata per la comunicazione tra UPS in configurazione BATTERIA UNICA RS232 USB utilizzata per il collegamento con software proprietario di programmazione e controllo MODBUS OPZIONALE utilizzata per la trasmissione dei dati all esterno per mezzo di protocollo MODBUS RUT RS485 SONDA TERMICA utilizzata per l acquisizione della tempera...

Page 159: ... Led Pin Stato in funzionamento normale Nome Stato in funzionamento normale RL1 Allarme A30 ALLARME GENERALE Non energ se allarme presente 2 3 Chiuso DL1 On 1 2 Aperto RL2 Allarme A1 MANCANZA RETE Non energ se allarme presente 5 6 Chiuso DL2 On 4 5 Aperto RL3 Allarme A9 FINE AUT BATTERIA Non energ se allarme presente 8 9 Chiuso DL3 On 7 8 Aperto RL4 Allarme A13 INV FUORI TOL Non energ se allarme p...

Page 160: ... Tutte le procedure che seguono fanno riferimento al dispositivo di interruzione BCB e sono valide solamente se tale dispositivo è installato esternamente e i suoi contatti ausiliari opportunamente cablati agli appositi morsetti nell UPS 5 1 VERIFICHE PRELIMINARI Prima di iniziare la procedura di avvio verificare che tutti i lavori di installazione e allacciamento elettrico siano stati eseguiti a ...

Page 161: ...i di bypass manuale uscita e batteria che vanno collegati agli appositi morsetti sull UPS In questo modo la logica di controllo acquisisce lo stato degli interruttori per guidare l operatore durante le procedure di avvio e bypass manuale No DISPLAY LCD AZIONE CONTROLLI OPERATIVI 1 SPENTO Chiudere RCB Alla chiusura del sezionatore RCB inizia la fase di precarica del banco capacitivo con l avvio del...

Page 162: ... chiusura statico SSI 9 AVVIO BYPASS CHIUDI SBCB Chiudere SBCB 10 AVVIO BYPASS ATTENDERE PREGO La logica di controllo verifica che tutti i parametri di bypass tensione senso ciclico frequenza siano corretti LED 2 acceso verde presenza tensione Bypass 11 AVVIO BATTERIA CHIUDI BCB Chiudere BCB 12 AVVIO BATTERIA ATTENDERE PREGO La logica di controllo verifica la chiusura dell interruttore per passare...

Page 163: ...PS mostra l allarme A15 Byp non disp Verificare di aver chiuso il sezionatore SBCB Controllare I fusibili di protezione static switch Bypass sono installati all interno dell UPS Controllare il senso ciclico della tensione di Bypass Controllare che la tensione e la frequenza siano in tolleranza 8 Dopo lo step 3 l UPS mostra l allarme A7 BCB aperto Verificare di aver chiuso interruttore di batteria ...

Page 164: ...ione sui carichi No AZIONE DISPLAY LCD CONTROLLI OPERATIVI 1 Muovere il selettore Bypass_SW su BYPASS A30 ALLARME GENERALE Il carico viene trasferito sulla linea di bypass LED 5 spento LED 6 acceso arancio 2 Chiudere MBCB A30 ALLARME GENERALE L inverter viene spento Il carico viene alimentato dalla rete d ingresso tramite l interruttore di bypass manuale L interruttore statico di bypass è ancora c...

Page 165: ...annello frontale sono accesi Il microprocessore controlla che tutte le condizioni di avvio siano buone per il riavvio LED 1 accesi verdi LED 8 acceso arancio 5 AVVIO RADDRIZZATORE ATTENDERE PREGO Il ponte Raddrizzatore ad IGBT inizia a modulare la tensione VDC viene portata al valore nominale accensione del LED 3 acceso verde presenza tensione DC 6 AVVIO DA MBCB CHIUDERE SBCB Chiudere SBCB 7 AVVIO...

Page 166: ...nte inverter e la tensione AC viene portata al valore nominale Il microprocessore controlla la sincronizzazione con la linea di by pass 12 AVVIO DA MBCB MUOVERE BYP SWITCH Muovere il selettore NORMAL BYPASS su NORMAL Il carico è trasferito sotto inverter LED 5 acceso verde 13 AVVIO TERMINATO ATTENDERE PREGO Il microprocessore controlla che tutti i parametri di uscita tensione corrente frequenza si...

Page 167: ...ISATEUR DE L ASI UTILIZZO DELL UPS Index Indice ENGLISH LANGUAGE 9 1 SCOPE 11 2 SAFETY RULES AND WARNINGS 12 3 GENERAL UPS DESCRIPTION 13 3 1 TYPOLOGY 13 3 2 SYSTEM DESCRIPTION 13 3 2 1 Rectifier 13 3 2 2 Inverter 14 3 2 3 Battery and battery charger 14 3 2 4 Static bypass 14 3 2 5 Manual bypass 14 3 3 OPERATING STATUS 15 3 3 1 Normal operation 15 3 3 2 Green Conversion 15 3 3 3 Bypass operation 1...

Page 168: ... 2 Alarms and operating status 30 6 SETTINGS AND ADVANCED OPERATIONS 32 6 1 SETTING DATE AND TIME 34 6 2 DISPLAY LANGUAGE SETTING 34 6 3 NEW BATTERY INSTALLATION 34 6 4 BATTERY CONFIGURATION 34 6 5 SETTING THE MODBUS PARAMETERS 36 6 6 UPS TEST 36 6 7 BATTERY TEST 37 6 8 SYSTEM RESET 37 6 9 ALARMS HISTORY RESET 38 7 SYSTEM INFORMATION 39 7 1 PARALLEL OPERATION INFORMATION 40 7 1 1 UPS position 40 7...

Page 169: ...U SYSTÈME 63 3 2 1 Redresseur 63 3 2 2 Onduleur 64 3 2 3 Batterie et chargeur de batterie 64 3 2 4 By pass statique 64 3 2 5 Bypass manuel 64 3 3 ÉTAT DE FONCTIONNEMENT 65 3 3 1 Fonctionnement normal 65 3 3 2 Conversion Green 65 3 3 3 Fonctionnement en by pass 66 3 3 4 Fonctionnement sur batterie 67 3 3 5 Bypass manuel 67 3 4 DISPOSITIFS DE CONTROLE ET DE FONCTIONNEMENT 69 3 4 1 Sectionneurs d iso...

Page 170: ...BATTERIE 87 6 8 RÉINITIALISATION DU SYSTÈME 87 6 9 REMISE A ZERO DE L HISTORIQUE DES ALARMES 89 7 INFORMATIONS SYSTÈME 90 7 1 INFORMATIONS SUR LE FONCTIONNEMENT EN PARALLELE 91 7 1 1 Position de l ASI 91 7 1 2 Hiérarchie maitre esclave 91 7 1 3 Surveillance du bus de communication 92 7 1 4 Type de système parallèle 92 7 1 5 Statistiques relatives aux messages 93 7 2 INFORMATIONS SUR LE FONCTIONNEM...

Page 171: ...nto da bypass 118 3 3 4 Funzionamento da batteria 118 3 3 5 Bypass manuale 119 3 4 COMANDI E ORGANI DI MANOVRA 121 3 4 1 Sezionatori 121 3 4 2 Comando di arresto di emergenza EPO 122 3 4 3 Selettore Normale Bypass 122 3 4 4 Pannello di comando LCD 122 4 PANNELLO FRONTALE 123 4 1 TASTI FUNZIONE 124 4 2 LED DEL SINOTTICO 125 4 3 BARRA LED 126 5 GESTIONE DEL PANNELLO LCD 127 5 1 MENU PRINCIPALI 127 5...

Page 172: ...MENTO IN PARALLELO 142 7 1 1 Posizione dell UPS 142 7 1 2 Priorità Master Slave 142 7 1 3 Controllo bus di comunicazione 143 7 1 4 Tipo di parallelo 143 7 1 5 Statistiche messaggi 144 7 2 INFORMAZIONI SUL FUNZIONAMENTO IN PARALLELO RADDRIZZATORE 144 7 2 1 Posizione dell UPS 144 7 2 2 Priorità Master Slave 144 7 2 3 Controllo bus di comunicazione 145 7 2 4 Tipo di parallelo 145 7 2 5 Statistiche me...

Page 173: ...cture of INFO menu 39 Illustration 1 Schéma bloc 63 Illustration 2 Fonctionnement normal 65 Illustration 3 Green Conversion 65 Illustration 4 Charge alimentée par bypass 66 Illustration 5 Fonctionnement sur batterie 67 Illustration 6 Bypass manuel pour vérification fonctionnelle 67 Illustration 7 By pass manuel pour réparations ou maintenance 68 Illustration 8 Panneau avant de l ASI 71 Illustratio...

Page 174: ...e funzionali 119 Figura 7 By pass manuale per manutenzione o riparazione 120 Figura 8 Pannello frontale UPS 123 Figura 9 Sinottico UPS 125 Figura 10 Barra LED 126 Figura 11 Struttura menu MISURE 1 di 2 128 Figura 12 Struttura menu MISURE 2 di 2 129 Figura 13 Struttura menu allarmi 130 Figura 14 Struttura menu SPECIALE 134 Figura 15 Struttura menu INFO 141 ...

Page 175: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMG38225 REV F 9 ENGLISH LANGUAGE ...

Page 176: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 10 OMG38225 REV F ...

Page 177: ...100 kVA BSM47 KEOR HPE 125 kVA BSM10 KEOR HPE 160 kVA Storing documentation This manual and any other supporting technical documentation relating to the product must be stored and made accessible to personnel in the immediate vicinity of the UPS Further information In the event that the information provided in this manual is not sufficiently exhaustive please contact the manufacturer of the device...

Page 178: ...ned in the manuals must be strictly followed Injury hazard due to device failure Potentially hazardous situations may arise in case of UPS failure Do not use the device if visibly damaged Maintain the device regularly to identify possible failure Possible device damage Whenever work is carried out on the device make sure all actions are taken in order to avoid electrostatic discharges which might ...

Page 179: ... line or the plugs supplied by the UPS making the User aware of this fact Picture 1 Block diagram The UPS uses IGBT technology with a high switching frequency in order to allow a low distortion of the current re injected into the supply line as well as high quality and stability of output voltage The components used assure high reliability very high efficiency and maintenance easiness 3 2 SYSTEM D...

Page 180: ...ic is completely integrated in the rectifier s control electronics The battery is charged according to the DIN 41773 Standard every time it has been partially or completely discharged When its full capacity is restored it is disconnected from the DC bus by means of a static switch in order to save energy reduce the stress due to the AC ripple thus increasing the lifetime This operating mode is cal...

Page 181: ...the inverter and compensates mains voltage as well as load variations keeping the DC voltage constant At the same time it provides to charge the battery The inverter converts the DC voltage into an AC sine wave with stabilized voltage and frequency and also supplies the load via its static switch SSI Picture 2 Normal operation 3 3 2 Green Conversion During the operation in Green Conversion mode th...

Page 182: ...s Lost capacity 20 Additional charge for 96 hours Such values complies with the recommendations of the main battery manufacturers Set the right battery capacity The UPS front panel allows the setting of the battery parameters including the rated capacity Considering the importance that such value assumes for the correct execution of the charge control algorithm it is highly recommended to verify t...

Page 183: ...stem restart from the black out condition can be customized based on the requirements of the plant in three different modes Bypass loads are supplied as soon as the bypass line is available factory configuration Inverter loads are supplied by the inverter even if the bypass line is available when the battery voltage has reached a programmed threshold after the rectifier restart Man Inverter the ou...

Page 184: ...auxiliary contacts Carry out a proper electrical installation by wiring the auxiliary contacts of the manual bypass and output isolators to the dedicated terminals on board the UPS This will allow the control logic to acquire the status of the switches and guide the operator during the start up and manual bypass procedures For further information refer to the section Installation and start up Duri...

Page 185: ...The use of the operation and control devices of the UPS is intended for authorized personnel only We recommend to check the training of the personnel responsible for the use and maintenance of the system 3 4 1 Isolators The isolators provided on the UPS are used to isolate the power components of the device from the AC supply line from the storage battery and from the load Voltage present on termi...

Page 186: ...d you are sure that there is no hazard to persons and things 3 4 3 Normal Bypass selector It is used during the manual bypass procedure when it is necessary to isolate the UPS for maintenance or repair Follow the procedures contained in the manual The Normal Bypass selector shall only be operated in accordance with the procedures specified in the installation and start up section The manufacturer ...

Page 187: ... OMG38225 REV F 21 4 FRONT PANEL The front panel of the UPS consisting of four rows alphanumeric display plus 5 function keys allows the complete monitoring of the UPS status The mimic flow helps to understand the operating status of the UPS Picture 8 UPS front panel ...

Page 188: ... 5 buttons whose functions are indicated in the following table Button Assigned functions Scrolls up the menus Increases the values by one unit Selects a value Scrolls down the menus Decreases the values by one unit Selects a value Selects a menu Confirms changes Silences the buzzer activated due to an alarm or a failure Returns to the previous menu ...

Page 189: ...GREEN Battery discharging or under TEST ORANGE Circuit breaker BCB open RED Battery fault following a battery test OFF Battery not available LED 5 GREEN Inverter voltage within tolerance and static switch closed GREEN Inverter overload or short circuit OFF Inverter off or voltage out of tolerance LED 6 ORANGE Re transfer blocked ORANGE Static bypass switch closed OFF Static bypass switch open LED ...

Page 190: ... charging ORANGE Battery discharging or under TEST fast blinking ORANGE Circuit breaker BCB open slow blinking RED End of battery autonomy Battery fault LED 13 GREEN Inverter voltage within tolerance and static switch closed ORANGE Inverter overload or short circuit RED Inverter critical alarm OFF Inverter off LED 14 GREEN AC bypass line within tolerance RED Wrong phase rotation fast blinking RED ...

Page 191: ... UPS NAME Main screen nominal power of the UPS xxx kVA UPS NAME UPS measures regarding basic parameters voltage current etc MEASURES UPS NAME UPS operating status possible alarms present and alarms history ALARMS UPS NAME Setting of parameters and special functions SPECIAL UPS NAME General information regarding the UPS INFO ...

Page 192: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 26 OMG38225 REV F 5 2 MEASURE DISPLAY The MEASURES menu is structured as follows Picture 11 Structure of MEASURES menu 1 of 2 ...

Page 193: ...ent 3 1 A Frequency 0 1 Hz Active power 1 kW Apparent power 1 kVA Load percentage 1 BYPASS Voltage 1 2 1 V Frequency 0 1 Hz INVERTER Voltage 1 2 1 V Frequency 0 1 Hz AC DC Rectifier output voltage 1 V BATTERY Voltage and current 1 V 1 A Nominal capacity 1 Ah Residual autonomy 1 min 1 1 The voltage measures are always referred to the phase to neutral value 2 The three voltages are displayed in one ...

Page 194: ...he ALARMS menu automatically whenever an alarm occurs The audible indicator if enabled is activated to show the occurred failure The audible alarm is silenced pressing the key BUZZER UPS STATUS Display of the first alarm present if no alarm is present the operating status is displayed alarm status no 1 UPS STATUS Press the key to browse the menu and to go to the next alarm status in alphabetical o...

Page 195: ...g the oldest event The quantity of stored events is displayed on the first line xxx yyy which contains the data currently displayed position in the list and the total number of stored data maximum number equal to 500 respectively An asterisk indicates the automatic reset of the alarm HISTORY 001 015 Latest event stored in order of time E g automatic reset of alarm A3 BOOSTER STOPPED A3 26 10 10 20...

Page 196: ...WR SEQ A46 PAR LOST REDUND A15 BYPASS FAULT A47 SEND PARAM ERROR A16 BYPASS LOAD A48 RCV PARAM ERROR A17 RETRANSFER BLOCK A49 TEST MODE ERROR A18 MBCB CLOSED A51 BATT TEMPERATURE A19 OCB OPEN A52 UNDER VOLTAGE LOCKOUT A20 OVERLOAD A53 FIRMWARE ERROR A21 THERMAL IMAGE A54 CAN ERROR A22 BYPASS SWITCH A55 PAR CABLE DISC A23 EPO PRESSED A56 MAINS UNBALANCE A24 HIGH TEMPERATURE A59 BACKFEED RELAY ON A2...

Page 197: ... ALARMS STATUSES menu is entered The alarms are shown when they are present and must be silenced with the buzzer The alarms remain displayed whilst they are present and they are automatically stored in the event log with date and time Description of alarms and statuses For a more detailed description of the alarms and statuses see the Faults and alarms section of the present manual ...

Page 198: ... utilisateur de l ASI Utilizzo dell UPS 32 OMG38225 REV F 6 SETTINGS AND ADVANCED OPERATIONS Some operating parameters of the UPS can be set via the SPECIAL menu which is structured as follows Picture 14 Structure of SPECIAL menu ...

Page 199: ...s a battery test NEW BATTERY INSTALL Sets autonomy to 100 RESET HISTORY Event log reset MODBUS MODBUS address of device RESET RUNNING HOURS Reset the hour counter related to the UPS running time Password protected access The SETTINGS menu is protected by a password set by the factory in order to prevent access to unauthorized personnel We recommend minimum disclosure of the access password Changes...

Page 200: ... parameters are changed via the arrow buttons to increase the digits and the button is used to confirm the entry 6 3 NEW BATTERY INSTALLATION The NEW BATTERY INSTALLATION menu is used in case battery circuit breaker BCB is not closed when requested in the start up phase In this case the system will start considering the battery completely discharged and activating the alarm A10 BATTERY FAULT To se...

Page 201: ...reen of the parameter set YES BAT RECHAR CURR SET The single digits can be modified via the arrow keys and confirmed by pressing ENTER 18 CONFIRM RECHAR CURR Confirmation screen of the parameter set YES AUTONOMY BAT SETTING The single digits can be modified via the arrow keys and confirmed by pressing ENTER 0020 CONFIRM AUTON BATT Confirmation screen of the parameter set YES SAVE BATT SETTINGS Con...

Page 202: ...e modified via the arrow keys and confirmed by pressing ENTER 202 Parameter Standard Range MODBUS ADDRESS 1 1 247 6 6 UPS TEST The UPS TEST menu allows to carry out a switching test of the inverter The inverter is switched off and the load is transferred to the bypass supply The inverter supply is automatically restored after a few seconds UPS TEST The value on the second line is ready to be chang...

Page 203: ...ssible loss of supply This test can affect the continuity of supply to the loads if the battery is not fully charged 6 8 SYSTEM RESET The UPS is equipped with internal protections which block the system or some of its sections The alarm can be cleared and normal operation can be resumed via the RESET menu In case the failure persists the UPS will return to the previous failure condition In some ca...

Page 204: ...ol loop error alarm A43 Static switch blocked alarm A50 Booster shutdown due to the operation of the load symmetry sensor alarm A33 Activation of the battery fault alarm alarm A10 Scheduled maintenance request alarm A29 For a description of the UPS status in each of the failure conditions listed above please refer to the Faults and alarms section 6 9 ALARMS HISTORY RESET Access the RESET HISTORY m...

Page 205: ...formation regarding the UPS based on the structure indicated below Picture 15 Structure of INFO menu All data shown in the various sections are set by the factory via a special interface software and cannot be altered except by personnel authorized by the manufacturer The only adjustable parameters are the MODBUS settings see SPECIAL menu ...

Page 206: ...ng technical service RUNNING HOURS Dates related to hours number of UPS running time 1 the menu is only active if the UPS belongs to a Parallel or Load Sync system 2 the menu is only active if the UPS belongs to a common battery system 7 1 PARALLEL OPERATION INFORMATION The PARALLEL menu is only active if the UPS belongs to a parallel or load sync system 7 1 1 UPS position PARALLEL 2 6 The first n...

Page 207: ...PS units UPS2 is currently the MASTER UPS we are checking the data communication on UPS3 UPS4 is not communicating The menu will be as shown below PARALLEL 1 S 2 M 3 S 4 In case there are more than four paralleled devices the menu will be as follows PARALLEL 1 S 2 M 3 S The dots indicate the presence of a further menu which shows the status of the other UPS units in the system 7 1 4 Parallel type ...

Page 208: ...he number will only increase on the SLAVE UPS units CAN STATISTICS INV MSG RX 9277 99 9 Number of messages received and percentage of reception accuracy regarding the status of the system The messages are exchanged between all the UPS units therefore the number will increase on all of them 7 2 PARALLEL RECTIFIER OPERATION INFORMATION The PARALLEL menu is only active if the UPS belongs to a paralle...

Page 209: ...y number X For example in a system composed of 2 UPS units REDUNDANT 1 means that only one of the UPS units is sufficient to feed the load 7 2 5 Message statistics The statistics section regarding the messages exchanged on the communication buses consists of two different menus CAN STATISTICS RAD SYNC RX 15849 100 0 Number of messages received and percentage of reception accuracy regarding the syn...

Page 210: ...BYPASS FAULT 1x UPS STATUS The other alarms present are displayed by scrolling the menu A30 COMMON ALARM UPS STATUS After the last alarm present the operating statuses are displayed S1 BOOSTER OK Injury hazard due to electric shock Before carrying out any operation on the UPS make sure that all the safety precautions are adhered to Any work on the unit must be carried out by qualified personnel In...

Page 211: ...ion The inverter is ready to feed the load Status S4 INVERTER LOAD Description The inverter feeds the load Operating condition The load is fed via the static inverter switch Status S5 INV BYPASS SYNC Description The inverter is synchronized with the bypass Operating condition The synchronization between the inverter and the bypass is locked and the static switch can change over from one source to ...

Page 212: ... is in standby mode Operating condition The inverter is off and ready to be started in case of anomaly of the bypass mains Status S12 BATT STANDBY NOT AVAILABLE Description The battery is in standby mode Operating condition The battery static switch is open and the battery is disconnected from the DC bus Status S14 BATT CHARGE I Description The battery is charging Operating condition The battery s...

Page 213: ...he phase rotation 2 If the alarm persists contact our Technical Support Service Alarm A3 BOOSTER STOPPED Description The rectifier has been temporarily disconnected and the inverter is fed by the battery Possible causes Instability of the AC line voltage or frequency Possible fault in the rectifier control circuit Solutions 1 Check the parameters of the AC line voltage 2 Restart the device 3 If th...

Page 214: ...of the battery Possible causes A battery test has been started automatically if set or manually by the user Solutions 1 Wait for the test to end and check possible battery faults Alarm A7 BCB OPEN Description The battery isolator is open Possible causes Battery isolator open Solutions 1 Check the status of the battery isolator 2 Check the functionality of the auxiliary contact of the isolator 3 Ch...

Page 215: ...attery 2 Reset the system 3 If the alarm persists contact our Technical Support Service Alarm A11 SHORT CIRCUIT Description The current sensor has detected a short circuit at the output Possible causes Load problem Measuring circuit failure Solutions 1 Check the loads connected to the UPS output 2 If the alarm persists contact our Technical Support Service Alarm A12 STOP TIMEOUT SC Description Inv...

Page 216: ...f power cables Solutions 1 Check the phase rotation 2 If the alarm persists contact our Technical Support Service Alarm A15 BYPASS FAULT Description The voltage or frequency of the bypass line are out of tolerance Possible causes Bypass line instability or failure Wrong phase rotation Solutions 1 Check the connections to the mains 2 Check the stability of mains voltage 3 If the alarm persists cont...

Page 217: ...ual bypass isolator 2 Check the functionality of the auxiliary contact of the isolator 3 If the alarm persists contact our Technical Support Service Alarm A19 OCB OPEN Description The output isolator is open Possible causes Output isolator open Solutions 1 Check the status of the output isolator 2 Check the functionality of the auxiliary contact of the isolator 3 If the alarm persists contact our ...

Page 218: ...chnical Support Service Alarm A23 EPO PRESSED Description The system is blocked due to the activation of the emergency power off button Possible causes Activation of the local or remote emergency power off button Solutions 1 Release the emergency power off button and reset the alarm 2 If the alarm persists contact our Technical Support Service Alarm A24 HIGH TEMPERATURE Description High temperatur...

Page 219: ...controller has detected an error in the parameters stored in EEPROM Possible causes Wrong parameters entered during programming Solutions 1 Contact our Technical Support Service Alarm A28 CRITICAL FAULT Description An alarm has been activated which causes the shutdown of part of the UPS rectifier inverter static switch Possible causes System failure Solutions 1 Check which alarms are present and c...

Page 220: ...D Description The system is blocked due to the activation of the emergency power off button Possible causes Activation of the local or remote emergency power off button Solutions 1 Release the emergency power off button and reset the alarm 2 If the alarm persists contact our Technical Support Service Alarm A33 ASYMMETRIC LOAD Description The positive and negative voltages measured on the DC capaci...

Page 221: ...ation of the protection sensor as a result of sudden DC voltage variations Possible causes Battery fault Solutions 1 Check the battery 2 Reset the system 3 If the alarm persists contact our Technical Support Service Alarm A38 INV LOAD Description The load is fed by the inverter This alarm is active for UPS systems in ECO mode where the preferential supply is from the bypass line Possible causes Te...

Page 222: ... The continuity is not guaranteed in case of failure of one of the rectifiers Possible causes The total load exceeds the maximum allowed value Possible failure on the measuring circuit Solutions 1 Verify the load supplied by the system 2 If the alarm persists contact our Technical Support Service Alarm A44 DESATURATION NOT AVAILABLE Description The inverter is blocked due to the operation of the d...

Page 223: ... Contact our Technical Support Service Alarm A48 RCV PARAM ERROR Description Internal error Possible causes Microcontroller communication problems Solutions 1 Contact our Technical Support Service Alarm A49 TEST MODE ERROR Description Internal error Possible causes Microcontroller communication problems Solutions 1 Contact our Technical Support Service Alarm A51 BATT TEMPERATURE Description The ba...

Page 224: ...unication problems Solutions 1 Contact our Technical Support Service Alarm A55 PAR CABLE DISC Description Parallel cable doesn t communicate Possible causes Parallel cable disconnected or damaged Solutions 1 Check the connection of cable 2 Contact our Technical Support Service Alarm A56 MAINS UNBALANCE Description The rectifier input voltage is unbalanced Possible causes Problems on the LV or MV d...

Page 225: ...ssible causes Voltage spike on the AC mains Possible internal fault Solutions 1 Check the mains voltage 2 If the alarm persists contact our Technical Support Service Alarm A63 START SEQ BLOCK Description During the UPS start up a failure prevented the proper execution of the sequence Possible causes Control devices in wrong position or operated improperly Possible internal fault Solutions 1 Make s...

Page 226: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 60 OMG38225 REV F LANGUE FRANÇAIS ...

Page 227: ...00 kVA BSM47 KEOR HPE 125 kVA BSM47 KEOR HPE 160 kVA Ce manuel ainsi que les autres documentations techniques relatives à ce produit doivent êtres stockés et mis à disposition du personnel à proximité immédiate de l ASI Si les informations fournies dans le présent manuel ne sont pas suffisamment complètes veuillez contacter le fabricant de l appareil dont les coordonnées sont indiquées dans la sec...

Page 228: ...ions potentiellement dangereuses peuvent découler d une défaillance de l ASI N utilisez pas l appareil s il est visiblement endommagé Entretenez régulièrement l appareil afin d identifier les éventuellesdéfaillances Lorsqu une intervention est réalisée sur l appareil assurez vous que toutes les mesures nécessaires sont prises afin d éviter des décharges électrostatiques susceptibles d endommager l...

Page 229: ...ignaler à l utilisateur Illustration 1 Schéma bloc L ASI utilise la technologie IGBT à haute fréquence d inversion afin de permettre une faible distorsion du courant réinjecté dans la ligne d alimentation ainsi qu une qualité et une stabilité élevées de la tension en sortie Les composants utilisés assurent une haute fiabilité une très haute efficacité et une facilité de maintenance 3 2 DESCRIPTION...

Page 230: ...ée à l électronique de contrôle du redresseur La batterie est chargée conformément à la norme DIN 41773 chaque fois qu elle a été partiellement ou complètement déchargée Lorsque sa pleine capacité est restaurée elle est maintenue en charge flottante afin de compenser l autodécharge réduire les contraintes dues à l ondulation résiduelle du courant alternatif et ainsi augmenter sa durée de vie Ce mo...

Page 231: ...mente l onduleur et compense les variations du secteur et de la charge assurant une tension CC constante Dans le même temps il maintient la batterie chargée chargement flottant ou boost en fonction du type de batterie L onduleur convertit la tension CC en onde sinusoïdale CA avec tension et fréquence stabilisées tout en alimentant la charge via son commutateur statique SSI Illustration 2 Fonctionn...

Page 232: ...e du DC bus Capacité perdue 10 Charge additionnelle pour 12 heures Capacité perdue entre 10 et 20 Charge additionnelle pour 48 heures Capacité perdue 20 Charge additionnelle pour 96 heures Ces valeurs sont conformes aux recommandations des principaux fabricants de batteries Le panneau avant de l onduleur permet de régler les paramètres de la batterie y compris la capacité nominale Compte tenu de l...

Page 233: ...e le redresseur recharge la batterie Dans la configuration standard les charges sont réalimentées via le commutateur statique SSB lorsque le secteur est à nouveau opérationnel L onduleur est redémarré une fois que la capacité de la batterie a été partiellement restaurée Les conditions de redémarrage du système après une panne totale peuvent être personnalisées en fonction des exigences du site dan...

Page 234: ...de l interrupteur de sortie sur le bornier de l ASI dédié à cet effet Cela permettra à la logique de commande d accéder à l état des interrupteurs et de guider l opérateur lors de la mise en route des procédures de démarrage et de bypass manuel Pour de plus amples renseignements veuillez consulter la section Installation et démarrage En cas de by pass manuel pour une intervention de réparation ou ...

Page 235: ...ifs de fonctionnement et de contrôle de l ASI est réservée au personnel autorisé uniquement Nous vous recommandons de vérifier la formation du personnel en charge de l utilisation et de la maintenance du système 3 4 1 Sectionneurs d isolation Les sectionneurs d isolation qui équipent l ASI sont utilisés afin d isoler les composants de puissance de l appareil de la ligne d alimentation CA de la bat...

Page 236: ... Il est utilisé lors de la procédure de by pass manuel lorsqu il est nécessaire d isoler l ASI pour une intervention de maintenance ou de réparation Le sélecteur normal by pass doit être utilisé conformément aux procédures indiquées dans la section relative à l installation et au démarrage Le fabricant ne pourra être tenu responsable des dommages liés à une utilisation incorrecte 3 4 4 Panneau de ...

Page 237: ...PANNEAU AVANT Le panneau avant de l ASI composé d un affichage alphanumérique à deux lignes et de 5 touches de fonction permet la surveillance complète de l état del ASI Le tableau à schéma permet de mieux comprendre l état de fonctionnement de l ASI Illustration 8 Panneau avant de l ASI ...

Page 238: ...indiquées dans le tableau suivant Touches Fonctions affectées Défilement des menus vers le haut Augmentation de la valeur d une unité Sélection d une valeur Défilement des menus vers le bas Diminution de la valeur d une unité Sélection d une valeur Sélection d un menu Confirmation des modifications Arrêt du buzzer activé lors d une alarme oudéfaillance Retour au menu précédent ...

Page 239: ...erie en décharge ou en TEST ORANGE Disjoncteur BCB ouvert ROUGE Défaut de la batterie suite à un test de batterie ETEINTE Batterie indisponible LED 5 VERTE Tension de l onduleur dans les tolérances et commutateur statique fermé VERTE Surcharge ou court circuit de l onduleur ETEINTE Onduleur arrêté ou tension hors tolérances LED 6 ORANGE Re transfert bloqué ORANGE Commutateur de by pass statique fe...

Page 240: ...e déchargée ou en TEST clignotement rapide ORANGE Disjoncteur BCB ouvert clignotement lent ROUGE Fin de l autonomie de la batterie Défault de la batterie LED 13 VERTE Tension de l onduleur dans les tolérances et commutateur statique fermé ORANGE Surcharge ou court circuit de l onduleur ROUGE Alarme critique de l onduleur ETEINTE Onduleur arrêté LED 14 VERTE Ligne de by pass CA dans les tolérances ...

Page 241: ...issance nominale de l ASI Mesures de l ASI pour les paramètres de base tension courant etc État de fonctionnement de l ASI éventuelles alarmes présentes et historique des alarmes Configuration des paramètres et des fonctions spéciales Informations générales concernant l ASI UPS NAME xxx kVA UPS NAME MEASURES UPS NAME ALARMS UPS NAME SPECIAL UPS NAME INFO ...

Page 242: ...anual Manuel de l utilisateur de l ASI Utilizzo dell UPS 76 OMG38225 REV F 5 2 AFFICHAGE DES MESURES Le menu MEASURES MESURES possède la structure suivante Illustration 11 Structure du menu MEASURES mesures 1 à 2 ...

Page 243: ...nce 0 1 Hz Puissance active 1 kW Puissance apparente 1 kVA Pourcentage de charge 1 BYPASS Tension 1 2 1 V Fréquence 0 1 Hz INVERTER ONDULEUR Tension 1 2 1 V Fréquence 0 1 Hz AC DC CA CC Tension en sortie du redresseur 1 V BATTERY BATTERIE Tension et courant 1 V 1 A Capacité nominale 1 Ah Autonomie résiduelle 1 min 1 1 Les mesures de tension font toujours référence à la valeurphase neutre 2 Les tro...

Page 244: ... ALARMES automatiquement dès qu une alarme se déclenche L indicateur sonore s il est sélectionné est activé afin d indiquer la survenance d une défaillance L alarme sonore peut être arrêtée en appuyant sur la touche BUZZER Affichage de la première alarme présente si aucune alarme n est présente l état de fonctionnement est affiché Appuyez sur la touche pour parcourir le menu et accéder à l alarme ...

Page 245: ...s est affiché sur la première ligne xxx yyy qui indique respectivement l événement actuellement affiché position dans la liste et le nombre total d événements enregistrés au maximum égal à 500 Une astérisque indique la réinitialisation automatique de l alarme Dernier événement enregistré dans l ordre chronologique Par ex réinitialisation automatique de l alarme A3 BOOSTER STOPPED A3 Arrêt du boost...

Page 246: ...LÈLE A15 DÉFAUT DE BY PASS A47 ERREUR D ENVOI DES PARAMÈTRES A16 BY PASS CHARGE A48 ERREUR DE RÉCEPTION DES PARAMÈTRES A17 BLOCAGE DE RETRANSFERT A49 ERREUR DU MODE DE TEST A18 MBCB FERMÉ A51 TEMPÉRATURE DE LA BATTERIE A19 OCB OUVERT A52 VERROUILLAGE DE SOUS TENSION A20 SURCHARGE A53 ERREUR DU LOGICIEL DE L APPAREIL A21 IMAGE THERMIQUE A54 ERREUR CAN A22 COMMUTATEUR DE BY PASS A55 CÂBLE PARALLÈLE ...

Page 247: ...ssent et leur indicateur sonore doit être désactivé à l aide de la touche buzzer Les alarmes restent affichées tant qu elles sont présentes Elles sont automatiquement enregistrées dans le journal d événements avec la date et l heure de leur survenance Pour une description plus détaillée des alarmes et des états voir la section Défauts et alarmes du présent manuel Description des alarmes et états M...

Page 248: ...de l ASI Utilizzo dell UPS 82 OMG38225 REV F 6 REGLAGES ET OPERATIONS AVANCEES Certains paramètres de fonctionnement de l ASI peuvent être réglés via le menu SPECIAL dont la structure est la suivante Illustration 14 Structure du menu SPECIAL ...

Page 249: ... BATTERY INSTALL Installation d une nouvelle batterie Règle l autonomie à 100 RESET HISTORY Remise à zéro de l historique Remise à zéro du journal des événements MODBUS Adresse MODBUS de l appareil RESET RUNNING HOURS Remise à zéro des heures de fonctionnement Remise à zéro du compteur d heures de fonctionnement de l ASI Le menu SETTINGS Réglages est protégé par un mot de passe défini en usine afi...

Page 250: ...rs et la touche pour valider 6 3 INSTALLATION D UNE NOUVELLE BATTERIE Le menu NEW BATTERY INSTALL Installation d une nouvelle batterie est utilisé lorsque le disjoncteur de batterie BCB n est pas fermé lorsque demandé dans la phase de démarrage Dans ce cas le système démarre en considérant que la batterie est complètement déchargée et active l alarme A10 BATTERY FAULT A10 Défaut de labatterie Pour...

Page 251: ...tre modifié à l aide des flèches et validé à l aide de la touche Entrée Écran de confirmation du réglage de paramètre Chaque chiffre peut être modifié à l aide des flèches et validé à l aide de la touche Entrée Écran de confirmation du réglage de paramètre Écran de confirmation de la configuration BAT CAPACITY SETTING 0120 CONFIRM BATT CAP YES BAT RECHAR CURR SET 18 CONFIRM RECHAR CURR YES AUTONOM...

Page 252: ...che Entrée Paramètre Standard Valeurs possibles Adresse MODBUS 1 1 247 6 6 TEST DE L ASI Le menu UPS TEST Test de l ASI permet de réaliser un test de commutation de l onduleur L onduleur est arrêté et la charge est transférée sur l alimentation de by pass L alimentation de l onduleur est automatiquement restaurée après quelques secondes La valeur de la seconde ligne est prête à être modifiée Le pa...

Page 253: ... pas complètement chargée 6 8 RÉINITIALISATION DU SYSTÈME L ASI est équipé de protections internes qui bloquent tout ou partie du système L alarme peut être effacée et le fonctionnement normal rétabli via le menu RESET Réinitialiser Si la défaillance persiste l ASI reviendra dans la condition de défaillanceprécédente Dans certains cas le menu RESET Réinitialiser est nécessaire pour la simple réini...

Page 254: ...l activation du capteur de déconnexion rapide alarme A36 Arrêt de l onduleur du fait d une erreur de la boucle de contrôle de la tension alarme A39 Arrêt du booster du fait d une erreur de la boucle de contrôle de la tension alarme A41 Arrêt du booster du fait d une erreur de la boucle de contrôle du courant alarmeA43 Commutateur statique bloqué alarme A50 Arrêt du booster du fait de l activation ...

Page 255: ...paramètre est modifié La modification est confirmée en appuyant sur Entrée Le système effectue une réinitialisation de l historique des alarmes puis revient à l écran précédent L historique des alarmes contient des données importantes pour la surveillance du comportement de l appareil dans le temps Nous vous recommandons d enregistrer les données avant toute remise à zéro Perte de données RESET HI...

Page 256: ...SI selon la structure de base suivante Illustration 15 Structure du menu INFO Toutes les données affichées dans les diverses sections sont définies en usine via un logiciel d interface spécial Elles ne peuvent pas être modifiées sauf par un personnel autorisé par le fabricant Les seuls paramètres pouvant être modifiés sont les réglages MODBUS voir le menu SPECIAL ...

Page 257: ...relatives à l entretien technique RUNNING HOUR Heures de fonctionnement Dates relatives au nombre d heures de fonctionnement de l ASI 1 Ce menu n est actif que si l ASI fait partie d un système parallèle ou de synchronisation de charge 2 Ce menu n est actif que si l ASI fait partie d un système common battery 7 1 INFORMATIONS SUR LE FONCTIONNEMENT EN PARALLELE Le menu PARALLEL Parallèle n est acti...

Page 258: ...nt l ASI maître on vérifie la communication des données sur l ASI 3 l ASI 4 ne communique pas Le menu affichera les informations suivantes S il y a plus de quatre appareils en parallèle le menu affichera les informations suivantes Les points indiquent la présence d une autre ligne de menu indiquant l état des autres ASI du système 7 1 4 Type de système parallèle La seconde ligne peut indiquer l un...

Page 259: ...ision de la réception concernant l état du système Les messages sont échangés entre tous les ASI par conséquent cette valeur augmentera sur chacun 7 2 INFORMATIONS SUR LE FONCTIONNEMENT EN PARALLELE REDRESSEUR Le menu PARALLEL Parallèle n est actif que si l ASI fait partie d un système parallèle ou de synchronisation de charge 7 2 1 Position de l ASI Le premier chiffre de la seconde ligne identifi...

Page 260: ...n système composé de 2 ASI REDUNDANT 1 signifie qu un seul ASI est nécessaire pour alimenter la charge 7 2 5 Statistiques relatives aux messages Les statistiques de la section pour les messages échangés sur le bus de communication se compose deux menus différents Nombre de messages reçus et pourcentage de précision de la réception concernant les signaux de synchronisme Les messages sont envoyés pa...

Page 261: ... affichées en faisant défiler le menu Après la dernière alarme présente les états de fonctionnement sont affichés Avant toute intervention sur l ASI assurez vous que toutes les précautions de sécurité sont respectées toute intervention sur l unité doit être réalisée par un personnel qualifié les composants internes ne peuvent être manipulés qu après déconnexion de l appareil de ses sources d alime...

Page 262: ... à alimenter la charge État S4 INVERTER LOAD Onduleur charge Description L onduleur alimente la charge Condition de fonctionnement La charge est alimentée par le commutateur d onduleur statique État S5 INV BYPASS SINCRO Description L onduleur est synchronisé avec le by pass Condition de fonctionnement La synchronisation entre l onduleur et le by pass est verrouillée Le commutateur statique peut ba...

Page 263: ...R STAND BY Description The inverter is in standby mode Condition de fonctionnement L onduleur est éteint et prêt à être démarré en cas d anomalie du réseau de base État S12 BATT STANDBY Description La batterie est en mode standby Condition de fonctionnement L interrupteur statique de la batterie est ouvert et la batterie est déconnectée du bus CC État S14 BATT CHARGING I Description La batterie es...

Page 264: ...ifiez la rotation des phases 2 Si l alarme persiste contactez notre service de supporttechnique Alarme A3 ARRÊT DU BOOSTER Description Le redresseur a été alimenté par la batterie temporairement déconnecté et l onduleur est Causes possibles Instabilité de la tension ou de la fréquence de la ligne CA Défaut possible du circuit de contrôle du redresseur Solutions 1 Vérifiez les paramètres de tension...

Page 265: ... lancé automatiquement si ce paramètre a été défini ou manuellement par l utilisateur Solutions 1 Attendez la fin du test et vérifiez les éventuels défauts de batterie Alarme A7 BCB OUVERT Description Le sectionneur d isolation de la batterie est ouvert Causes possibles Sectionneur d isolation de la batterie ouvert Solutions 1 Vérifiez l état du sectionneur d isolation de la batterie 2 Vérifiez la...

Page 266: ...i l alarme persiste contactez notre service de supporttechnique Alarme A11 COURT CIRCUIT Description Le capteur de courant a détecté un court circuit à la sortie Causes possibles Problème de charge Défaillance du circuit de mesure Solutions 1 Vérifiez les charges raccordées à la sortie de l ASI 2 Si l alarme persiste contactez notre service de supporttechnique Alarme A12 ARRÊT DÉLAIDE COURT CIRCUI...

Page 267: ...on Solutions 1 Vérifiez la rotation des phases 2 Si l alarme persiste contactez notre service de supporttechnique Alarme A15 DÉFAUT DE BY PASS Description La tension ou la fréquence de la ligne de by pass est hors tolérances Causes possibles Instabilité ou défaillance de la ligne de by pass Mauvaise rotation des phases Solutions 1 Vérifiez les raccordements au secteur 2 Vérifiez la stabilité de la...

Page 268: ... 2 Vérifiez la fonctionnalité du contact auxiliaire du sectionneur d isolation 3 Si l alarme persiste contactez notre service de supporttechnique Alarme A19 OCB OUVERT Description Le sectionneur d isolation de la sortie est ouvert Causes possibles Sectionneur d isolation de la sortie ouvert Solutions 1 Vérifiez l état du sectionneur d isolation de la sortie 2 Vérifiez la fonctionnalité du contact ...

Page 269: ...nné Causes possibles Opération de maintenance Solutions 1 Vérifiez la position du sélecteur 2 Si l alarme persiste contactez notre service de supporttechnique Alarme A23 ARRÊT D URGENCEDÉCLENCHÉ Description Le système d urgence est bloqué du fait de l activation du bouton d arrêt Causes possibles Activation du bouton d arrêt d urgence local ou distant Solutions 1 Relâchez le bouton d arrêt d urgen...

Page 270: ...service de supporttechnique Alarme A26 ERREUR DE COMMUNICATION Description Erreur interne Causes possibles Problèmes de communication au niveau dumicrocontrôleur Solutions 1 Si l alarme persiste contactez notre service de support technique Alarme A27 ERREUR DE L EEPROM Description Le contrôleur a détecté une erreur dans les paramètres enregistrés dans l E2 PROM Causes possibles Mauvais paramètres ...

Page 271: ... Vérifiez l état du sectionneur d isolation de by passmanuel 2 Vérifiez la fonctionnalité du contact auxiliaire du sectionneur d isolation 3 Si l alarme persiste contactez notre service de supporttechnique Alarme A32 BUS EPO FERMÉ Description Le système d urgence est bloqué du fait de l activation du bouton d arrêt Causes possibles Activation du bouton d arrêt d urgence local ou distant Solutions ...

Page 272: ...démarrage du générateur diesel 3 Si l alarme persiste contactez notre service de supporttechnique Alarme A36 ARRÊT RAPIDE CC Description Arrêt de l onduleur du fait d un déclenchement du capteur de protection suite à des variations soudaines de la tension CC Causes possibles Défaut de la batterie Solutions 1 Vérifiez la batterie 2 Réinitialisez le système 3 Si l alarme persiste contactez notre ser...

Page 273: ...ortie du redresseur Causes possibles Défaillance du système de régulation Solutions 1 Réinitialisez le système 2 Si l alarme persiste contactez notre service de supporttechnique Alarme A42 REDONDANCE REDRESSEUR PERTE Description Cette alarme peut être activée par le réglage EEPROM uniquement sur les systèmes dotés de la pile commune La continuité n est pas garantie en cas de défaillance de l un de...

Page 274: ...s ASI Causes possibles La charge totale est supérieure à la valeur maximum attendue Possible défaillance du circuit de mesure Solutions 1 Vérifiez la charge alimentée par le système 2 Si l alarme persiste contactez notre service de supporttechnique Alarme A47 ERREUR D ENVOI DES PARAMÈTRES Description Erreur interne EEPROM MAUVAISE TRANSMISSION DES PARAMÈTRES Causes possibles Problèmes de communica...

Page 275: ...eur est bloqué en raison d une anomalie sur l alimentation de contrôle Causes possibles Erreur interne Solutions 1 Contactez notre service de support technique Alarme A53 ER COMP FIRMWARE Description Le contrôleur a détecté une incompatibilité au niveau du logiciel de contrôle Causes possibles La mise à jour du logiciel n a pas été effectuée correctement Solutions 1 Contactez notre service de supp...

Page 276: ...upporttechnique Alarm A62 SUTENSION DU RESEAU Description Augmentation soudaine de la tension d entrée AC capteur rapide Possible causes Sp Pointe de tension sur le secteur AC Erreur interne possible Solutions 1 Vérifiez la tension du secteur 2 Si l alarme persiste contactez notre service d assistance technique Alarm A63 BLOCK BLOCAGE DE LA SÉQUENCE DE DÉMARRAGE Description Lors du démarrage de l ...

Page 277: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMG38225 REV F 111 LINGUA ITALIANA ...

Page 278: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 112 OMG38225 REV F ...

Page 279: ...KEOR HPE 125 kVA BSM10 KEOR HPE 160 kVA Conservazione della documentazione Questo manuale e tutta la restante documentazione tecnica di supporto al prodotto devono essere conservati e possibilmente resi accessibili al personale nelle immediate vicinanze dell UPS Informazioni aggiuntive Nel caso le informazioni riportate nel presente manuale non fossero abbastanza esaurienti si prega di contattare ...

Page 280: ...riportate nei manuali Pericolo di lesioni a seguito di guasti al dispositivo In caso di guasto dell UPS si possono creare situazioni potenzialmente pericolose Non utilizzare il dispositivo se presenta danni visibili Effettuare regolarmente interventi di manutenzione al fine di rilevare possibili anomalie Possibile danneggiamento del dispositivo Prima di qualsiasi intervento sul dispositivo aver cu...

Page 281: ...he in mancanza della rete per cui in accordo alle prescrizioni della CEI EN62040 1 l installatore dovrà identificare la linea o le prese alimentate dall UPS richiamando l attenzione dell utente Figura 1 Schema a blocchi L UPS è realizzato con tecnologia ad IGBT ad elevata frequenza di commutazione per consentire una bassa distorsione della corrente re iniettata nella rete di alimentazione e un alt...

Page 282: ...60 80kVA Per KEOR HPE 100 125 160kVA la batteria è installata all esterno dell UPS E generalmente ubicata all interno di un armadio La logica del carica batteria è integrata all interno dell elettronica di controllo del raddrizzatore La batteria viene sottoposta ad un ciclo di carica in accordo alle DIN41773 ogni volta che avviene una scarica parziale o totale Al ripristino della completa capacità...

Page 283: ... compensa le variazione della tensione di rete così come quelle di carico mantenendo la tensione DC costante Allo stesso tempo provvede a caricare la batteria L inverter converte la tensione DC in una sinusoide AC stabilizzata in tensione e frequenza e provvede ad alimentare il carico tramite il suo static switch SSI Figura 2 Funzionamento normale 3 3 2 Green Conversion Durante il funzionamento in...

Page 284: ...pacità persa è 10 Carica mantenimento per 12 ore Capacità persa è compresa tra il 10 e il 20 Carica mantenimento per 48 ore Capacità persa è 20 Carica mantenimento per 96 ore Tali valori sono conformi alle raccomandazioni dei principali produttori di batterie Impostare il corretto valore di capacità Il pannello frontale dell UPS permette l impostazione dei parametri di batteria inclusa la capacità...

Page 285: ...vvio dell inverter avviene quando la batteria ha ripristinato parte della sua capacità La ripartenza del sistema dalla condizione di black out può essere personalizzata sulla base delle esigenze dell impianto in tre modalità differenti Bypass i carichi vengono alimentati appena la rete di bypass è disponibile configurazione di fabbrica Inverter i carichi vengono alimentati dall inverter anche se l...

Page 286: ...lazione elettrica prestare cura al cablaggio dei contatti ausiliari degli isolatori di bypass manuale uscita e batteria che vanno collegati agli appositi morsetti sull UPS In questo modo la logica di controllo acquisisce lo stato degli interruttori per guidare l operatore durante le procedure di avvio e bypass manuale Per maggiori informazioni fare riferimento alla sezione Installazione e avviamen...

Page 287: ...lizzo degli organi di manovra e comando dell UPS è destinato a personale autorizzato Si consiglia di verificare l addestramento del personale addetto all utilizzo e alla manutenzione del sistema 3 4 1 Sezionatori I sezionatori previsti sull UPS servono per isolare la parte di potenza del dispositivo dalla rete AC di alimentazione dalla batteria di accumulatori e dai carichi Presenza di tensione su...

Page 288: ...ll arresto di emergenza sono state eliminate e si è certi che non ci siano pericoli per le persone o le cose 3 4 3 Selettore Normale Bypass Viene utilizzato durante la procedura di bypass manuale quando è necessario isolare l UPS per manutenzione o riparazione Seguire le procedure riportate nel manuale Il selettore Normale Bypass deve essere manovrato solamente in accordo alle procedure riportate ...

Page 289: ...23 4 PANNELLO FRONTALE Il pannello frontale dell UPS è composto da un display alfanumerico a 4 righe più 5 tasti funzione e consente il completo monitoraggio dello stato dell UPS Il sinottico di flusso agevola la comprensione dello stato di funzionamento Figura 8 Pannello frontale UPS ...

Page 290: ...ui funzioni sono indicate nella tabella seguente Tasto Funzioni assegnate Scorre i menu verso l alto Incrementa i valori di una unità Seleziona un valore Scorre i menu verso il basso Decrementa i valori di una unità Seleziona un valore Seleziona un menu Conferma le modifiche Silenzia il buzzer attivato a seguito di un allarme o anomalia Torna al menu precedente ...

Page 291: ...IO Interruttore BCB aperto ROSSO Batteria guasta a seguito test di batteria OFF Batteria non presente LED 5 VERDE Tensione inverter in tolleranza e static switch chiuso VERDE Sovraccarico inverter o corto circuito OFF Inverter spento o tensione fuori tolleranza LED 6 ARANCIO Ritrasferimento bloccato ARANCIO Static switch bypass chiuso OFF Static switch bypass aperto LED 7 VERDE Interruttore di usc...

Page 292: ...ARANCIO Batteria in scarica o in TEST lampeggio veloce ARANCIO Interruttore BCB aperto lampeggio lento ROSSO Fine autonomia batteria Batteria guasta LED 13 VERDE Tensione inverter in tolleranza e static switch chiuso ARANCIO Sovraccarico inverter o corto circuito ROSSO Allarme critico inverter OFF Inverter spento LED 14 VERDE Rete AC bypass in tolleranza ROSSO Senso ciclico errato lampeggio veloce...

Page 293: ...ta principale dove è visualizzata la potenza nominale dell UPS xxx kVA NOME UPS Misure dei parametri fondamentali dell UPS tensione corrente ecc MISURE NOME UPS Stato di funzionamento dell UPS eventuali allarmi presenti e storico allarmi ALLARMI NOME UPS Impostazione parametri e funzioni speciali SPECIALE NOME UPS Informazioni generali sull UPS INFO ...

Page 294: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 128 OMG38225 REV F 5 2 VISUALIZZAZIONE DELLE MISURE Il menu MISURE è strutturato come segue Figura 11 Struttura menu MISURE 1 di 2 ...

Page 295: ...Frequenza 0 1 Hz Potenza attiva 1 kW Potenza apparente 1 kVA Percentuale di carico 1 BYPASS Tensione 1 2 1 V Frequenza 0 1 Hz INVERTER Tensione 1 2 1 V Frequenza 0 1 Hz AC DC Tensione uscita raddrizzatore 1 V BATTERIA Tensione e corrente 1 V 1 A Capacità nominale 1 Ah Autonomia residua 1 min 1 1 Le misure di tensione sono sempre riferite tra fase e neutro 2 Le tre tensioni sono visualizzate in una...

Page 296: ...LARMI ogni volta che si verifica un allarme il segnalatore acustico se abilitato viene attivato per indicare l avvenuta anomalia La tacitazione viene effettuata premendo il pulsante BUZZER STATO UPS Visualizzazione del primo allarme presente se non presenti allarmi visualizzazione dello stato di funzionamento Allarme stato no 1 STATO UPS Premendo il tasto si scorre il menu e si passa all allarme s...

Page 297: ...più vecchio La quantità di eventi memorizzati è visualizzata sulla prima riga xxx yyy dove sono riportati rispettivamente il dato visualizzato al momento posizione nella lista e il numero totale di dati memorizzati numero massimo pari a 500 Un asterisco indica il reset automatico dell allarme STORICO 001 015 Ultimo evento memorizzato in ordine di tempo Es reset automatico allarme A3 RADD SPENTO A3...

Page 298: ...RIDOND A15 BYPASS NON DISP A47 ERR INVIO PARAM A16 BYP CARICO A48 ERR RIC PARAM EE A17 RITRASF BLOC A49 DISCOR TEST MODE A18 MBCB CHIUSO A51 TEMPERATURA BATT A19 OCB APERTO A52 INVERTER BLOCCATO UVL A20 SOVRACCARICO A53 ER COMP FIRMWARE A21 IMMAGINE TERMICA A54 ERRORE CAN A22 BYPASS SWITCH A55 CAVO PAR DISC A23 EPO CHIUSO A56 TERNA SBILANCIATA A24 ALTA TEMPERATURA A59 RELE BACKFEED ON A25 INVERTER...

Page 299: ...cente Gli allarmi vengono mostrati quando si presentano e devono essere tacitati con il buzzer Gli allarmi restano visibili finché sono presenti e vengono registrati automaticamente nello storico eventi con data e ora Descrizione degli allarmi e degli stati Per una descrizione più approfondita degli allarmi e degli stati vedere la sezione del presente manuale Guasti e allarmi ...

Page 300: ...ateur de l ASI Utilizzo dell UPS 134 OMG38225 REV F 6 IMPOSTAZIONI E OPERAZIONI AVANZATE L impostazione di alcuni parametri operativi dell UPS è possibile dal menu SPECIALE che è strutturato come segue Figura 14 Struttura menu SPECIALE ...

Page 301: ...della batteria INSTALL NUOVA BATT Imposta l autonomia al 100 RESET STORICO Reset dello storico eventi MODBUS Indirizzo MODBUS del dispositivo AZZERA CONTAORE Azzeramento del contaore di funzionamento della macchina Accesso protetto da password Il menu IMPOSTAZIONI è protetto da una password impostata in fabbrica per impedire l accesso a personale non autorizzato Si raccomanda la minima divulgazion...

Page 302: ...ametri si effettua utilizzando i tasti freccia per incrementare le cifre e il tasto per confermare l inserimento 6 3 INSTALLAZIONE NUOVA BATTERIA Il menù INSTALLAZIONE NUOVA BATTERIA serve nel caso in cui durante la fase di avvio non viene chiuso l interruttore di batteria BCB quando richiesto In tal caso il sistema si avvia considerando la batteria completamente scarica e attivando l allarme A10 ...

Page 303: ... parametro impostato SI CONFIG COR RICAR BAT Le singole cifre si modificano con i tasti freccia e si confermano con il tasto ENTER 18 CONF CORR RICARICA Schermata di conferma del parametro impostato SI CONFIG AUTONOMIA BAT Le singole cifre si modificano con i tasti freccia e si confermano con il tasto ENTER 0020 CONF AUTONOMIA BATT Schermata di conferma del parametro impostato SI SALVARE CONFIG BA...

Page 304: ...icano con i tasti freccia e si confermano con il tasto ENTER 202 Parametro Standard Range INDIRIZZO MODBUS 1 1 247 6 6 TEST DELL UPS Il menù TEST UPS permette di effettuare una prova di commutazione dell inverter L inverter viene spento e il carico trasferito all alimentazione di bypass L alimentazione da inverter viene ripristinata automaticamente dopo pochi secondi TEST UPS Il valore sulla secon...

Page 305: ... Questo test può essere rischioso per la continuità sui carichi se la batteria non è pienamente carica 6 8 RESET DEL SISTEMA L UPS è provvisto di protezioni interne che provvedono al blocco del sistema o di alcune sue sezioni Tramite il menu RESET è possibile sbloccare l allarme e ripristinare il funzionamento normale Nel caso l anomalia persista l UPS si riporta nella condizione di blocco precede...

Page 306: ...e statico allarme A50 Arresto booster per intervento del sensore di simmetria del carico allarme A33 Intervento allarme di avaria batteria allarme A10 Richiesta manutenzione programmata allarme A29 Per la descrizione dello stato dell UPS in ciascuna delle condizioni di blocco elencata in precedenza fare riferimento alla sezione Guasti e allarmi 6 9 RESET STORICO ALLARMI Accedere al menu RESET STOR...

Page 307: ... fornisce informazioni generali sull UPS secondo la struttura mostrata di seguito Figura 15 Struttura menu INFO Tutti i dati mostrati all interno delle varie sezioni sono impostati in fabbrica tramite apposito software di interfaccia e non possono essere modificati tranne che da parte di personale autorizzato dal costruttore ...

Page 308: ...sto scorrevole con informazioni relative all assistenza tecnica CONTATORE Dati relativi al numero di ore di funzionamento della macchina 1 Il menù è attivo solamente se l UPS fa parte di un sistema Parallelo oppure Load Sync 2 Il menù è attivo solamente se l UPS fa parte di un sistema con batteria unica 7 1 INFORMAZIONI SUL FUNZIONAMENTO IN PARALLELO Il menù PARALLELO è attivo solamente se l UPS f...

Page 309: ...UPS2 stiamo verificando la comunicazione dati sull UPS3 l UPS4 non comunica Il menù si presenterà come mostrato di seguito PARALLELO 1 S 2 M 3 S 4 Nel caso che i dispositivi in parallelo siano più di quattro il menù si presenta come segue PARALLELO 1 S 2 M 3 S I punti indicano la presenza di un ulteriore menù che mostra lo stato degli altri UPS del sistema 7 1 4 Tipo di parallelo PARALLELO RIDONDA...

Page 310: ...mero incrementa solo sugli UPS SLAVE STATIST CAN INV MSG RX 9277 99 9 Numero di messaggi ricevuti e percentuale di accuratezza della ricezione relativamente agli stati del sistema I messaggi vengono scambiati fra tutti gli UPS quindi il numero incrementa su tutti 7 2 INFORMAZIONI SUL FUNZIONAMENTO IN PARALLELO RADDRIZZATORE Il menù PARALLELO è attivo solamente se l UPS fa parte di un sistema paral...

Page 311: ...ato dal numero X Per esempio in un sistema composto da 2 UPS RIDONDANTE 1 significa che uno solo degli UPS è sufficiente per alimentare il carico 7 2 5 Statistiche messaggi La sezione statistiche relative ai messaggi scambiati sui bus di comunicazione si compone di due diversi menù STATIST CAN RADR SYNC RX 15849 100 0 Numero di messaggi ricevuti e percentuale di accuratezza della ricezione relativ...

Page 312: ...ATO UPS Scorrendo il menu dove vengono visualizzati gli altri allarmi presenti A30 ALLARME GENERALE STATO UPS Dopo l ultimo allarme presente si passa alla visualizzazione degli stati operativi S1 BOOSTER OK Pericolo di lesioni a seguito shock elettrico Prima di effettuare qualsiasi intervento sull UPS aver cura di rispettare tutte le indicazioni relative alla sicurezza tutti i lavori sull apparato...

Page 313: ... pronto per erogare alimentare il carico Stato S4 INV CARICO Descrizione L inverter alimenta il carico Condizione operativa Il carico è alimentato attraverso l interruttore statico di inverter Stato S5 INV BYPASS SINCRO Descrizione L inverter è sincronizzato con il bypass Condizione operativa Il sincronismo fra inverter e bypass è agganciato e l interruttore statico può effettuare commutazioni fra...

Page 314: ...in modalità standby Condizione operativa L inverter è spento e pronto ad essere avviato in caso di anomalia della rete di bypass Stato S12 BATTERIA STANDBY NON DISPONIBILE Descrizione La batteria è in modalità standby Condizione operativa L interruttore statico di batteria è aperto e la batteria è disconnessa dal bus DC Stato S14 BATT IN CARICA I Descrizione La batteria è in carica Condizione oper...

Page 315: ... Verificare il senso ciclico delle fasi 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A3 RADD SPENTO Descrizione Il raddrizzatore è stato momentaneamente arrestato e l inverter viene alimentato dalla batteria Possibili cause Instabilità della tensione o della frequenza della rete AC Possibile guasto del circuito di controllo del raddrizzatore Soluzioni 1 Verificare i...

Page 316: ...atteria Possibili cause E stato avviato un test di batteria automaticamente se impostato oppure manualmente dall operatore Soluzioni 1 Attendere la fine del test e verificare eventuali anomalie della batteria Allarme A7 BCB APERTO Descrizione Il sezionatore di batteria è aperto Possibili cause Sezionatore di batteria aperto Soluzioni 1 Verificare lo stato del sezionatore di batteria 2 Verificare l...

Page 317: ...ria 2 Resettare il sistema 3 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A11 CORTO CIRCUITO Descrizione Il sensore di corrente ha rilevato un corto circuito in uscita Possibili cause Problema sui carichi Guasto del circuito di misura Soluzioni 1 Verificare i carichi connessi all uscita dell UPS 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Alla...

Page 318: ... il senso ciclico delle fasi 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A15 BYPASS NON DISP Descrizione La tensione o la frequenza della rete di bypass sono fuori dal range di tolleranza Possibili cause Instabilità o mancanza della rete di bypass Errato senso ciclico delle fasi Soluzioni 1 Controllare i collegamenti di connessione alla rete 2 Verificare la stabili...

Page 319: ... manuale 2 Verificare la funzionalità del contatto ausiliario del sezionatore 3 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A19 OCB APERTO Descrizione Il sezionatore di uscita è aperto Possibili cause Sezionatore di uscita aperto Soluzioni 1 Verificare lo stato del sezionatore di uscita 2 Verificare la funzionalità del contatto ausiliario del sezionatore 3 Se l allar...

Page 320: ...sistenza Tecnica Allarme A23 EPO CHIUSO Descrizione Il sistema è bloccato in seguito all azionamento del pulsante di arresto di emergenza Possibili cause Azionamento del pulsante di arresto di emergenza locale o remoto Soluzioni 1 Sbloccare l arresto di emergenza e resettare l allarme 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A24 ALTA TEMPERATURA Descrizione Alta...

Page 321: ...llore ha rilevato un errore nei parametri memorizzati in EEPROM Possibili cause Inserimento di parametri errati durante la programmazione Soluzioni 1 Contattare il servizio di Assistenza Tecnica Allarme A28 GUASTO CRITICO Descrizione E presente un allarme che causa l arresto di una parte dell UPS raddrizzatore inverter interruttore statico Possibili cause Guasto del sistema Soluzioni 1 Verificare ...

Page 322: ... Il sistema è bloccato in seguito all azionamento del pulsante di arresto di emergenza Possibili cause Azionamento del pulsante di arresto di emergenza locale o remoto Soluzioni 1 Sbloccare l arresto di emergenza e resettare l allarme 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A33 CARICO ASIMMETR Descrizione Le tensioni misurate sui condensatori DC positiva e nega...

Page 323: ...one per variazioni repentine della tensione DC Possibili cause Anomalia batteria Soluzioni 1 Verificare la batteria 2 Resettare il sistema 3 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A38 INV CARICO Descrizione Il carico è alimentato dall inverter Allarme attivo per UPS in modalità ECO dove l alimentazione privilegiata è dalla rete di bypass Possibili cause Trasferi...

Page 324: ...ta in caso di anomalia al raddrizzatore di uno degli UPS Possibili cause Il carico totale è superiore al valore massimo atteso Possibile guasto del circuito di misura Soluzioni 1 Verificare il carico alimentato dal sistema 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A44 DESATURAZIONE Descrizione L inverter è bloccato in seguito all intervento del sensore di desatur...

Page 325: ...interno Possibili cause Problemi di comunicazione del microcontrollore Soluzioni 1 Contattare il servizio di Assistenza Tecnica Allarme A49 DISCOR TEST MODE Descrizione Errore interno Possibili cause Problemi di comunicazione del microcontrollore Soluzioni 1 Contattare il servizio di Assistenza Tecnica Allarme A51 TEMPERATURA BATT Descrizione La temperatura della batteria è fuori dai limiti di tol...

Page 326: ...tare il servizio di Assistenza Tecnica Allarme A54 ERRORE CAN Descrizione Errore interno Possibili cause Problemi di comunicazione del microcontrollore Soluzioni 1 Contattare il servizio di Assistenza Tecnica Allarme A55 CAVO PAR DISC Descrizione Mancata comunicazione del cavo parallelo Possibili cause Cavo di parallelo disconnesso o danneggiato Soluzioni 1 Controllare la connessione del cavo 2 Co...

Page 327: ... il corretto funzionamento sezione statico 3 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A62 MAINS OVERVOLTAGE Descrizione Rilevazione di un picco di tensione sull ingresso AC Possibili cause Picco di tensione sulla rete AC Possibile guasto interno Soluzioni 1 Controllare la rete AC 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A63 SEQ ...

Page 328: ...UPS OPERATING MANUAL MANUEL DE FONCTIONNEMENT DE L UPS MANUALE OPERATIVO UPS KEOR HPE 200 250 300 kVA ...

Page 329: ...plémentaires peuvent être nécessaires pour éviter les perturbations Catégorie ASI C3 conformément á la norme IEC 62040 2 Questo prodotto è destinato ad applicazioni commerciali e industriali del secondo ambiente durante l installazione può essere necessario introdurre alcune limitazioni ed adottare misure aggiuntive per prevenire i disturbi Classe UPS C3 in accordo alla norma CEI 62040 2 ELECTROMA...

Page 330: ......

Page 331: ...S OPERATING MANUAL MANUALE OPERATIVO UPS Index of sections Indice delle sezioni Code Codice 1 WARNINGS AND GENERAL INFORMATION AVERTISSEMENTS ET INFORMATIONS GÉNÉRALES AVVERTENZE E INFORMAZIONI GENERALI OMB81276 2 INSTALLATION AND START UP INSTALLATION ET DÉMARRAGE DE L ASI INSTALLAZIONE ED AVVIAMENTO OMP06262 3 UPS USER MANUAL MANUEL DE L UTILISATEUR DE L ASI UTILIZZO DELL UPS OMP06263 ...

Page 332: ...GENERAL INFORMATION AVERTISSEMENTS ET INFORMATIONS GÉNÉRALES AVVERTENZE E INFORMAZIONI GENERALI Index Indice ENGLISH LANGUAGE 4 1 CONVENTIONS USED 5 2 DOCUMENTATION NOTES 6 3 FACTORY WARRANTY 7 4 LIMITATION OF LIABILITY 9 LANGUE FRANÇAIS 10 1 CONVENTIONS UTILISEES 11 2 REMARQUES RELATIVES A LA DOCUMENTATION 12 3 GARANTIE USINE 13 4 LIMITATION DE RESPONSABILITÉ 15 LINGUA ITALIANA 16 5 CONVENZIONI U...

Page 333: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali 2 OMB81276 REV B ...

Page 334: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali OMB81276 REV B 3 ...

Page 335: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali 4 OMB81276 REV B ENGLISH LANGUAGE ...

Page 336: ...n so as to minimize the risks to persons and property HAZARD HAZARD statements contain characteristics and basic instructions for the safety of persons Non compliance with such indications may cause serious injury or death WARNING WARNING statements contain characteristics and basic instructions for the safety of persons Non compliance with such indications may cause injury CAUTION CAUTION stateme...

Page 337: ...is manual and any other supporting technical documentation relating to the product must be stored and made accessible to personnel in the immediate vicinity of the UPS Further information In the event that the information provided in this manual is not sufficiently exhaustive please contact the manufacturer of the device whose details are available in the Contacts section ...

Page 338: ... and will be charged to the end customer c In case of service performed following a call made by mistake or in case our technicians incur extra time and or costs due to the site inaccessibility or due to work interruptions required by the customer such costs will be invoiced in accordance with ANIE rates CLASS III COLUMN B Modes required a In the event of a fault covered by the warranty the custom...

Page 339: ...nal factors such as dirt fire flooding failed operation of the air conditioning system etc Non compliance with applicable safety standards Force majeure e g lightning surges natural disasters fire acts of war riots etc Fall or displacement due to incorrect installation Ordinary wear caused by proper and continuous use of the device b Protective devices inside the units fuses and dischargers are al...

Page 340: ... use is considered improper and therefore hazardous The manufacturer cannot be held responsible for possible damage arising from improper erroneous or unreasonable usage Legrand assumes responsibility for the equipment in its original configuration Any intervention that alters the structure or the operating cycle of the equipment must be carried out and authorized directly by Legrand Legrand will ...

Page 341: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali 10 OMB81276 REV B LANGUE FRANÇAIS ...

Page 342: ... Les indications DANGER contiennent des caractéristiques et des instructions de base destinées à assurer la sécurité des personnes Le non respect de ces indications peut entraîner des blessures graves voire la mort AVERTISSEMENT Les indications AVERTISSEMENT contiennent des caractéristiques et des instructions de base destinées à assurer la sécurité des personnes Le non respect de ces indications ...

Page 343: ...mentation Ce manuel ainsi que les autres documentations techniques relatives à ce produit doivent être stockés et mis à disposition du personnel à proximité immédiate de l UPS Autres informations Si les informations fournies dans le présent manuel ne sont pas suffisamment complètes veuillez contacter le fabricant de l appareil dont les coordonnées sont indiquées dans la section Contacts ...

Page 344: ...ande effectuée par erreur ou si nos techniciens interviennent plus longtemps que prévu et ou encourent des frais supplémentaires en raison de l inaccessibilité du site ou d interruptions de travail demandées par le client les coûts correspondants seront facturés conformément aux conditions d intervention en vigueur dans le pays d installation Documents requis a Si le client constate un défaut couv...

Page 345: ... la climatisation etc Du non respect des normes de sécurité en vigueur D un événement de force majeure par ex orage surtensions catastrophe naturelle incendie guerre émeute etc D une chute ou d un déplacement dû à une installation incorrecte De l usure ordinaire résultant de l utilisation correcte et continue de l appareil b Les dispositifs de protection inclus dans les unités fusibles et décharge...

Page 346: ...tilisation sera considérée comme inappropriée et dangereuse Le fabricant ne saurait être tenu responsable des éventuels dommages résultant d une utilisation inappropriée incorrecte ou déraisonnable Legrand est responsable de l équipement dans sa configuration d origine Toute intervention modifiant la structure ou le cycle de fonctionnement de l équipement devra être réalisée et autorisée directeme...

Page 347: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali 16 OMB81276 REV B LINGUA ITALIANA ...

Page 348: ...imizzare i rischi per persone e cose PERICOLO Le indicazioni di PERICOLO riportano caratteristiche e istruzioni fondamentali per la sicurezza delle persone L inosservanza di tali indicazioni può causare lesioni gravi o morte AVVERTIMENTO Le indicazioni di AVVERTIMENTO riportano caratteristiche e istruzioni fondamentali per la sicurezza delle persone L inosservanza di tali indicazioni può causare l...

Page 349: ...nuale e tutta la restante documentazione tecnica di supporto al prodotto devono essere conservati e possibilmente resi accessibili al personale nelle immediate vicinanze dell UPS Informazioni aggiuntive Nel caso le informazioni riportate nel presente manuale non fossero abbastanza esaurienti si prega di contattare il costruttore del dispositivo i cui dettagli sono disponibili alla sezione Contatti...

Page 350: ...a e saranno riaddebitati al cliente finale f In caso di intervento in seguito ad una chiamata fatta per errore o nell eventualità in cui i nostri tecnici dovessero incorrere in tempo e o spese aggiuntive a causa di inaccessibilità del sito o sospensioni del lavoro richieste da parte del cliente tali oneri verranno fatturati in accordo alle tariffe ANIE CLASSE III COLONNA B Modalità richieste a In ...

Page 351: ...menti mancato funzionamento dell impianto di condizionamento etc mancato rispetto delle norme di sicurezza pertinenti forza maggiore per es fulmini sovratensioni calamità naturali incendi atti di guerra sommosse etc cadute o spostamenti dovuti ad installazione non corretta normale usura causata da un uso proprio e continuativo dell apparecchio b Sono inoltre esclusi dalla garanzia i dispositivi di...

Page 352: ...epita Ogni altro uso è da considerarsi improprio e quindi pericoloso Il Costruttore non può essere considerato responsabile per eventuali danni causati da usi impropri erronei ed irragionevoli Legrand si ritiene responsabile della macchina nella sua configurazione originale Qualsiasi intervento che alteri la struttura o il ciclo di funzionamento della macchina deve essere eseguito ed autorizzato d...

Page 353: ...ET DÉMARRAGE DE L ASI KEOR HPE 200 250 300 KVA INSTALLAZIONE E AVVIAMENTO UPS KEOR HPE 200 250 300 KVA Installation and start up of KEOR HPE UPS 200 250 300 kVA Installation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA Rev Descrizione Description Data Date Emesso Issued Approvato Approved Lingua Language Pagina Page di Pag of Pag B VR09 202...

Page 354: ...l connection 16 2 3 6 Operation 17 2 3 7 Maintenance 18 2 3 8 Storage 19 2 4 ENVIRONMENTAL PROTECTION 19 2 4 1 ISO 14001 certification 19 2 4 2 Recycling of packing materials 19 2 4 3 Device disposal 19 3 INSTALLATION 20 3 1 RECEIPT OF THE UPS 20 3 1 1 Storage 20 3 2 HANDLING OF THE UPS 21 3 3 POSITIONING AND INSTALLATION 22 3 3 1 Base plan static load and weights 23 3 3 2 Overall dimensions clear...

Page 355: ...UP AND SHUTDOWN 41 5 1 PRELIMINARY CHECKS 41 5 2 START UP PROCEDURE 42 5 3 SHUT DOWN PROCEDURE 46 5 4 SWITCHING PROCEDURE TO MANUAL BYPASS 46 5 5 RESTART FROM MANUAL BYPASS 47 LANGUE FRANÇAIS 51 1 PORTEE 53 2 RÈGLES DE SECURITE ET AVERTISSEMENTS 54 2 1 UTILISATION DE L ASI 54 2 2 VALEURS NOMINALES DE L ASI 55 2 3 AVERTISSEMENTS SPÉCIFIQUES RELATIFS À LA SÉCURITÉ 56 2 3 1 Avertissements généraux 56...

Page 356: ... 72 4 2 DISPOSITIF DE PROTECTION CONTRE LE BACKFEED 74 4 3 BORNIERS 76 4 4 BATTERIES 78 4 5 RACCORDEMENT DES CABLES AUXILIAIRES 79 4 5 1 By pass manuel externe 79 4 5 2 Commande externe NORMAL BYPASS 79 4 5 3 Interrupteur de sortie ASI 79 4 5 4 Bouton d arrêt d urgence à distance EPO 80 4 5 5 Contact auxiliaire de batterie 80 4 5 6 Contact auxiliaire du Groupe electrogène 80 4 6 PRÉDISPOSITION POU...

Page 357: ...mballaggio 103 2 4 3 Smaltimento del dispositivo 103 3 INSTALLAZIONE 104 3 1 RICEZIONE DELL UPS 104 3 1 1 Immagazzinamento 104 3 2 MOVIMENTAZIONE DELL UPS 105 3 3 POSIZIONAMENTO ED INSTALLAZIONE 106 3 3 1 Pianta di base carico statico e pesi 107 3 3 2 Dimensioni di ingombro distanze minime dalle pareti e ventilazione 108 3 3 3 Condizioni ambientali di installazione 110 3 4 POSIZIONAMENTO E ALLACCI...

Page 358: ...tto ausiliario sezionatore di batteria 122 4 5 6 Contatto ausiliario Generatore Diesel 122 4 6 PREDISPOSIZIONE PER COLD START 122 4 7 INTERFACCE SERIALI 123 4 8 COLLEGAMENTO SCHEDA RELÈ OPZIONALE 124 5 AVVIAMENTO E ARRESTO 125 5 1 VERIFICHE PRELIMINARI 125 5 2 PROCEDURA DI AVVIAMENTO 126 5 3 PROCEDURA DI ARRESTO 130 5 4 PROCEDURA DI TRASFERIMENTO SU BYPASS MANUALE 130 5 5 RIAVVIO DA BYPASS MANUALE...

Page 359: ...re 12 Rectifier start up 43 Picture 13 Inverter start up 44 Picture 14 Bypass start up 44 Picture 15 Battery start up 45 Picture 16 Connecting the UPS to the load 45 Picture 17 Start up end 46 Picture 18 Start up from manual bypass 47 Picture 19 Bypass start up 47 Picture 20 Connecting the battery 48 Picture 21 Closing the UPS output switch 48 Picture 22 Opening the manual bypass switch 49 Picture...

Page 360: ...e dérivation manuelle 91 Illustration 23 Démarrage de l onduleur 91 Illustration 24 Transférer la charge 92 Illustration 25 Redémarrer à partir du bypass manuel terminé 92 Figura 1 Targhetta caratteristiche KEOR HPE 200 250 300 kVA 97 Figura 2 Movimentazione UPS KEOR HPE 200 250 300 kVA 105 Figura 3 Pianta di base 107 Figura 4 Dimensioni di ingombro 108 Figura 5 Distanze di rispetto 108 Figura 6 S...

Page 361: ...ione e avviamento KEOR HPE UPS 200 250 300 kVA OMP06262 REV B 9 Figura 20 Connessione della batteria 132 Figura 21 Chiusura del sezionatore uscita UPS 132 Figura 22 Apertura del sezionatore di bypass manuale 133 Figura 23 Avvio inverter 133 Figura 24 Trasferimento del carico 134 Figura 25 Avvio da bypass manuale completato 134 ...

Page 362: ...tallation and start up of KEOR HPE UPS 200 250 300 kVA Installation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA 10 OMP06262 REV B ENGLISH LANGUAGE ...

Page 363: ...ms listed below BSP06 KEOR HPE 200 kVA BSO02 KEOR HPE 250 kVA BSS88 KEOR HPE 300 kVA Storing documentation This manual and any other supporting technical documentation relating to the product must be stored and made accessible to personnel in the immediate vicinity of the UPS Further information In the event that the information provided in this manual is not sufficiently exhaustive please contact...

Page 364: ...ke your time to read the following manual The purpose of this manual is to give a short description of the parts composing the UPS and to guide the installer or the user through the installation of the unit in its using environment The installer or the user must read and correctly perform the instructions included in the present manual with particular reference to the requirements regarding safety...

Page 365: ...he KEOR HPE UPS 200 250 300 kVA is provided with an identification plate containing the operation ratings The plate is fixed in the inside of the UPS door Picture 1 Rating plate of KEOR HPE 200 250 300 kVA Check the technical characteristics Before carrying out any installation or start up operation on the UPS make sure its technical characteristics are compatible with the AC supply line and with ...

Page 366: ...the part regarding safety Such training and qualification shall be considered as such only when certified by the manufacturer 2 3 3 Transport and handling Avoid bending or deforming the components and altering the insulation distances while transporting and handling the product Undistributed weight The weight of the UPS is not uniformly distributed Pay attention when lifting Please inspect the dev...

Page 367: ...es Never expose the device to direct sunlight or place it near a source of heat Special environmental conditions The UPS is designed for normal climatic and environmental operating conditions as defined in the technical specification altitude ambient operating temperature relative humidity and environmental transport and storage conditions It is necessary to implement specific protective measures ...

Page 368: ...e identification plate correspond to the AC power system and to the actual electrical consumption of all of the equipment connected Check the conformity to the Standards The UPS must be installed in compliance with the standards in force in the country of installation IT system The UPS is also designed to be connected to an IT power distribution system All the electrical connections must be carrie...

Page 369: ...on The installations to which the UPS systems belong must comply with all the current safety standards technical equipment and accident prevention regulations The device can be started operated and disconnected only by authorized personnel The settings can only be changed using the original interface software Injury hazard due to electric shock During operation the UPS converts power characterized...

Page 370: ...even after shutdown and disconnection from the supply sources due to the internal capacitors which discharge slowly Thus we recommend to wait at least 5 minutes before opening the device doors Injury hazard due to electric shock Any operation must be carried out only when voltage is absent and in compliance with safety directives Make sure the battery circuit breaker that may be placed near the ba...

Page 371: ...treme temperature variations bad ventilation conductive or radiant heat from other sources fungus insects vermin 2 4 ENVIRONMENTAL PROTECTION 2 4 1 ISO 14001 certification Legrand is particularly sensitive to the environmental impact of its products That is why the UPS has been manufactured with cutting edge eco design criteria ISO 14001 certification Special care was taken in using fully recyclab...

Page 372: ...roduct need to be returned to the manufacturer please use the original package Danger to persons due to transport damages Mechanical damage to the electrical components constitutes a serious danger to persons and property In case of doubt regarding the non integrity of the package or of the product contained therein contact the manufacturer before carrying out the installation and or the start up ...

Page 373: ...t always be handled in upright position During loading and unloading operations always respect the indications regarding the device barycentre marked on the package Before positioning the UPS in order to avoid risks of turnover it s recommended to move the system on the wood pallet on which the UPS is fixed Before the positioning in the final location remove the UPS from the pallet To handle the U...

Page 374: ...r the environmental conditions in the place of installation in compliance with the current legislation please refer to the Overall dimensions minimum distances from the walls and ventilation section Special environmental conditions It is necessary to implement specific protective measures in case of unusual environmental conditions harmful smoke dust abrasive dust humidity vapour salt air bad weat...

Page 375: ... 1 Base plan static load and weights 859 850 900 750 880 970 300 713 90 5 63 38 Ø 1 3 x 4 GLAND PLATE Picture 3 Base plan The supporting base of the UPS must be designed to carry the UPS weight and to ensure its steady and safe support Its carrying capacity must be adequate to the static load indicated in the table below Power kVA 200 250 300 Weight kg 530 630 675 Static load kg m2 785 930 1000 ...

Page 376: ...250 300 kVA Installation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA 24 OMP06262 REV B 3 3 2 Overall dimensions clearances and ventilation Picture 4 Overall dimensions Picture 5 Clearances ...

Page 377: ...ability and to allow a correct air flow as much as possible With regard to the minimum distances from the walls for all of the UPS sizes the same installation conditions apply as indicated in the table below A mm B mm C mm D mm Recommended clearances 50 1200 50 600 Minimum clearances 0 1200 0 400 The table below shows the air volume required for an optimal ventilation and cooling of the UPS Power ...

Page 378: ...wind rain snow hail etc NO Water with an origin other than rain NO Ice formation NO Classification of biological conditions EN 60721 3 3 Environmental parameter Class 3B1 3B2 3B3 a Flora NO Presence of mildew fungus etc Presence of mildew fungus etc b Fauna NO Presence of rodents and other animals that are harmful to products excluding termites Presence of rodents and other animals that are harmfu...

Page 379: ...e is strictly monitored and regulated clean spaces category X Places where atmosphere is permanently monitored X Places located in rural and urban regions where industrial activities are few and where traffic is moderate X Places located in urban regions with industrial activities and or considerable traffic X Places in proximity to industrial sources with chemical emissions X Places located in in...

Page 380: ...w the installation instructions For battery installation please respect EN62040 1 strictly and follow the installation manual of the UPS To obtain the battery life indicated by the battery manufacturer the operating temperature must remain between 0 and 25 C However although the battery can operate up to 40 C there will be a significant reduction of the battery life To avoid the formation of any k...

Page 381: ...tput connections in compliance with the local standards Cables must be selected bearing in mind technical financial and safety aspects The selection and the sizing of cables from a technical viewpoint depend on the voltage on the current absorbed by the UPS on the bypass line and on the batteries on the ambient temperature and on the voltage drop Finally the kind of cable laying must be taken into...

Page 382: ...connecting the UPS to the mains 4 1 CONNECTION OF THE POWER CABLES For the electric connection of the KEOR HPE UPS 200 250 kVA connect the following cables DC supply from the battery if the battery is external AC supply from the rectifier and bypass supply mains AC output to the loads Injury hazard due to electric shock Very high voltages are present at the ends of the cables coming from the batte...

Page 383: ... The sections given in the table above are indicative only The cables have been designed according to the standard CEI UNEL35024 1 using the following data 70 C rated PVC copper cables ambient temperature equal to 40 C maximum length of the cables equal to 30 m voltage drop 0 5 cables laid in cavities of structures or solid bottom cable trays The given cross sections do not take into account the o...

Page 384: ...nt protection using a MCCB equipped with a shunt trip coil and connected to UPS applying the wiring diagram principle described in Figure 6 In case of backfeed failure detected by the UPS the UPS will send a signal to trip the MCCB to isolate the UPS in order to protect the upstream distribution circuits The installer shall apply the following warning label on all primary power isolator that suppl...

Page 385: ...PS 200 250 300 kVA Installation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA OMP06262 REV B 33 Picture 6 Single Line Diagram KEOR HPE 200 250 300kVA with connection to external device ...

Page 386: ...ower cables and of auxiliary connections Picture 7 Terminal board KEOR HPE 200 250 kVA RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION INGRESSO RADDRIZZATORE RECTIFIER INPUT 1 N N 1 L1 R 1 L3 T 1 L2 S 2 L1 R 2 L2 S 2 L3 T 2 N N 3 L1 R 3 L3 T 3 L2 S RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION INGRESSO BY PASS BY PASS ...

Page 387: ...E 300 kVA RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION INGRESSO RADDRIZZATORE RECTIFIER INPUT 1 N N 1 L1 R 1 L3 T 1 L2 S 2 L1 R 2 L2 S 2 L3 T 2 N N 3 L1 R 3 L3 T 3 L2 S RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION INGRESSO BY PASS BY PASS INPUT USCITA UPS UPS OUTPUT B N B 3 N N RISPETTARE LA POLARITA PLEASE RESPECT...

Page 388: ...rical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply circuit Batteries installation For battery installation please respect the prescriptions of the EN62040 1 standard paragraph 7 6 To obtain the battery life indicated by the battery manufacturer the o...

Page 389: ...CB The auxiliary contacts of the external switches MBCB BCB and OCB if provided must be mandatorily connected to the UPS Picture 8 Auxiliary terminals of KEOR HPE 200 250 300 kVA 4 5 1 External manual bypass Auxiliary contact of the external Manual Bypass Switch if provided on terminals X10 1 2 A normally open contact is required when the contact is closed see Manual Bypass procedure the microproc...

Page 390: ...e terminals 7 8 4 5 5 Battery auxiliary contact Battery auxiliary contact on terminals X10 9 10 This auxiliary contact is necessary to indicate the position of the isolator open closed 4 5 6 Diesel Generator auxiliary contact Auxiliary contact from the Diesel Generator on terminals X10 11 12 A normally open contact must be used the contact must close when the diesel generator is operating The micr...

Page 391: ...ial interfaces of KEOR HPE 200 250 300 kVA RS232 USB it is used for connection to the proprietary programming and control software SRC 2 relay card used for the remote signalisations of status and alarms PARALLEL OPTIONAL it is used for communication between paralleled UPS units MODBUS OPTIONAL it is used for the transmission of data to the outside via MODBUS RTU protocol RS485 THERMAL PROBE it is...

Page 392: ...Status Status M1 Led Pins Status in normal operation Name Status in normal operation RL1 Alarm A30 COMMON ALARM Not energized if alarm is present 2 3 Closed DL1 On 1 2 Open RL2 Alarm A1 MAINS FAULT Not energized if alarm is present 5 6 Closed DL2 On 4 5 Open RL3 Alarm A9 BATTERY AUT END Not energized if alarm is present 8 9 Closed DL3 On 7 8 Open RL4 Alarm A13 INV OUT OF TOL Not energized if alarm...

Page 393: ...e Contacts section External isolators All the procedures that follow make reference to the external isolator BCB and are only valid if such device is installed externally and its auxiliary contacts properly wired to the UPS terminals 5 1 PRELIMINARY CHECKS Before starting up the unit make sure that all installation and electric connection works have been performed professionally all power and cont...

Page 394: ...uxiliary contacts Carry out a proper electrical installation by wiring the auxiliary contacts of the external manual bypass output and battery isolators to the dedicated terminals on board the UPS This will allow the control logic to acquire the status of the switches and guide the operator during the start up and manual bypass procedures The system start up is completely guided the indications av...

Page 395: ...0 300 kVA OMP06262 REV B 43 1 Close the rectifier input switch RCB After some seconds the touch screen will start and will show the UPS mimic diagram Picture 11 UPS start up page 2 After the software loading phase the control logic will acquire the system status and the operation of the RCB switch and will show the operating sequences Picture 12 Rectifier start up ...

Page 396: ...R HPE UPS 200 250 300 kVA 44 OMP06262 REV B Picture 13 Inverter start up 3 As the inverter is correctly started up close the bypass switch SBCB when indicated by the display The logic will check the correctness of the bypass phase sequence and RMS voltage value Picture 14 Bypass start up 4 Close the battery switch BCB when indicated by the display ...

Page 397: ...ch The switch BCB located in the external battery cabinet can only be closed if the DC voltage is in tolerance Serious damages both to the battery and the equipment may occur if the breaker is closed before the front panel requires it 5 Close the UPS output switch OCB to connect the UPS to the load bus After this operation the start up is completed and the display will show the final mimic diagram...

Page 398: ...ual Bypass with no interruption of supply to the loads In this configuration the system can be restarted via the return procedure from load on manual bypass without the need to de energize the loads Manual bypass To perform the switching procedure correctly make sure no alarms are present on the system During Manual Bypass the load is supplied directly by the input mains therefore continuous suppl...

Page 399: ...s make sure the Bypass_Sw selector is in BYPASS position and the MBCB isolator is closed 1 Close the rectifier input switch RCB After some seconds the touch screen will start and will show the UPS mimic diagram Picture 18 Start up from manual bypass 2 After the software loading phase the control logic will acquire the system status and the operation of the RCB switch and will show the operating se...

Page 400: ...mento KEOR HPE UPS 200 250 300 kVA 48 OMP06262 REV B 3 Close the battery switch BCB when indicated by the display Picture 20 Connecting the battery 4 Close the output switch OCB when required and immediately after the display will require to open the manual bypass switch MBCB The inverter will start Picture 21 Closing the UPS output switch ...

Page 401: ...300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA OMP06262 REV B 49 Picture 22 Opening the manual bypass switch Picture 23 Inverter start up 5 As soon as the inverter is started it will be possible to transfer the load Move the bypass switch as required by the display to complete the UPS start up ...

Page 402: ...E UPS 200 250 300 kVA Installation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA 50 OMP06262 REV B Picture 24 Transferring the load Picture 25 Re start from manual bypass completed ...

Page 403: ...tallation and start up of KEOR HPE UPS 200 250 300 kVA Installation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA OMP06262 REV B 51 LANGUE FRANÇAIS ...

Page 404: ...Installation and start up of KEOR HPE UPS 200 250 300 kVA Installation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA 52 OMP06262 REV B ...

Page 405: ...es ASI telle qu indiquée ci dessous BSP06 KEOR HPE 200 kVA BSS02 KEOR HPE 250 kVA BSS88 KEOR HPE 300 kVA Ce manuel ainsi que les autres documentations techniques relatives à ce produit doivent être stockés et mis à disposition du personnel à proximité immédiate de l ASI Si les informations fournies dans le présent manuel ne sont pas suffisamment complètes veuillez contacter le fabricant de l appar...

Page 406: ...VA nous vous suggérons de lire attentivement le présentmanuel L objectif de ce manuel est de vous fournir une brève description des éléments composant l ASI et de vous guider dans l installation de l unité dans son environnement d utilisation L installateur ou l utilisateur devra lire et respecter les instructions fournies dans le présent manuel en particulier les exigences relatives à la sécurité...

Page 407: ...0 300 kVA est fourni avec une plaque signalétique indiquant ses valeurs nominales de fonctionnement Cette plaque est apposée sur la face intérieure de la porte Illustration 1 Plaque signalétique de l ASI KERO HPE 200 250 300 kVA Avant toute opération d installation ou de démarrage de l ASI assurez vous que ses caractéristiques techniques sont compatibles avec l alimentation CA et les charges en so...

Page 408: ...is l intégralité de ce manuel en particulier les exigences relatives à la sécurité La formation et les qualifications du personnel ne seront considérées comme valides que si elles ont été certifiées par le fabricant 2 3 3 Transport et manutention Évitez de tordre ou de déformer les composants ainsi que de modifier les distances d isolement lors du transport et de la manutention du produit Le poids...

Page 409: ...d une source de chaleur L ASI est conçu pour des conditions de fonctionnement environnementales et climatiques normales telles que définies dans les caractéristiques techniques altitude température ambiante de fonctionnement humidité relative et conditions environnementales de transport et de stockage Il est nécessaire de mettre en œuvre des mesures de protection spécifiques en cas de conditions i...

Page 410: ...orrespondent au système d alimentation CA et à la consommation électrique réelle de tous les équipements raccordés L ASI doit être installé conformément à la réglementation nationale en vigueur L ASI est également conçu pour être raccordé sur un système d alimentation inormatique Tous les raccordements électriques doivent être réalisés par un personnel autorisé Avant tout raccordement de l apparei...

Page 411: ...s les normes de sécurité en vigueur réglementations relatives aux équipements techniques et à la prévention des accidents L appareil ne peut être mis en marche utilisé et déconnecté que par un personnel autorisé Lorsqu il fonctionne l ASI convertit des puissances caractérisées par des tensions et courants élevés Toutes les portes et tous les capots doivent rester fermés La batterie fournie avec l ...

Page 412: ...déconnexion des sources d alimentation du fait de la décharge lente des condensateurs internes Nous recommandons par conséquent de patienter au moins 5 minutes avant d ouvrir les portes de l appareil Toute opération doit être réalisée uniquement en l absence de tension et dans le respect des directives de sécurité Assurez vous que le disjoncteur de la batterie qui peut se trouver à proximité de ce...

Page 413: ...trêmes mauvaise ventilation chaleur conduite ou rayonnante en provenance d autres sources moisissures insectes nuisibles 2 4 PROTECTION DE L ENVIRONNEMENT 2 4 1 Certification ISO 14001 Legrand est particulièrement sensible à l impact de ses produits sur l environnement C est pourquoi l ASI est fabriqué en tenant compte de critères d éco conception de pointe certification ISO 14001 Une attention sp...

Page 414: ...liser l emballaged origine Les dommages mécaniques subis par les composants électriques constituent un grave danger pour les personnes et les biens En cas de doute concernant l intégrité de l emballage ou du produit contactez le fabricant avant toute installation et ou démarrage 3 1 1 Stockage L emballage protège normalement l appareil de l humidité et des éventuels dommages pouvant se produire pe...

Page 415: ...de déchargement respectez toujours les indications concernant le barycentre de l appareil qui figurent sur l emballage Avant de positionner l onduleur et afin d éviter les risques de bascules il est recommandé de déplacer le système sur la palette de bois sur lequel l onduleur est fixé Avant le positionnement dans l emplacement final retirer l onduleur de la palette Pour manipuler l onduleur suppr...

Page 416: ... du site d installation qui doivent être conformes à la législation en vigueur veuillez vous reporter à la section Ventilation Il est nécessaire de mettre en œuvre des mesures de protection spécifiques en cas de conditions environnementales inhabituelles fumées dangereuses poussières poussières abrasives humidité vapeur air à forte teneur en sel mauvaises conditions météorologiques ou aspersion d ...

Page 417: ...arge statique et poids 859 850 900 750 880 970 300 713 90 5 63 38 Ø 1 3 x 4 PLAQUE ENTRÈE CÂBLES llustration 3 Plan de base Le sol soutenant l ASI doit être conçue pour supporter le poids de l ASI et assurer un maintien sûr et stable Sa capacité de soutien doit correspondre aux charges statiques indiquées dans le tableau ci dessous Puissance kVA 200 250 300 Poids kg 530 630 675 Charge statique kg ...

Page 418: ...nstallation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA 66 OMP06262 REV B 3 3 2 Dimensions totales dégagement minimum et ventilation Illustration 4 Dimensions globales Illustration 5 Dégagement minimum ...

Page 419: ...de l air aussi correcte que possible Concernant le dégagement minimum par rapport aux murs les mêmes conditions d installation telles qu indiquées dans le tableau ci dessous s appliquent quelle que soit la taille de l ASI A mm B mm C mm D mm Dégagements recommandés 50 1200 50 600 Dégagement minimum 0 1200 0 400 La table ci dessous indique le volume d air nécessaire pour une ventilation et un refro...

Page 420: ... etc NON Eau provenant d une source autre que la pluie NON Formation de glace NON Classification des conditions biologiques EN 60721 3 3 Agent d environnement Classe 3B1 3B2 3B3 a Flore NON Présence de moisissures champignons etc Présence de moisissures champignons etc b Faune NON Présence de rongeurs et d autres animaux nuisibles aux produits hors termites Présence de rongeurs et d autres animaux...

Page 421: ... surveillée et régulée de manière stricte catégorie des espaces propres X Sites sur lesquels l atmosphère est surveillée en permanence X Sites situés dans des régions rurales et urbaines présentant une faible activité industrielle et un trafic modéré X Sites situés dans des régions urbaines présentant une activité industrielle et ou un trafic important X Sites à proximité de sources industrielles ...

Page 422: ...lié à la terre Pour l installation de la batterie respecter strictement la norme EN62040 1 2 et suivez le manuel d installation de l ASI Pour obtenir la durée de vie de la batterie indiquée par le fabricant de la batterie la température de fonctionnement doit rester comprise entre 0 et 25 C Cependant bien que la batterie puisse fonctionner jusqu à 40 C il y aura une réduction significative de la d...

Page 423: ...oint de vue technique dépendent de la tension du courant absorbé par l ASI de la ligne de by pass et des batteries de la température ambiante et de la chute de tension Enfin la façon de poser les câbles doit également faire l objet d une attention particulière Pour plus d explications concernant le choix et le dimensionnement des câbles reportez vous aux normes CEI concernées en particulier la nor...

Page 424: ...4 1 RACCORDEMENT DES CÂBLES D ALIMENTATION Pour le raccordement électrique de l ASI KEOR HPE 200 250 300 kVA les câbles suivants doivent être raccordés Alimentation CC depuis la batterie Alimentation CA depuis le secteur avec redresseur et by pass Sortie CA vers les charges Les câbles doivent être protégés contre les courts circuits et les courants de fuite à la terre Les points de raccordement do...

Page 425: ...icatives Les câbles ont été conçus selon la norme CEI UNEL35024 1 en utilisant les données suivantes Câbles de cuivre en PVC évalués à 70 température ambiante égale à 40 C longueur maximale des câbles égale à 30 m chute de tension 0 5 câbles posés dans des cavités de structures ou des chemins de câbles à fond plein Les sections transversales données ne prennent pas en compte les courants de surcha...

Page 426: ...nsités en utilisant un disjoncteur avec bobine de déclenchement à émission raccordé à l ASI suivant le schéma de principe décrit Illustration 6 En cas de défaut de retour de tension de l ASI l ASI enverra un signal de déclenchement au disjoncteur pour isoler l ASI et ainsi protéger les circuits de distribution amont L installateur doit appliquer le marquage d avertissement suivant sur tous les iso...

Page 427: ...250 300 kVA Installation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA OMP06262 REV B 75 Illustration 6 Diagramme à une ligne KEOR HPE 200 250 300kVA avec connexion à un périphérique externe ...

Page 428: ...ments auxiliaires Illustration 7 Borniers KEOR HPE 200 250 kVA RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION INGRESSO RADDRIZZATORE RECTIFIER INPUT 1 N N 1 L1 R 1 L3 T 1 L2 S 2 L1 R 2 L2 S 2 L3 T 2 N N 3 L1 R 3 L3 T 3 L2 S RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION INGRESSO BY PASS BY PASS INPUT USCITA UPS UPS OUT...

Page 429: ...O CICLICO PLEASE RESPECT PHASE ROTATION INGRESSO RADDRIZZATORE RECTIFIER INPUT 1 N N 1 L1 R 1 L3 T 1 L2 S 2 L1 R 2 L2 S 2 L3 T 2 N N 3 L1 R 3 L3 T 3 L2 S RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION INGRESSO BY PASS BY PASS INPUT USCITA UPS UPS OUTPUT B N B 3 N N RISPETTARE LA POLARITA PLEASE RESPECT POLARITY BATTERIA BATTERY E...

Page 430: ...ite si de telles mises à la terre sont supprimées durant l installation ou la maintenance appliquable aux équipements et alimentations à base de batteries ne nécessitant pas d avoir un circuit d alimentation relié à la terre Pour l installation de la batterie respecter strictement la norme EN62040 1 2 et suivez le manuel d installation de l ASI Pour obtenir la durée de vie de la batterie indiquée ...

Page 431: ...ue La section utilisée pour ces borniers est de 6 mm2 Les contacts auxiliaires des interrupteurs MBCB BCB et OCB lorsqu ils ne sont pas fournis sur la carte doivent être obligatoirement connectés à l ASI Illustration 8 Bornes auxiliaires du KEOR HPE 200 250 300 kVA 4 5 1 By pass manuel externe Contact auxiliaire du commutateur de by pass manuel externe sur les bornes X10 1 2 Un contact normalement...

Page 432: ...rtie soit interrompue Dans le cas où la commande externe EPO n est pas fournie faire un pont entre les bornes 7 8 4 5 5 Contact auxiliaire de batterie Contat auxiliaire de batterie bornes X10 9 10 Ce contact auxiliaire est nécessaire pour indiquer la position de l isolateur ouvert fermé 4 5 6 Contact auxiliaire du Groupe electrogène Contact auxiliaire du Groupe electrogène des bornes X10 11 12 Un ...

Page 433: ...aces de série du KEORHPE 200 250 300 kVA RS232 USB il est utilisé pour la connexion de la programmation exclusive et le lgiciel de contrôle SRC 2 carte relais utilisée pour les répétitions à distance des statuts et alarmes PARALLEL OPTIONNEL utilisé pour la communication entre des ASI enparallèles MODBUS OPTIONNEL utilisé pour la transmission de données vers l extérieur via le protocole MODBUS RUT...

Page 434: ... normal Nom Statuts en fonctionnement normal RL1 Alarme A30 ALARME GENERALE Hors tension si alarme présente 2 3 Fermé DL1 On 1 2 Ouvert RL2 Alarme A1 DEFAUT SECTEUR Hors tension si alarme présente 5 6 Fermé DL2 On 4 5 Ouvert RL3 Allarme A9 FIN AUTONOMIE BATTERIE Hors tension si alarme présente 8 9 Fermé DL3 On 7 8 Ouvert RL4 Alarme A13 ONDULEUR EN DEHORS DES TOLERANCES Hors tension si alarme prése...

Page 435: ... de tels dispositifs sont installés en externe et leurs contacts auxiliaires proprement connectés au bornier de l ASI 5 1 VERIFICATIONS PRELIMINAIRES Avant de démarrer l unité assurez vous que tous les travaux d installation et de raccordement électrique ont été réalisés de manière professionnelle tous les câbles d alimentation et de commande sont correctement raccordés et serrés sur les borniers ...

Page 436: ... cela ne soit demandé dans les instructions affichées par le panneau avant Les composants internes de l ASI et ou la batterie pourraient être gravement endommagés Réaliser une installation électrique correcte par le câblage des contacts auxiliaires du bypass manuel de l interrupteur de sortie et de la protection batterie au bornier dédié à l ASI Cela permettra à la logique de commande d acquérir l...

Page 437: ...5 1 Fermer l interrupteur d entrée du redresseur RCB Ovrir quelques secondes l écran tactile démarre et affiche le schéma synoptique de l onduleur Illustration 11 UPS start up page 2 Après la phase de chargement du logiciel la logique de commande acquiert l état du système et le fonctionnement du commutateur RCB et affiche les séquences de fonctionnement Illustration 12 Rectifier start up ...

Page 438: ... REV B Illustration 13 Inverter start up 3 Lorsque l onduleur est correctement démarré fermez l interrupteur de dérivation SBCB lorsque cela est indiqué par l affichage La logique vérifie l exactitude de la séquence de phase de dérivation et de la valeur de tension efficace Illustration 14 Bypass start up 4 Fermer l interrupteur de batterie BCB lorsque cela est indiqué par l affichage ...

Page 439: ... situé dans l armoire de batteries externe ne peut être fermé que si la tension continue est en tolérance Des dommages sérieux à la fois à la batterie et à l équipement peuvent se produire si le disjoncteur est fermé avant que le panneau avant ne l exige 5 Fermer l interrupteur de sortie de l onduleur OCB pour connecter l onduleur au bus de charge Après cette opération le démarrage est terminé et ...

Page 440: ... l alimentation des charges Dans cette configuration le système peut être redémarré via la procédure de retour depuis la charge en by pass manuel sans qu il soit nécessaire de mettre les charges hors tension Bypass manuel Afin de réaliser correctement la procédure de basculement assurez vous que le système n affiche aucune alarme Lors d un by pass manuel la charge est alimentée directement par le ...

Page 441: ...teur Bypass_Sw est en position BYPASS et que l isolateur MBCB est fermé 1 Fermez l interrupteur d entrée du redresseur RCB Après quelques secondes l écran tactile démarre et affiche le schéma synoptique de l onduleur Illustration 18 REDEMARRAGE DEPUIS LE BY PASS MANUEL 2 Après la phase de chargement du logiciel la logique de commande acquiert l état du système et le fonctionnement du commutateur R...

Page 442: ...62 REV B 3 Fermez l interrupteur de batterie BCB lorsque cela est indiqué par l affichage Illustration 20 Connexion de la batterie 4 Fermer le commutateur de sortie OCB lorsque cela est nécessaire et immédiatement après l affichage vous devrez ouvrir le commutateur de dérivation manuelle MBCB L onduleur va démarrer Illustration 21 Fermeture de l interrupteur de sortie de l onduleur ...

Page 443: ...amento KEOR HPE UPS 200 250 300 kVA OMP06262 REV B 91 Illustration 22 Ouverture du commutateur de dérivation manuelle Illustration 23 Démarrage de l onduleur 5 Dès le démarrage de l onduleur il sera possible de transférer la charge Déplacez le commutateur de dérivation comme requis par l affichage pour terminer le démarrage de l onduleur ...

Page 444: ...0 250 300 kVA Installation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA 92 OMP06262 REV B Illustration 24 Transférer la charge Illustration 25 Redémarrer à partir du bypass manuel terminé ...

Page 445: ...tallation and start up of KEOR HPE UPS 200 250 300 kVA Installation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA OMP06262 REV B 93 LINGUA ITALIANA ...

Page 446: ...Installation and start up of KEOR HPE UPS 200 250 300 kVA Installation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA 94 OMP06262 REV B ...

Page 447: ...o BSP06 KEOR HPE 200 kVA BSO02 KEOR HPE 250 kVA BSS88 KEOR HPE 300 kVA Conservazione della documentazione Questo manuale e tutta la restante documentazione tecnica di supporto al prodotto devono essere conservati e possibilmente resi accessibili al personale nelle immediate vicinanze dell UPS Informazioni aggiuntive Nel caso le informazioni riportate nel presente manuale non fossero abbastanza esa...

Page 448: ... di dedicare il tempo per la lettura del seguente manuale Lo scopo di questo manuale è di descrivere brevemente le parti che compongono l UPS e di guidare l installatore o l utente ad una corretta installazione dell apparato nell ambiente di utilizzo L installatore o l utente dovrà leggere ed eseguire correttamente quanto dichiarato nel presente manuale con particolare riguardo alle richieste rela...

Page 449: ...isto di una targhetta di identificazione che riporta i dati nominali di funzionamento La targhetta è fissata nella parte interna della porta frontale Figura 1 Targhetta caratteristiche KEOR HPE 200 250 300 kVA Verificare le caratteristiche tecniche Prima di effettuare qualsiasi operazione di installazione e avviamento del dispositivo verificare che le caratteristiche tecniche siano compatibili con...

Page 450: ...ica sono da considerarsi tali solo se certificati dall azienda produttrice 2 3 3 Trasporto e movimentazione Durante il trasporto e la movimentazione del prodotto prestare la massima attenzione al fine di evitare di piegare o deformare le parti componenti e di modificare le distanze di isolamento Peso non distribuito Il peso dell UPS non è uniformemente distribuito Prestare particolare attenzione n...

Page 451: ...dispositivo all esposizione diretta dei raggi solari e non posizionarlo in prossimità di una fonte di calore Condizioni ambientali particolari L UPS è progettato per sopportare condizioni climatiche ed ambientali di esercizio normali come indicato nella specifica tecnica altitudine temperatura ambiente d esercizio umidità relativa condizioni ambientali di trasporto e stoccaggio Si rende necessarie...

Page 452: ...te elettrica di alimentazione ed al consumo elettrico reale della totalità delle apparecchiature collegate Verificare la conformità alle normative L UPS deve essere installato conformemente alle normative vigenti nel paese di installazione Sistema IT L apparecchiatura è stata progettata anche per essere collegata ad un sistema di distribuzione dell alimentazione IT Tutti i collegamenti elettrici d...

Page 453: ...ui fanno parte gli UPS devono seguire tutte le norme vigenti riguardanti la sicurezza equipaggiamenti tecnici e regolamenti antinfortunistici Il dispositivo deve essere avviato manovrato e disconnesso solamente da parte di personale autorizzato Le tarature possono essere modificate solo utilizzando il software di interfaccia originale Pericolo di lesioni a seguito shock elettrico Durante il funzio...

Page 454: ...ento e l eventuale disconnessione dalle sorgenti di alimentazione a causa dei condensatori interni che si scaricano lentamente Si consiglia quindi di attendere almeno 5 minuti prima di aprire le porte del dispositivo Pericolo di lesioni a seguito shock elettrico Eventuali interventi devono essere effettuati solamente in assenza di tensione e nel rispetto delle direttive sulla sicurezza Accertarsi ...

Page 455: ...a aerazione calore condotto o irradiato proveniente da altre fonti funghi insetti nocivi parassiti 2 4 TUTELA AMBIENTALE 2 4 1 Certificazione ISO 14001 Legrand è particolarmente sensibile all impatto ambientale dei propri prodotti per questo motivo l UPS è stato realizzato seguendo i più moderni criteri di eco progettazione certificazione ISO 14001 E stata prestata particolare attenzione nell util...

Page 456: ...odotto al costruttore si prega di utilizzare l imballaggio originale Pericolo per le persone a seguito di danni da trasporto Il danneggiamento meccanico dei componenti elettrici costituisce un grave pericolo per persone e cose Qualora si abbia il dubbio di una non completa integrità dell imballo o del prodotto entro ad esso contenuto contattare l azienda produttrice prima di effettuare l installaz...

Page 457: ...ne eretta Durante le manovre di carico e scarico rispettare sempre le indicazioni relative al baricentro del dispositivo contrassegnato sull imballaggio Per gli spostamenti dell UPS prima del posizionamento finale si consiglia di non rimuoverlo dal pancale in legno sul quale è fissato per evitare eventuali rischi di ribaltamento Prima del posizionamento rimuovere l UPS dal pancale togliendo le sta...

Page 458: ...iguarda le condizioni ambientali nel luogo di installazione in accordo alle normative correnti fare riferimento alla sezione Dimensioni di ingombro distanze minime dalle pareti e ventilazione Condizioni ambientali particolari Si rende necessario mettere in atto misure di protezione specifiche in caso di condizioni ambientali insolite fumi nocivi polveri polvere abrasiva umidità vapore aria salina ...

Page 459: ...o statico e pesi 859 850 900 750 880 970 300 713 90 5 63 38 Ø 1 3 x 4 PIASTRA INGRESSO CAVI Figura 3 Pianta di base La base di appoggio dell UPS deve essere progettata per sopportare il peso del dispositivo e per garantirne il supporto saldo e sicuro La capacità portante deve essere conforme al carico statico indicato nella tabella seguente Potenza kVA 200 250 300 Peso kg 530 630 675 Carico static...

Page 460: ...llation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA 108 OMP06262 REV B 3 3 2 Dimensioni di ingombro distanze minime dalle pareti e ventilazione Figura 4 Dimensioni di ingombro Figura 5 Distanze di rispetto ...

Page 461: ...o possibile il corretto flusso di aria Per tutte le taglie di UPS valgono le stesse condizioni di installazione per quanto riguarda le distanze minime dalle pareti come indicate nella tabella seguente A mm B mm C mm D mm Distanze raccomandate 50 1200 50 600 Distanze minime 0 1200 0 400 La tabella seguente mostra il volume d aria richiesto per la ventilazione e il raffreddamento ottimali del dispos...

Page 462: ...O Acqua di origine diversa dalla pioggia NO Formazione di ghiaccio NO Classificazione delle condizioni biologiche EN 60721 3 3 Parametro ambientale Classe 3B1 3B2 3B3 c Flora NO Presenza di muffa funghi ecc Presenza di muffa funghi ecc d Fauna NO Presenza di roditori e altri animali dannosi ai prodotti escludendo le termiti Presenza di roditori e altri animali dannosi ai prodotti includendo le ter...

Page 463: ...tmosfera strettamente monitorata e controllata categoria camera pulita X Luoghi con atmosfera continuamente controllata X Luoghi posti in zone rurali e urbane dove sono modeste le attività industriali e il traffico è moderato X Luoghi in zone urbane con attività industriali e o grande traffico X Luoghi posti in prossimità di sorgenti industriali con emissioni chimiche X Luoghi posti all interno di...

Page 464: ...e messo a terra Seguire le istruzioni d installazione Per l installazione delle batterie attenersi rigorosamente alle EN62040 1 inoltre dovrà essere seguito il manuale di installazione dell UPS Per ottenere una durata di vita della batteria pari a quella indicata dal costruttore la temperatura di esercizio deve essere compresa fra 0 e 25 C La batteria può comunque operare fino a 40 C con forte rid...

Page 465: ...e fatta tenendo in considerazione gli aspetti tecnici economici e di sicurezza La scelta e il dimensionamento dei cavi dal punto di vista tecnico è funzione della tensione della corrente assorbita dall UPS dalla rete bypass e dalle batterie della temperatura ambiente e della caduta di tensione infine si deve tenere in particolare considerazione il tipo di posa del cavo Ulteriori chiarimenti sulla ...

Page 466: ...S alla rete 4 1 COLLEGAMENTO CONDUTTORI DI POTENZA Per il collegamento elettrico dell UPS KEOR HPE 200 250 300 kVA è necessario allacciare i seguenti conduttori Alimentazione DC da batteria se la batteria è esterna Alimentazione AC dalla rete di alimentazione raddrizzatore e bypass Uscita AC verso i carichi Pericolo di lesioni a seguito shock elettrico Sono presenti tensioni molto elevate ai capi ...

Page 467: ...a tabella precedente sono indicative I cavi sono stati dimensionati in accordo alla norma CEI UNEL35024 1 utilizzando i seguenti dati cavi unipolari in rame con isolamento in PVC e temperatura massima di 70 C temperatura ambiente pari a 40 C massima lunghezza dei cavi pari a 30 m caduta di tensione 0 5 posa dei cavi in cavità di strutture o passerelle non perforate Le sezioni dei cavi non tengono ...

Page 468: ...ass mediante MCCB dotato di una bobina a lancio di corrente e collegata all UPS secondo lo schema elettrico riportato in Figura 6 In caso di guasto di backfeed rilevato dall UPS l UPS invierà alla bobina un segnale di 230 Vac impulsivo che farà trippare il MCCB quindi isolerà l UPS al fine di proteggere i circuiti di distribuzione a monte dell UPS L installatore deve applicare la seguente etichett...

Page 469: ...S 200 250 300 kVA Installation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA OMP06262 REV B 117 Figura 6 Schema unifilare KEOR HPE 200 250 300kVA con collegamento al dispositivo esterno ...

Page 470: ...i potenza e delle connessioni ausiliarie Figura 7 Morsettiera KEOR HPE 200 250 kVA RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION INGRESSO RADDRIZZATORE RECTIFIER INPUT 1 N N 1 L1 R 1 L3 T 1 L2 S 2 L1 R 2 L2 S 2 L3 T 2 N N 3 L1 R 3 L3 T 3 L2 S RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION INGRESSO BY PASS BY PASS INPU...

Page 471: ... 300 kVA RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION INGRESSO RADDRIZZATORE RECTIFIER INPUT 1 N N 1 L1 R 1 L3 T 1 L2 S 2 L1 R 2 L2 S 2 L3 T 2 N N 3 L1 R 3 L3 T 3 L2 S RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION RISPETTARE IL SENSO CICLICO PLEASE RESPECT PHASE ROTATION INGRESSO BY PASS BY PASS INPUT USCITA UPS UPS OUTPUT B N B 3 N N RISPETTARE LA POLARITA PLEASE RESPECT ...

Page 472: ...are una scossa elettrica La probabilità può essere ridotta se i collegamenti di terra vengono interrotti durante l installazione e la manutenzione applicabile ad apparecchiature e ad alimentazioni a batteria poste a distanza prive di circuito di alimentazione messo a terra Installazione batterie Per l installazione delle batterie attenersi rigorosamente alle EN62040 1 paragrafo 7 6 Per ottenere un...

Page 473: ...iliari degli interruttori MBCB BCB e OCB esterni se previsti devono obbligatoriamente essere collegati all UPS Figura 8 Morsetti ausiliari KEOR HPE 200 250 300 kVA 4 5 1 Bypass manuale esterno Contatto ausiliario dell interruttore di bypass manuale esterno se previsto morsetti X10 1 2 Un contatto normalmente aperto deve essere utilizzato alla chiusura del contatto vedere procedura di Bypass Manual...

Page 474: ...ircuitare i morsetti 7 8 4 5 5 Contatto ausiliario sezionatore di batteria Contatto ausiliario del sezionatore di Batteria morsetti X10 9 10 Contatto ausiliario necessario per l indicazione della posizione del sezionatore aperto chiuso 4 5 6 Contatto ausiliario Generatore Diesel Contatto ausiliario proveniente da gruppo elettrogeno morsetti X10 11 12 Deve essere utilizzato un contatto normalmente ...

Page 475: ...E 200 250 300kVA RS232 USB utilizzata per il collegamento con software proprietario di programmazione e controllo SRC 2 scheda relè utilizzata per la ripetizione a distanza di stati di funzionamento e allarmi PARALLELO OPZIONALE utilizzata per la comunicazione tra UPS in configurazione parallelo MODBUS utilizzata per la trasmissione dei dati all esterno per mezzo di protocollo MODBUS RUT RS485 SON...

Page 476: ...i Stato M1 Led Pin Stato in funzionamento normale Nome Stato in funzionamento normale RL1 Allarme A30 ALLARME GENERALE Non energ se allarme presente 2 3 Chiuso DL1 On 1 2 Aperto RL2 Allarme A1 MANCANZA RETE Non energ se allarme presente 5 6 Chiuso DL2 On 4 5 Aperto RL3 Allarme A9 FINE AUT BATTERIA Non energ se allarme presente 8 9 Chiuso DL3 On 7 8 Aperto RL4 Allarme A13 INV FUORI TOL Non energ se...

Page 477: ...esterni Tutte le procedure che seguono fanno riferimento al dispositivo di interruzione BCB e sono valide solamente se tale dispositivo è installato esternamente e i suoi contatti ausiliari opportunamente cablati agli appositi morsetti nell UPS 5 1 VERIFICHE PRELIMINARI Prima di iniziare la procedura di avvio verificare che tutti i lavori di installazione e allacciamento elettrico siano stati eseg...

Page 478: ... dei contatti ausiliari Durante l installazione elettrica prestare cura al cablaggio dei contatti ausiliari degli isolatori di bypass manuale uscita e batteria che vanno collegati agli appositi morsetti sull UPS In questo modo la logica di controllo acquisisce lo stato degli interruttori per guidare l operatore durante le procedure di avvio e bypass manuale L avviamento del sistema è completamente...

Page 479: ...2 REV B 127 1 Chiudere il sezionatore di ingresso raddrizzatore RCB Dopo alcuni secondi il touch screen si avvierà e mostrerà il diagramma sinottico dell UPS Figura 11 Schermata avvio UPS 2 Dopo la fase di caricamento del software la logica di controllo acquisisce lo stato del sistema a seguito della chiusura di RCB e mostra le sequenze di avviamento Figura 12 Avvio raddrizzatore ...

Page 480: ... UPS 200 250 300 kVA 128 OMP06262 REV B Figura 13 Avvio inverter 3 Appena l inverter è correttamente avviato chiudere il sezionatore SBCB quando indicato dal display La logica controlla che la sequenza fasi e il valore RMS della tensione di bypass siano corrette Figura 14 Avvio bypass 4 Chiudere il sezionatore di batteria BCB quando indicato dal display ...

Page 481: ...sura del sezionatore BCB posto nell armadio esterno può essere effettuata solamente se la tensione DC è in tolleranza Se effettuata prima che venga richiesta dal pannello frontale può causare seri danni all apparecchiatura e o alla batteria 5 Chiudere il sezionatore di uscita OCB per connettere l UPS alla sbarra di carico Dopo questa operazione l avviamento è completo e il display mostra il sinott...

Page 482: ... discontinuità di alimentazione sui carichi In questa configurazione tramite la procedura di ritorno da carico su bypass manuale è anche possibile riavviare il sistema senza dover disalimentare i carichi Bypass manuale Per eseguire la procedura di trasferimento in modo corretto verificare che non siano presenti allarmi sul sistema In bypass manuale il carico è alimentato direttamente dalla rete d ...

Page 483: ... selettore Bypass_Sw sia in posizione BYPASS e il sezionatore MBCB Chiuso 1 Chiudere il sezionatore di ingresso raddrizzatore RCB Dopo alcuni secondi il touch screen si avvierà e mostrerà il diagramma sinottico dell UPS Figura 18 Avvio da bypass manuale 2 Dopo la fase di caricamento del software la logica di controllo acquisisce lo stato del sistema a seguito della chiusura di RCB e mostra le sequ...

Page 484: ...300 kVA 132 OMP06262 REV B 3 Chiudere il sezionatore di batteria BCB quando indicato dal display Figura 20 Connessione della batteria 4 Chiudere il sezionatore OCB quando richiesto immediatamente dopo il display richiederà di aprire il sezionatore di bypass manuale MBCB A seguito di tale operazione l inverter si avvierà Figura 21 Chiusura del sezionatore uscita UPS ...

Page 485: ...A Installazione e avviamento KEOR HPE UPS 200 250 300 kVA OMP06262 REV B 133 Figura 22 Apertura del sezionatore di bypass manuale Figura 23 Avvio inverter 5 Appena l inverter è correttamente avviato sarà possibile trasferire il carico Muovere il selettore Bypass SW come richiesto per completare l avviamento dell UPS ...

Page 486: ...PE UPS 200 250 300 kVA Installation et démarrage de l ASI KEOR HPE 200 250 300 kVA Installazione e avviamento KEOR HPE UPS 200 250 300 kVA 134 OMP06262 REV B Figura 24 Trasferimento del carico Figura 25 Avvio da bypass manuale completato ...

Page 487: ...e ENGLISH LANGUAGE 11 1 SCOPE 12 2 SAFETY RULES AND WARNINGS 13 3 GENERAL UPS DESCRIPTION 14 3 1 TYPOLOGY 14 3 2 SYSTEM DESCRIPTION 14 3 2 1 Rectifier 14 3 2 2 Inverter 15 3 2 3 Battery and battery charger 15 3 2 4 Static bypass 15 3 2 5 Manual bypass 15 3 3 OPERATING STATUS 16 3 3 1 Normal operation 16 3 3 2 Green Conversion 16 3 3 3 Bypass operation 17 3 3 4 Battery operation 17 3 3 5 Manual byp...

Page 488: ...tery test 33 5 3 3 Resetting the history log 34 5 3 4 Modifying the operating mode ECO MODE 34 5 4 SETTINGS AND ADVANCED OPERATIONS 35 5 4 1 Setting date and time 36 5 4 2 Setting the display language 37 5 4 3 Setting the battery 38 5 4 4 New battery 39 5 4 5 Setting the RS485 user interface parameters 39 5 4 6 Setting the display network parameters 39 5 4 6 1 Setting the LAN parameters 39 5 4 6 2...

Page 489: ...É ET AVERTISSEMENTS 67 3 DESCRIPTION GÉNÉRALE DE L ALIMENTATION SANS COUPURE UPS 68 3 1 TYPOLOGIE 68 3 2 DESCRIPTION DU SYSTÈME 68 3 2 1 Redresseur 68 3 2 2 Onduleur 69 3 2 3 Batterie et chargeur de batterie 69 3 2 4 Commutateur de dérivation statique 69 3 2 5 Commutateur de dérivation manuelle 69 3 3 ÉTAT D EXPLOITATION 70 3 3 1 Fonctionnement normal 70 3 3 2 Conversion écologique 70 3 3 3 Foncti...

Page 490: ...9 5 4 1 Configuration de la date et de l heure 90 5 4 2 Configuration de la langue d affichage 91 5 4 3 Configuration de la batterie 92 5 4 4 Nouvelle batterie 93 5 4 5 Configuration des paramètres de l interface utilisateur RS485 93 5 4 6 Configuration des paramètres réseau d affichage 93 5 4 6 1 Configuration des paramètres LAN 93 5 4 6 2 Configuration des paramètres NTP 94 5 4 6 3 Modification ...

Page 491: ...LE E AVVERTENZE DI SICUREZZA 121 3 DESCRIZIONE GENERALE DELL UPS 122 3 1 TIPOLOGIA 122 3 2 DESCRIZIONE DEL SISTEMA 122 3 2 1 Raddrizzatore 122 3 2 2 Inverter 123 3 2 3 Batteria e carica batteria 123 3 2 4 Bypass statico 123 3 2 5 Bypass manuale 123 3 3 STATI DI FUNZIONAMENTO 124 3 3 1 Funzionamento normale 124 3 3 2 Green Conversion 124 3 3 3 Funzionamento da bypass 125 3 3 4 Funzionamento da batt...

Page 492: ...splay 145 5 4 3 Impostazioni batteria 146 5 4 4 Nuova batteria 147 5 4 5 Impostazione parametri di interfaccia utente RS485 147 5 4 6 Impostazione parametri di rete del touch screen 147 5 4 6 1 Impostazione parametri LAN 147 5 4 6 2 Impostazione parametri NTP 148 5 4 6 3 Modifica dei parametri 149 5 5 INFORMAZIONI SUL SISTEMA 150 5 5 1 Informazioni dispositivo 150 5 5 2 Informazioni parallelo 151 ...

Page 493: ...izzo dell UPS OMP06263 REV B 7 5 5 4 Informazioni sulla comunicazione RS485 154 5 5 5 Versioni firmware 154 5 5 6 Informazioni relative all assistenza 154 6 GUASTI E ALLARMI 155 6 1 DEFINIZIONE DEGLI STATI DI FUNZIONAMENTO 156 6 2 CONTROLLO DEI GUASTI 159 ...

Page 494: ...ory log page 2 29 Picture 16 Saving the history log 29 Picture 17 Access password to the Controls section 32 Picture 18 Controls section 32 Picture 19 Access password to the Settings section 35 Picture 20 Settings section 35 Picture 21 Clock manual setting 36 Picture 22 Clock automatic setting 37 Picture 23 Language setting 37 Picture 24 Battery parameters setting 38 Picture 25 Battery parameters ...

Page 495: ... journal des historiques 83 Image 17 Mot de passe d accès à la section Controles 86 Image 18 Section Controles 86 Image 19 Mot de passe d accès à la section Reglages 89 Image 20 Section Reglages 89 Image 21 Configuration manuelle de l horloge 90 Image 22 Configuration automatique de l horloge 91 Image 23 Configuration de la langue 91 Image 24 Configuration des paramètres de la batterie 92 Image 25...

Page 496: ...37 Figura 17 Password di accesso alla sezione Controlli 140 Figura 18 Sezione Controlli 140 Figura 19 Password di accesso alla sezione Impostazioni 143 Figura 20 Sezione Impostazioni 143 Figura 21 Impostazione manuale orologio 144 Figura 22 Impostazione automatica orologio 145 Figura 23 Impostazione lingua 145 Figura 24 Impostazione parametri batteria 146 Figura 25 Impostazione capacità batteria c...

Page 497: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMP06263 REV B 11 ENGLISH LANGUAGE ...

Page 498: ... 300 kVA BST87 KEOR HPE 400 kVA BSU14 KEOR HPE 500 kVA Storing documentation This manual and any other supporting technical documentation relating to the product must be stored and made accessible to personnel in the immediate vicinity of the UPS Further information In the event that the information provided in this manual is not sufficiently exhaustive please contact the manufacturer of the devic...

Page 499: ...ned in the manuals must be strictly followed Injury hazard due to device failure Potentially hazardous situations may arise in case of UPS failure Do not use the device if visibly damaged Maintain the device regularly to identify possible failure Possible device damage Whenever work is carried out on the device make sure all actions are taken in order to avoid electrostatic discharges which might ...

Page 500: ...e line or the plugs supplied by the UPS making the User aware of this fact Picture 1 Block diagram The UPS uses IGBT technology with a high switching frequency in order to allow a low distortion of the current re injected into the supply line as well as high quality and stability of output voltage The components used assure high reliability very high efficiency and maintenance easiness 3 2 SYSTEM ...

Page 501: ...ectifier s control electronics The battery is charged according to the DIN 41773 Standard every time it has been partially or completely discharged When its full capacity is restored it is disconnected from the DC bus by means of a static switch in order to save energy reduce the stress due to the AC ripple thus increasing the lifetime This operating mode is called Green Conversion It is however p...

Page 502: ...the inverter and compensates mains voltage as well as load variations keeping the DC voltage constant At the same time it provides to charge the battery The inverter converts the DC voltage into an AC sine wave with stabilized voltage and frequency and also supplies the load via its static switch SSI Picture 2 Normal operation 3 3 2 Green Conversion During the operation in Green Conversion mode th...

Page 503: ... 48 hours Lost capacity 20 Additional charge for 96 hours Such values complies with the recommendations of the main battery manufacturers Set the right battery capacity The UPS front panel allows the setting of the battery parameters including the rated capacity Considering the importance that such value assumes for the correct execution of the charge control algorithm it is highly recommended to ...

Page 504: ...y The system restart from the black out condition can be customized based on the requirements of the plant in three different modes Bypass loads are supplied as soon as the bypass line is available factory configuration Inverter loads are supplied by the inverter even if the bypass line is available when the battery voltage has reached a programmed threshold after the rectifier restart Man Inverte...

Page 505: ...auxiliary contacts Carry out a proper electrical installation by wiring the auxiliary contacts of the manual bypass and output isolators to the dedicated terminals on board the UPS This will allow the control logic to acquire the status of the switches and guide the operator during the start up and manual bypass procedures For further information refer to the section Installation and start up Duri...

Page 506: ...n and control devices of the UPS is intended for authorized personnel only We recommend to check the training of the personnel responsible for the use and maintenance of the system 3 4 1 Isolators The isolators provided on the UPS are used to isolate the power components of the device from the AC supply line from the storage battery and from the load Voltage present on terminals The isolators do n...

Page 507: ...d you are sure that there is no hazard to persons and things 3 4 3 Normal Bypass selector It is used during the manual bypass procedure when it is necessary to isolate the UPS for maintenance or repair Follow the procedures contained in the manual The Normal Bypass selector shall only be operated in accordance with the procedures specified in the installation and start up section The manufacturer ...

Page 508: ...ng through the pages of the touch screen is possible through the seven icons provided on the right hand side the icon with the up down arrows controls the display communication Description of the icon Icon Assigned functions Home Goes back to the Home page Measures Enters the Measures section A page of the Measures section is currently displayed Controls Enters the Controls section A page of the C...

Page 509: ...section A page of the Info section is currently displayed Back Goes back one page Communication Controls the communication between the panel and the UPS electronics Communication Ok Controls the communication between the panel and the UPS electronics Communication Ko in case of communication error between the touch screen and the UPS control logic 4 2 STATUS BAR The status bar at the bottom provid...

Page 510: ...sections of the control panel from the Home page directly 5 1 DISPLAYING THE MEASURES Pressing on a specific object gives access to the display of the measurements of that specific section of the UPS Picture 9 UPS front panel Home page For example by clicking on the object indicated in the figure above you access the Measures Inverter screen visible below Picture 10 Measures Inverter ...

Page 511: ... is given below Sub page Displayed data Accuracy INPUT Rectifier input voltage 1 1 V Rectifier input current 1 A Frequency 0 1 Hz Input power 1 kVA OUTPUT Voltage 1 1 V Current 1 A Load percentage 1 Active power 1 kW Apparente power 1 kVA Frequency 0 1 Hz BYPASS Voltage 1 1 V Frequency 0 1 Hz INVERTER Voltage 1 1 V Frequency 0 1 Hz AC DC Rectifier output voltage 1 V BATTERY Voltage and current 1 V...

Page 512: ...izzo dell UPS 26 OMP06263 REV B Sub page Displayed data Accuracy TEMPERATURE 2 Battery 0 1 C UPS 0 1 C 1 The voltage measures are always given referred to the phase to neutral value 2 The temperatures are displayed only if the relevant probe is installed ...

Page 513: ...perating status or the history log can be selected Picture 12 Alarms section 5 2 1 Displaying the operating status Press UPS status to show the UPS operating status which includes possible active alarms Picture 13 Alarms section The current system status is shown in case the list is longer than the page capacity 8 lines it can be scrolled by sliding a finger on the screen ...

Page 514: ...ory Picture 14 History log page 1 The first event shown is the latest one in order of time a new event makes all the other events automatically shift one position clearing the oldest event Each line shows the number of the event position within the list the alarm code and date and time an asterisk indicates the automatic reset of the alarm The maximum number of events which can be shown is equal t...

Page 515: ...ing page Picture 16 Saving the history log The touch screen automatically recognizes when an external memory support USB stick or SD card is inserted and changes the colour of the relevant icon from grey disabled to white enabled The text file that will be saved contains the same information available on the History pages completed with the decription of each event ...

Page 516: ... OVER CURRENT A16 BYPASS LOAD A50 CURRENT INVERTER SATURED A17 RETRANSFER BLOCKED A51 BATTERY TEMPERATURE A18 MBCB CLOSED MBCB BUS CLOSED A52 UNDER VOLTAGE LOCKOUT A19 OCB OPEN A53 FIRMWARE ERROR A20 OVERLOAD A54 CAN ERROR A21 THERMAL IMAGE A55 PARALLEL CABLE DISCONNECTED A22 BYPASS SWITCH A56 MAINS UNBALANCED A23 EPO PRESSED A57 CONTACTOR FAILURE A24 HIGH TEMPERATURE A58 INVERTER CURRENT UNBALANC...

Page 517: ...e ALARMS STATUS menu is entered The alarms are shown when they are present and must be silenced with the buzzer The alarms remain displayed whilst they are present and they are automatically stored in the event log with date and time Description of alarms and statuses For a more detailed description of the alarms and statuses see the Faults and alarms section of the present manual ...

Page 518: ...icon will show the control section access page protected by password Picture 17 Access password to the Controls section Picture 18 Controls section Password protected access The CONTROLS menu is protected by a password set by the factory in order to prevent access to unauthorized personnel We recommend minimum disclosure of the access password ...

Page 519: ... A44 INVERTER DESATURATION A50 CURRENT INVERTER SATURED A52 UNDER VOLTAGE LOCKOUT A55 PARALLEL CABLE DISCONNECTED System restart after a shutdown due to EPO activation For a description of the UPS status in each of the failure conditions listed above please refer to the Faults and alarms section A28 CRITICAL STOP NOTE Reccomended to performe the service test before restart the UPS The UPS is equip...

Page 520: ...rter is turned on ready to take over in case of anomalies of the mains The transfer occurs in a maximum time of 10 ms The stability of the AC mains is controlled bu a specific algorithm which provides to automatically de activate the ECO MODE mode in case the voltage or frequency are not compliant with the programmed requirements Modifying the UPS operating mode ECO MODE The modification of the UP...

Page 521: ...icon will show the setting section access page protected by password Picture 19 Access password to the Settings section Picture 20 Settings section Password protected access The SETTINGS menu is protected by a password set by the factory in order to prevent access to unauthorized personnel We recommend minimum disclosure of the access password ...

Page 522: ...ime Date and time may be set via the CLOCK page Picture 21 Clock manual setting Setting the current date and time correctly The correct setting of the date and time is essential for the recording of the event log The system also allows the setting of a NTP server for the synchronization of date and time Such configuration mode is enabled by pressing the label Disabled As the NTP server is enabled ...

Page 523: ...e configured via the Network configuration pages in the Settings section In case the server does not respond or the LAN connection is lacking the message NTP ERROR will be displayed 5 4 2 Setting the display language The following picture shows the languages that can be set Picture 23 Language setting The language selection is made pressing one of the flags ...

Page 524: ...ge battery the BATTERY PARAM section allows to set such data Each single settable parameter can be accessed via the following page Picture 24 Battery parameters setting The various parameters setting pages are similar to each other and requires the operator to enter and confirm the value the setting page of the battery capacity is given below as a reference Picture 25 Battery parameters setting ...

Page 525: ...tting the RS485 user interface parameters The parameters regarding the communication via RS485 interface can be set in the MODBUS RS485 section This section allows to set the ModBus address the communication mode and the data transmission speed 5 4 6 Setting the display network parameters The NETWORK CONFIG section allows to configure the parameters related to the LAN network and to the system tim...

Page 526: ...B Picture 27 LAN parameters setting 5 4 6 2 Setting the NTP parameters The NTP service parameters which can be set are the following Primary NTP server address Secondary NTP server address NTP Enabling Disabling is performed in the menu SETTINGS CLOCK Picture 28 NTP parameters setting ...

Page 527: ... will be displayed on the editable string in the upper part of the page together with a keypad Picture 29 Modification of numerical parameters The fields related to the NTP servers may either be numerical IP address of the remote server or alphanumerical when the remote server can be reached via a web address In such case the keypad that will appear in the page is complete Picture 30 Modification ...

Page 528: ... information about the UPS press the related icon to open the main page Picture 31 Info section All the data shown in the varius sections are set during the factory test via a specific interface software and cannot be modified by anyone except for personnel authorized by the manufacturer 5 5 1 Device information Picture 32 Device information ...

Page 529: ...rrent system date and time setting 5 5 2 Parallel information The page containing the information about the parallel is only enabled if the UPS is in parallel with others UPS Picture 33 Parallel information 5 5 2 1 Parallel index The first number identifies the position of that specific UPS within the parallel system The second number represents the total number of UPS units 5 5 2 2 Master Slave p...

Page 530: ...s that the system is redundant and the redundancy index is indicated by number X For example in a system composed of 3 UPS units REDUNDANT 2 means that only one of the UPS units is sufficient to feed the load 5 5 2 5 Message statistics The statistics section regarding the messages exchanged on the communication buses consists of three different parts CAN STAT SSW Number of messages received and pe...

Page 531: ...ectively The brackets around a letter indicate that we are working on that specific UPS unit A question mark next to a number indicates that that UPS unit is not communicating on the data bus 5 5 3 4 Parallel type The string may have two values POWER or REDUNDANT x POWER means that the parallel system is so set as to require the presence of all the UPS units to feed the load REDUNDANT x means that...

Page 532: ... the settings of the communication port as regards the assigned ModBus address the communication mode and the data transmission speed 5 5 5 Firmware release Picture 36 Firmware release The second page of the firmware release info contains the license contract related to the touch screen operating software 5 5 6 Service information The SERVICE menu provides important information regarding the techn...

Page 533: ...larm code and a brief description are shown Injury hazard due to electric shock Before carrying out any operation on the UPS make sure that all the safety precautions are adhered to Any work on the unit must be carried out by qualified personnel Internal components can only be accessed after disconnecting the device from supply sources Always use protective devices designed for each type of activi...

Page 534: ...e inverter is ready to feed the load Status S4 INVERTER LOAD Description The inverter feeds the load Operating condition The load is fed via the static inverter switch Status S5 INVERTER BYPASS SYNCHRONIZED Description The inverter is synchronized with the bypass Operating condition The synchronization between the inverter and the bypass is locked and the static switch can change over from one sou...

Page 535: ...on The battery is charging Operating condition The battery static switch is closed and the battery is in the second and final phase of the I U charging mode DIN 41773 with constant voltage and decreasing current Status S16 HIGH BYPASS COMMUTATION Description Switching with high bypass voltage Operating condition Switching from inverter to bypass with inverter switch off caused by the bypass voltag...

Page 536: ... the phase rotation 2 If the alarm persists contact our Technical Support Service Alarm A3 BOOSTER STOPPED Description The rectifier has been temporarily disconnected and the inverter is fed by the battery Possible causes Instability of the AC line voltage or frequency Possible fault in the rectifier control circuit Solutions 1 Check the parameters of the AC line voltage 2 Restart the device 3 If ...

Page 537: ...of the battery Possible causes A battery test has been started automatically if set or manually by the user Solutions 1 Wait for the test to end and check possible battery faults Alarm A7 BCB OPEN Description The battery isolator is open Possible causes Battery isolator open Solutions 1 Check the status of the battery isolator 2 Check the functionality of the auxiliary contact of the isolator 3 Ch...

Page 538: ...ery 2 Reset the system 3 If the alarm persists contact our Technical Support Service Alarm A11 SHORT CIRCUIT Description The current sensor has detected a short circuit at the output Possible causes Load problem Measuring circuit failure Solutions 1 Check the loads connected to the UPS output 2 If the alarm persists contact our Technical Support Service Alarm A12 STOP TIMEOUT SHORT CIRCUIT Descrip...

Page 539: ...nection of power cables Solutions 1 Check the phase rotation 2 If the alarm persists contact our Technical Support Service Alarm A15 BYPASS FAULT Description The voltage or frequency of the bypass line are out of tolerance Possible causes Bypass line instability or failure Wrong phase rotation Solutions 1 Check the connections to the mains 2 Check the stability of mains voltage 3 If the alarm pers...

Page 540: ...f the manual bypass isolator 2 Check the functionality of the auxiliary contact of the isolator 3 If the alarm persists contact our Technical Support Service Alarm A19 OCB OPEN Description The output isolator is open Possible causes Output isolator open Solutions 1 Check the status of the output isolator 2 Check the functionality of the auxiliary contact of the isolator 3 If the alarm persists con...

Page 541: ...chnical Support Service Alarm A23 EPO PRESSED Description The system is blocked due to the activation of the emergency power off button Possible causes Activation of the local or remote emergency power off button Solutions 1 Release the emergency power off button and reset the alarm 2 If the alarm persists contact our Technical Support Service Alarm A24 HIGH TEMPERATURE Description High temperatur...

Page 542: ...controller has detected an error in the parameters stored in EEPROM Possible causes Wrong parameters entered during programming Solutions 1 Contact our Technical Support Service Alarm A28 CRITICAL STOP Description An alarm has been activated which causes the shutdown of part of the UPS rectifier inverter static switch Possible causes System failure Solutions 1 Check which alarms are present and ca...

Page 543: ...capacitors towards the middle point are different Possible causes Possible failure on the measuring circuit Possible fault of DC capacitors Solutions 1 Reset the system 2 If the alarm persists contact our Technical Support Service Alarm A34 SERVICE REQUIRED Description A UPS check is necessary Possible causes Possible UPS fault Solutions 1 If the alarm persists contact our Technical Support Servic...

Page 544: ... isolator 2 Check the functionality of the auxiliary contact of the isolator 3 If the alarm persists contact our Technical Support Service Alarm A38 INVERTER LOAD Description The load is fed by the inverter This alarm is active for UPS systems in ECO mode where the preferential supply is from the bypass line Possible causes Temporary changeover due to bypass line failure Solutions 1 Verify the sta...

Page 545: ...auses The UPS detected the DC current out of limits and switch off the inverter booster and disconnected the battery from the UPS Solutions 1 Check that there aren t short circuit in DC bus 2 Check the battery current sensor 3 Check the battery blocks 4 If the alarm persists contact our Technical Support Service Alarm A42 LOST OF REDUND POWER SUPPLY Description Failure of the redundant auxiliary p...

Page 546: ...k the air conditioning system if present 4 If the alarm persists contact our Technical Support Service Alarm A46 LOST OF REDUNDANCY Description This alarm is only active on PARALLEL systems Continuity is not ensured in the event of a fault on one of the UPS units Possible causes The total load is higher than the maximum expected value Possible failure on the measuring circuit Solutions 1 Check the...

Page 547: ...alous temperature in the battery cabinet Possible failure on the measuring circuit Solutions 1 Check the temperature on the batteries and remove the cause of the alarm if any 2 If the alarm persists contact our Technical Support Service 3 Alarm A52 UNDER VOLTAGE LOCKOUT Description The inverter is blocked because of an anomaly on the control power supply Possible causes Internal error Solutions 1 ...

Page 548: ...ter conctactor is fault This alarm is only active when the contactor is installed an anabled through eeprom manager Possible causes Aux contactor Fault Wiring circuit Fault or PCB Fault Solutions 1 Check the auxiliary contact functions check the interconnection cables or PCB 2 Contact our Technical Support Service Alarm A58 INVERTER CURRENT UNBALANCED Description The inverter s bridge currents are...

Page 549: ...S 3 Verify the battery blocks 4 Verify the status of the UPS 5 Verify the DC voltage value 6 If the alarm persists contact our Technical Support Service Alarm A62 MAINS OVERVOLTAGE Description Sudden increase of the AC input voltage fast sensor Possible causes Voltage spike on the AC mains Possible internal fault Solutions 1 Check the mains voltage 2 If the alarm persists contact our Technical Sup...

Page 550: ...3 REV B Alarm A64 ULTRA FAST GRID MONITOR Description Sudden drop of the AC input voltage fast sensor Possible causes Voltage drop on the AC mains brown out Possible internal fault Solutions 1 Check the mains voltage 2 If the alarm persists contact our Technical Support Service ...

Page 551: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMP06263 REV B 65 LANGUE FRANÇAIS ...

Page 552: ... 300 kVA BST87 KEOR HPE 400 kVA BSU14 KEOR HPE 500 kVA Documentation à mettre en réserve Ce manuel et toute autre documentation d appui technique relative au produit doivent être entreposés et rendus accessibles au personnel dans le voisinage immédiat de l UPS Informations complémentaires Dans le cas où les informations fournies dans ce manuel ne sont pas suffisamment exhaustives veuillez contacte...

Page 553: ...être strictement suivies Risque de blessure dû à une panne du dispositif Des situations potentiellement dangereuses peuvent survenir en cas de panne de l alimentation sans coupure UPS Ne pas utiliser l appareil si visiblement endommagé Faire l entretien de l appareil régulièrement pour identifier la panne possible Dommage du dispositif possible Chaque fois que le travail est effectué sur l apparei...

Page 554: ...onscient de ce fait Image 1 Schéma fonctionnel Le système d alimentation sans coupure UPS et la technologie du transistor bipolaire à porte isolée IGBT avec une fréquence élevée de commutation de façon à permettre une faible distorsion du courant réinjecté dans la ligne d alimentation ainsi qu une qualité et stabilité élevées de la tension de sortie de courant Les composantes utilisées garantissen...

Page 555: ...resseur La batterie est chargée selon la norme DIN 41773 chaque fois qu elle a été partiellement ou complètement déchargée Lorsque sa pleine capacité est restaurée elle est débranchée de la barre omnibus pour courant continu au moyen d un commutateur statique afin d économiser l énergie réduire la contrainte due à l ondulation du courant alternatif augmentant ainsi la durée de vie Ce mode de fonct...

Page 556: ...variations de charge en maintenant constante la tension continue En même temps il permet le chargement de la batterie L onduleur convertit la tension de courant continu en un courant alternatif en régime sinusoïdal avec fréquence et courant stabilisé et alimente également la charge par l intermédiaire de son commutateur statique SSI Image 2 Fonctionnement normal 3 3 2 Conversion écologique Lors du...

Page 557: ... référant à la valeur nominale Capacité perdue 10 Charge supplémentaire pendant 12 heures Capacité perdue entre 10 et 20 Charge supplémentaire pendant 48 heures Capacité perdue 20 Charge supplémentaire pendant 96 heures Ces valeurs se conforment aux recommandations des fabricants de la batterie principale Définir la bonne capacité de la batterie Le panneau frontal de l UPS permet de régler les par...

Page 558: ...a partiellement restauré sa capacité Le redémarrage du système à partir de la condition d interruption peut être personnalisé selon les exigences de l installation en trois modes différents Les charges de dérivation sont fournies dès que la ligne de dérivation est disponible configuration à l usine Les charges de l onduleur sont fournies par l onduleur même si la ligne de dérivation est disponible...

Page 559: ...ectrique adaptée en branchant les contacts auxiliaires des sectionneurs de dérivation manuelle et de sortie aux bornes dédiées à bord de l UPS Ceci permettra à la logique de contrôle d acquérir l état des commutateurs et de guider l opérateur lors des procédures de démarrage et de dérivation manuelle Pour plus de renseignements reportez vous à la partie Installation et démarrage Lors de la dérivat...

Page 560: ...ontrôle de l unité d alimentation sans coupure UPS s adresse au personnel autorisé seulement Nous recommandons de vérifier la formation du personnel chargé de l utilisation et de la maintenance du système 3 4 1 Isolateurs Les sectionneurs prévus sur l unité d alimentation sans coupure UPS sont utilisés pour isoler les composantes d alimentation du dispositif à partir de la ligne d alimentation en ...

Page 561: ... a aucun danger pour les personnes et les choses 3 4 3 Sélecteur normal de dérivation Il est utilisé au cours de la procédure de dérivation manuelle quand il est nécessaire d isoler l unité d alimentation sans coupure UPS pour entretien ou réparation Suivre les procédures contenues dans le manuel Le sélecteur normal de dérivation ne doit être utilisé que conformément aux procédures spécifiées dans...

Page 562: ...ge d Accueil 4 1 ICÔNES Le parcours des pages de l écran tactile est possible par le biais de sept icônes fournies à droite l icône avec les flèches haut bas contrôle la communication d affichage Description de l icône Icône Fonctions attribuées Accueil Retourne à la page d Accueil Mesures Entre dans la section Mesures Une page de la section Mesures est actuellement affichée Contrôles Entre dans l...

Page 563: ...ction Info Une page de la section Info est actuellement affichée Précédent Recule d une page Communication Contrôle la communication entre le panneau et les composants électroniques de l UPS Communication OK Contrôle la communication entre le panneau et les composants électroniques de l UPS Communication Ko en cas d erreur de communication entre l écran tactile et la logique de commande de l UPS 4...

Page 564: ...ions du panneau de commande de la page d Accueil directement 5 1 AFFICHAGE DES MESURES Appuyer sur un objet spécifique donne accès à l affichage des mesures de cette section spécifique de l UPS Image 9 Panneau de commande UPS page d Accueil Par exemple en cliquant sur l objet indiqué dans la figure ci dessus vous accédez à l écran Onduleur de mesures visible ci dessous Image 10 Page des mesures de...

Page 565: ...esures disponibles est donnée ci dessous Sous page Données affichées Exactitude ENTRÉE Tension d entrée du redresseur 1 1 V Courant d entrée du redresseur 1 A Fréquence 0 1 Hz Puissance d entrée 1 kVA SORTIE Tension 1 1 V Courant 1 A Pourcentage de charge 1 Puissance active 1 kW Puissance apparente 1 kVA Fréquence 0 1 Hz DÉRIVATION Tension 1 1 V Fréquence 0 1 Hz ONDULEUR Tension 1 1 V Fréquence 0 ...

Page 566: ... Exactitude BATTERIE Tension et courant 1 V 1 A Capacité nominale 1 Ah Autonomie résiduelle 1 min 1 TEMPÉRATURE 2 Batterie 0 1 C UPS 0 1 C 1 Les mesures de la tension sont toujours données en référence à la valeur phase à neutre 2 Les températures sont affichées seulement si la sonde correspondante est installée ...

Page 567: ...ment de l UPS ou soit le journal des historiques Image 12 Section ALARMES 5 2 1 Affichage de l état de fonctionnement Appuyez sur état UPS pour afficher l état de fonctionnement de l UPS qui comprend des alarmes actives possibles Image 13 Section ALARMES L état du système actuel est indiqué si la liste est plus longue que la capacité de la page 8 lignes elle peut être défilée en faisant glisser un...

Page 568: ...Le premier événement montré est le dernier dans l ordre chronologique un nouvel événement fait changer automatiquement de position tous les autres événements en effaçant l évènement le plus ancien Chaque ligne montre le numéro de l événement position dans la liste le code d alarme et la date et l heure un astérisque indique la réinitialisation automatique de l alarme Le nombre maximal d événements...

Page 569: ...z la page suivante Image 16 Enregistrer le journal des historiques L écran tactile reconnaît automatiquement quand un support de mémoire externe clé USB ou carte SD est inséré e et change la couleur de l icône correspondante de gris désactivé à bleu activé Le fichier texte sera sauvegardé contenant les mêmes informations disponibles sur les pages Historique accompagnées de la description de chaque...

Page 570: ...RANT BATTERIE CRETE MAX A16 BYPASS CHARGE A50 LIMITATION COURANT ONDULEUR A17 RETRANSFERT BLOQUÉ A51 TEMPERATURE BATTERIE A18 MBCB FERMÉ MBCB BUS FERMÉ A52 DEFAUT TENSION MINI A19 OCB OUVERT A53 DÉFAUT LOGICIEL A20 SURCHAGE EN SORTIE A54 DÉFAUT CAN BUS A21 IMAGE THERMIQUE A55 CABLE PARALLELE DECONNECTE A22 BYPASS SWITCH A56 TENS ALIM DESEQUILIBREES A23 ARRÊT D URGENCE A57 DEFAUT CONTACTEUR ONDULEU...

Page 571: ...ES ÉTATS est entré Les alarmes s affichent quand ils sont présents et doivent être interrompues avec l avertisseur Les alarmes restent affichées quand ils sont présents et sont automatiquement enregistrés dans le journal des événements avec la date et l heure Description des alarmes et états Pour une description plus détaillée des alarmes et des états consultez la section Pannes et alarmes du prés...

Page 572: ... de l icône Controles affichera la page d accès à la section de configuration protégée par mot de passe Image 17 Mot de passe d accès à la section Controles Image 18 Section Controles Accès protégé par mot de passe Le menu CONTROLES est protégé par un mot de passe défini par l usine afin de prévenir l accès au personnel non autorisé ...

Page 573: ...ance puis l unité d alimentation sans coupure ASI reprendra son fonctionnement Les conditions de défaillance qui imposent un réarmement manuel sont A10 BATTERIES DÉFECTUEUSES A12 ARRET PAR COURT CIRCUIT A29 MAINTENANCE À PRÉVOIR A33 UTIL A COMPOS CONTINUE A40 TENSION VDC MIN A44 DÉSATURATION ONDULEUR A50 LIMITATION COURANT ONDULEUR A52 DEFAUT TENSION MINI A55 CABLE PARALLELE DECONNECTE Redémarrage...

Page 574: ...onctionnement en Fréquence de tension indépendante VFI Voltage Frequency Independent double conversion en ligne à la Fréquence de tension dépendante VFD Voltage Frequency Dependent Dans ce mode la charge est directement fournie par le CA et l onduleur est activé prêt à prendre la relève en cas d anomalies des réseaux de distribution Le transfert se produit en un temps maximal de 10 ms La stabilité...

Page 575: ... OPERATIONS La pression de l icône Reglages affichera la page d accès à la section de configuration protégée par mot de passe Image 19 Mot de passe d accès à la section Reglages Image 20 Section Reglages Accès protégé par mot de passe Le menu CONTROLES est protégé par un mot de passe défini par l usine afin de ...

Page 576: ...Configuration de la date et de l heure La date et l heure peuvent être réglées au moyen du menu HORLOGE Image 21 Configuration manuelle de l horloge Configuration de la date et de l heure courantes correctement Le réglage exact de la date et de l heure est essentiel pour l enregistrement du journal des événements Le système permet également de configurer un serveur NTP pour la synchronisation de l...

Page 577: ...nfigurés via les pages de Configuration réseau dans la section Reglages Si le serveur ne répond pas ou que la connexion LAN est manquante le message ERREUR NTP s affichera 5 4 2 Configuration de la langue d affichage L image suivante montre les langues qui peuvent être définies Image 23 Configuration de la langue La sélection de la langue est effectuée en appuyant sur l un des drapeaux ...

Page 578: ...ATION DE BATTERIE permet de configurer ces données Chaque paramètre configurable simple est accessible via la page suivante Image 24 Configuration des paramètres de la batterie Les différentes pages de configuration des paramètres sont semblables les unes aux autres et nécessitent que l opérateur saisit et confirme la valeur la page de configuration de la capacité de la batterie est indiquée ci de...

Page 579: ...es de l interface utilisateur RS485 Les paramètres concernant la communication au moyen de l interface RS485 peuvent être configurés dans la section MODBUS RS485 Cette section permet de définir l adresse ModBus le mode de communication et la vitesse de transmission des données 5 4 6 Configuration des paramètres réseau d affichage La section CONFIG RÉSEAU permet de configurer les paramètres se rapp...

Page 580: ...ation du DHCP Image 27 Configuration des paramètres LAN 5 4 6 2 Configuration des paramètres NTP Les paramètres du service NTP configurables sont les suivants Adresse du serveur NTP primaire Adresse du serveur NTP secondarie L activation désactivation NTP s effectue dans le menu RÉGLAGES HORLOGE Image 28 Configuration des paramètres NTP ...

Page 581: ...ramètre s affichera sur la chaîne modifiable en haut de la page avec un clavier Image 29 Modification des paramètres numériques Les champs liés aux serveurs NTP peuvent être soit numériques adresse IP du serveur distant ou alphanumériques quand le serveur distant peut être atteint via une adresse Web Auquel cas le clavier qui apparaîtra dans la page est complet Image 30 Modification des paramètres...

Page 582: ...n sans coupure ASI appuyez sur l icône correspondante pour ouvrir la page principale Image 31 Section INFO Toutes les données affichées dans les diverses sections sont définies lors de l essai en usine via un logiciel d interface spécifique et ne peuvent être modifiées par quiconque sauf le personnel autorisé par le fabricant 5 5 1 Informations sur le dispositif Image 32 Informations sur le dispos...

Page 583: ... de l heure du système actuel 5 5 2 Informations parallèles La page contenant les informations sur le parallèle est seulement activée si l alimentation sans coupure ASI est parallèle aux autres ASI Image 33 Informations parallèles 5 5 2 1 Indice parallèle Le premier chiffre identifie la position de cette alimentation sans coupure ASI spécifique dans le système parallèle Le second chiffre représent...

Page 584: ...demander la présence de toutes les unités d alimentation sans coupure ASI pour alimenter la charge REDONDANT x signifie que le système est redondant et l index de redondance est indiqué par le numéro x Par exemple dans un système composé de 3 unités d alimentation sans coupure ASI REDONDANT 2 signifie que seulement une des unités d alimentation sans coupure est suffisante pour alimenter la charge ...

Page 585: ...sinon il y aura un conflit sur le bus de communication des données 5 5 3 3 État du système surveillance du bus de communication Ce champ donne une indication générale concernant la communication entre les unités de l alimentation sans coupure ASI composant le système Les numéros représentent les unités d alimentation sans coupure ASI individuelles Les lettres M et S sont pour MAÎTRE et ESCLAVE res...

Page 586: ...re de messages reçus et pourcentage de précision de réception en ce qui concerne l état du système Les messages sont échangés entre toutes les unités d alimentation sans coupure ASI donc le nombre va augmenter sur chacun d eux 5 5 4 Informations de communication RS485 La section MODBUS RS485 fournit des informations sur les paramètres du port de communication concernant l adresse ModBus attribuée ...

Page 587: ...larme sont affichés Risque de blessure dû à un choc électrique Avant d effectuer toute opération sur l ASI s assurer que toutes les précautions de sécurité soient respectées Tout travail sur l unité doit être effectué par un personnel qualifié Les composantes internes ne peuvent être accessibles qu après avoir débranché l appareil à partir de sources d alimentation Toujours utiliser les dispositif...

Page 588: ...t prêt à alimenter la charge État S4 ONDULEUR CHARGE Description L onduleur alimente la charge Condition de fonctionnem ent La charge est alimentée par le commutateur d onduleur statique État S5 OND BYPASS SYNCHRO Description L onduleur est synchronisé avec la dérivation Condition de fonctionnem ent La synchronisation entre l onduleur et la dérivation est verrouillée et le commutateur statique peu...

Page 589: ... Condition de fonctionnem ent L interrupteur statique de la batterie est fermé et la batterie se trouve dans la deuxième et dernière phase du mode de charge I U DIN 41773 avec une tension constante et un courant décroissant Status S16 TRANSFERT SUR BY PASS VR2max Description Commutation avec tension de dérivation élevée Operating condition Commutation de l onduleur au bypass avec coupure de l ondu...

Page 590: ...e phase 2 Si l alarme persiste contacter notre service d assistance technique Alarme A3 REDRESSEUR À L ÂRRET Description Le redresseur a été temporairement déconnecté et l onduleur est alimenté par la batterie Causes possibles L instabilité de la fréquence ou de la tension de la ligne à courant alternatif Panne possible sur le circuit de contrôle du redresseur Solutions 1 Vérifier les paramètres d...

Page 591: ...uses possibles Un test de la batterie a été démarré automatiquement si activé ou manuellement par l utilisateur Solutions 1 Attendre la fin du test et vérifier les éventuels défauts de batterie Alarme A7 BCB OUVERT Description Le sectionneur de la batterie est ouvert Causes possibles Sectionneur de la batterie ouvert Solutions 1 Vérifier l état du sectionneur de la batterie 2 Vérifier le fonctionn...

Page 592: ...alarme persiste contacter notre service d assistance technique Alarme A11 COURT CIRCUIT Description Le capteur de courant a détecté un court circuit à la sortie Causes possibles Problème de charge Mesure de défaillance du circuit Solutions 1 Vérifier les charges connectées à la sortie de l unité d alimentation sans coupure ASI 2 Si l alarme persiste contacter notre service d assistance technique A...

Page 593: ...Solutions 1 Vérifier la rotation de phase 2 Si l alarme persiste contacter notre service d assistance technique Alarme A15 DÉFAUT BYPASS Description La tension ou la fréquence de la ligne de dérivation est hors tolérance Causes possibles Panne ou instabilité de la ligne de dérivation Mauvaise rotation de phase Solutions 1 Vérifier les connexions au réseau 2 Vérifier la stabilité de la tension d al...

Page 594: ... dérivation manuel 2 Vérifier le fonctionnement du contact auxiliaire du sectionneur 3 Si l alarme persiste contacter notre service d assistance technique Alarme A19 OCB OUVERT Description Le sectionneur de sortie est ouvert Causes possibles Isolateur de sortie ouvert Solutions 1 Vérifier l état du sectionneur de sortie 2 Vérifier le fonctionnement du contact auxiliaire du sectionneur 3 Si l alarm...

Page 595: ...n Le système est bloqué en raison de l activation de la touche de mise hors tension d urgence Causes possibles Activation du bouton de mise hors tension d urgence local ou distant Solutions 1 Relâcher le bouton d arrêt d urgence et réinitialiser l alarme 2 Si l alarme persiste contacter notre service d assistance technique Alarme A24 SURCHAUFFE Description Température élevée du dissipateur de chal...

Page 596: ...erreur dans les paramètres mémorisés dans EEPROM Causes possibles Mauvais paramètres entrés lors de la programmation Solutions 1 Contacter notre service de support technique Alarm A28 ARRET CRITIQUE Description Une alarme a été activée ce qui provoque la fermeture d une partie de l unité d alimentation sans coupure ASI redresseur onduleur commutateur statique Possible causes Panne du système Solut...

Page 597: ...nce sur le circuit de mesure Cause possible de condensateurs à courant continu Solutions 1 Réinitialiser le système 2 Si l alarme persiste contacter notre service d assistance technique Alarme A34 APPEL SERVICE APRÈS VENTE Description Une vérification de l unité d alimentation sans coupure ASI est nécessaire Causes possibles Possible défaillance de l unité d alimentation sans coupure ASI Solutions...

Page 598: ...e fonctionnement du contact auxiliaire du sectionneur 3 Si l alarme persiste contactez notre Service d assistance technique Alarme A38 ONDULEUR CHARGE Description La charge est alimentée par l onduleur Cette alarme est active pour les systèmes d unité d alimentation sans coupure ASI en mode ÉCO où l approvisionnement préférentiel est de la ligne de dérivation Causes possibles Passage temporaire du...

Page 599: ... continu hors des limites et a éteint l onduleur le booster et a déconnecté la batterie de l ASI Solutions 1 Vérifiez qu il n y a pas de court circuit dans le bus DC 2 Vérifier le capteur actuel de la batterie 3 Vérifier les blocs de la batterie 4 Si l alarme persiste contactez notre Service d assistance technique Alarme A42 PERTE REDONDANCE ALIM Description Défaillance de l alimentation électriqu...

Page 600: ...ifier le système de conditionnement d air si présent 4 Si l alarme persiste contacter notre service d assistance technique Alarme A46 PERTE DE REDONDANCE Description Cette alarme n est active que sur les systèmes PARALLÈLES La continuité n est pas assurée dans le cas d un défaut sur l une des unités d alimentation sans coupure ASI Causes possibles La charge totale est supérieure à la valeur maxima...

Page 601: ...ue la sonde de température est installée et activée sur la batterie Causes possibles Température anormale dans la batterie du cabinet Éventuelle défaillance sur le circuit de mesure Solutions 1 Vérifier la température sur les batteries et éliminer la cause de l alarme le cas échéant 2 Si l alarme persiste contacter notre service d assistance technique Alarme A52 DEFAUT TENSION MINI Description L o...

Page 602: ...ion BT ou de moyenne tension MT Défaut du circuit de mesure Solutions 1 Vérifier la tension d entrée 2 Contacter notre service de support technique Alarme A57 DEFAUT CONTACTEUR ONDULEUR Description Le contacteur de l onduleur est défectueux Cette alarme n est active que lorsque le contacteur est installé et activé via eeprom manager Causes possibles Défaillance du contacteur auxiliaire Défaillance...

Page 603: ...e 2 Si l alarme persiste contactez notre Service d assistance technique Alarme A61 TENSION VDC MAX Description L ASI s est arrêté en raison du fonctionnement du capteur de protection comme résultat de fortes variations soudaines de tension DC au dessus des limites Causes possibles Problème de tension bus DC Solutions 1 Vérifiez qu il n y a pas de court circuit dans le bus DC 2 Vérifiez l état de l...

Page 604: ...interne Solutions 1 S assurer que la position des dispositifs de contrôle sectionneurs sélecteurs est telle que spécifiée dans les procédures voir section Installation et démarrage 2 Si l alarme persiste contacter notre service d assistance technique Alarme A64 TRANSITOIRE TENSION RESEAU Description Détection d un abaissement rapide AC sur l entrée Causes possibles Lower Abaissement brutal du rése...

Page 605: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMP06263 REV B 119 LINGUA ITALIANA ...

Page 606: ... KEOR HPE 400 kVA BSU14 KEOR HPE 500 kVA Conservazione della documentazione Questo manuale e tutta la restante documentazione tecnica di supporto al prodotto devono essere conservati e possibilmente resi accessibili al personale nelle immediate vicinanze dell UPS Informazioni aggiuntive Nel caso le informazioni riportate nel presente manuale non fossero abbastanza esaurienti si prega di contattare...

Page 607: ...riportate nei manuali Pericolo di lesioni a seguito di guasti al dispositivo In caso di guasto dell UPS si possono creare situazioni potenzialmente pericolose Non utilizzare il dispositivo se presenta danni visibili Effettuare regolarmente interventi di manutenzione al fine di rilevare possibili anomalie Possibile danneggiamento del dispositivo Prima di qualsiasi intervento sul dispositivo aver cu...

Page 608: ...e dall UPS richiamando l attenzione dell utente Figura 1 Schema a blocchi L UPS è realizzato con tecnologia ad IGBT ad elevata frequenza di commutazione per consentire una bassa distorsione della corrente re iniettata nella rete di alimentazione e un alta qualità e stabilità della tensione di uscita La componentistica utilizzata garantisce elevata affidabilità altissima efficienza e facilità di ma...

Page 609: ...ca di controllo del raddrizzatore La batteria viene sottoposta ad un ciclo di carica in accordo alle DIN41773 ogni volta che avviene una scarica parziale o totale Al ripristino della completa capacità viene disconnessa dal bus DC per mezzo di un interruttore statico a SCR per di risparmiare energia e ridurre lo stress dovuto al ripple AC tutto al fine di aumentare la vita attesa Tale modalità oper...

Page 610: ... compensa le variazione della tensione di rete così come quelle di carico mantenendo la tensione DC costante Allo stesso tempo provvede a caricare la batteria L inverter converte la tensione DC in una sinusoide AC stabilizzata in tensione e frequenza e provvede ad alimentare il carico tramite il suo static switch SSI Figura 2 Funzionamento normale 3 3 2 Green Conversion Durante il funzionamento in...

Page 611: ...pacità persa è 10 Carica mantenimento per 12 ore Capacità persa è compresa tra il 10 e il 20 Carica mantenimento per 48 ore Capacità persa è 20 Carica mantenimento per 96 ore Tali valori sono conformi alle raccomandazioni dei principali produttori di batterie Impostare il corretto valore di capacità Il pannello frontale dell UPS permette l impostazione dei parametri di batteria inclusa la capacità...

Page 612: ...vvio dell inverter avviene quando la batteria ha ripristinato parte della sua capacità La ripartenza del sistema dalla condizione di black out può essere personalizzata sulla base delle esigenze dell impianto in tre modalità differenti Bypass i carichi vengono alimentati appena la rete di bypass è disponibile configurazione di fabbrica Inverter i carichi vengono alimentati dall inverter anche se l...

Page 613: ...lazione elettrica prestare cura al cablaggio dei contatti ausiliari degli isolatori di bypass manuale uscita e batteria che vanno collegati agli appositi morsetti sull UPS In questo modo la logica di controllo acquisisce lo stato degli interruttori per guidare l operatore durante le procedure di avvio e bypass manuale Per maggiori informazioni fare riferimento alla sezione Installazione e avviamen...

Page 614: ... comando dell UPS è destinato a personale autorizzato Si consiglia di verificare l addestramento del personale addetto all utilizzo e alla manutenzione del sistema 3 4 1 Sezionatori I sezionatori previsti sull UPS servono per isolare la parte di potenza del dispositivo dalla rete AC di alimentazione dalla batteria di accumulatori e dai carichi Presenza di tensione sui terminali I sezionatori non i...

Page 615: ...ll arresto di emergenza sono state eliminate e si è certi che non ci siano pericoli per le persone o le cose 3 4 3 Selettore Normale Bypass Viene utilizzato durante la procedura di bypass manuale quando è necessario isolare l UPS per manutenzione o riparazione Seguire le procedure riportate nel manuale Il selettore Normale Bypass deve essere manovrato solamente in accordo alle procedure riportate ...

Page 616: ...ll UPS Figura 8 Pannello frontale UPS schermata Home 4 1 ICONE Il touch screen è provvisto di 7 icone sulla parte destra dello schermo che permettono la navigazione e di un icona di controllo della comunicazione Description of the icon Icon Assigned functions Home Torna alla pagina Home Misure Entra nella sezione Misure Si è all interno della sezione Misure Controlli Entra nella sezione Controlli ...

Page 617: ... Info Entra nella sezione Info Si è all interno della sezione Info Indietro Torna indietro di una pagina Comunicazione Comunicazione Ok fra il pannello e la logica di controllo dell UPS Comunicazione Ko fra il pannello e la logica di controllo dell UPS errore di comunicazione tra touch screen e UPS 4 2 BARRA DI STATO La barra di stato in basso dà un indicazione dello stato di alimentazione del car...

Page 618: ...el pannello di controllo direttamente dalla pagina Home 5 1 VISUALIZZAZIONE DELLE MISURE Premendo su un determinato oggetto si accede alla visualizzazione delle misure di quella specifica sezione dell UPS Figura 9 Pannello frontale UPS schermata Home Per esempio cliccando sull oggetto indicato in figura sopra si accede alla schermata Misure Inverter visibile di seguito Figura 10 Misure Inverter ...

Page 619: ... di tutte le misure disponibili Sotto menu Dati visualizzati Accuratezza INGRESSO Tensione ingresso raddrizzatore 1 1 V Corrente ingresso raddrizzatore 1 A Frequenza 0 1 Hz Potenza di ingresso 1 kVA USCITA Tensione 1 1 V Corrente 1 A Percentuale di carico 1 Potenza attiva 1 kW Potenza apparente 1 kVA Frequenza 0 1 Hz BYPASS Tensione 1 1 V Frequenza 0 1 Hz INVERTER Tensione 1 1 V Frequenza 0 1 Hz A...

Page 620: ...enu Dati visualizzati Accuratezza BATTERIA Tensione e corrente 1 V 1 A Capacità nominale 1 Ah Autonomia residua 1 min 1 TEMPERATURE 2 Batteria 0 1 C UPS 0 1 C 1 Le misure di tensione sono sempre riferite tra fase e neutro 2 Le temperature sono visualizzate solo se la relativa sonda è installata ...

Page 621: ...unzionamento dell UPS o dello storico eventi Figura 12 Sezione ALLARMI 5 2 1 Visualizzazione dello stato di funzionamento Premere su Stato UPS per visualizzare lo stato di funzionamento dell UPS inclusi eventuali allarmi presenti Figura 13 Sezione ALLARMI Viene visualizzato lo stato attuale del sistema che può essere scorso con uno slide sullo schermo nel caso le righe non entrino nella prima sche...

Page 622: ...armi pagina 1 Il primo evento visualizzato è l ultimo in ordine di tempo un nuovo evento fa scorrere automaticamente gli altri di una posizione ed elimina l evento più vecchio Su ogni riga sono riportati rispettivamente il dato visualizzato al momento posizione nella lista il codice dell allarme e data e ora un asterisco indica il reset automatico dell allarme Il numero massimo di eventi visualizz...

Page 623: ...ina Figura 16 Storico allarmi salvataggio file Il touch screen riconosce automaticamente l inserimento di un supporto di memoria esterno USB stick o scheda SD e cambia il colore della rispettiva icona da grigio disabilitato a bianco abilitato Viene salvato un file di testo che riporta tutte le stesse informazioni disponibili nelle schermate integrate dalla descrizione dell evento ...

Page 624: ...ACORRENTE BATTERIA A16 BYPASS CARICO A50 SATURAZIONE CORRENTE INVERTER A17 RITRASFERIMENTO BLOCCATO A51 TEMPERATURA BATTERIA A18 MBCB CHIUSO MBCB BUS CHIUSO A52 INVERTER BLOCCATO UVL A19 OCB APERTO A53 ERRORE COMPATIBILITÀ FIRMWARE A20 SOVRACCARICO A54 ERRORE COMUNIC CAN PARALLELO A21 IMMAGINE TERMICA A55 CAVO PARALLELO DISCONNESSO A22 BYPASS SWITCH A56 TERNA SBILANCIATA A23 EPO CHIUSO A57 TELERUT...

Page 625: ...zzati sempre in ordine crescente Gli allarmi vengono mostrati quando si presentano e devono essere tacitati con il buzzer Gli allarmi restano visibili finché sono presenti e vengono registrati automaticamente nello storico eventi con data e ora Descrizione degli allarmi e degli stati Per una descrizione più approfondita degli allarmi e degli stati vedere la sezione del presente manuale Guasti e al...

Page 626: ...zo dell UPS 140 OMP06263 REV B 5 3 CONTROLLI E OPERAZIONI AVANZATE La pressione sull icona Controlli visualizza la pagina di accesso alla sezione controlli protetto da password Figura 17 Password di accesso alla sezione Controlli Figura 18 Sezione Controlli ...

Page 627: ...T è necessario per ripristinare semplicemente una segnalazione di anomalia quindi l UPS continua a funzionare Le condizioni di blocco che impongono un reset manuale sono A10 ANOMALIA BATTERIA A12 STOP TIMEOUT CORTO CIRCUITO A29 MANUTENZIONE PROGRAMMATA A33 CARICO ASIMMETRICO A40 MINIMA TENSIONE DC A44 DESATURAZIONE INVERTER A50 SATURAZIONE CORRENTE INVERTER A52 INVERTER BLOCCATO UVL A55 CAVO PARAL...

Page 628: ...al funzionamento VFI Voltage Frequency Independent on line doppia conversione a quello VFD Voltage Frequency Dependent In tale modalità il carico è alimentato direttamente dalla rete AC e l inverter è acceso pronto a subentrare in caso di anomalia della rete La commutazione avviene in un tempo massimo pari a 10 ms La stabilità delle rete AC è controllata da uno specifico algoritmo che provvede a d...

Page 629: ...UPS OMP06263 REV B 143 5 4 IMPOSTAZIONI E OPERAZIONI AVANZATE La pressione sull icona Impostazioni visualizza la pagina di accesso alla sezione impostazioni protetto da password Figura 19 Password di accesso alla sezione Impostazioni Figura 20 Sezione Impostazioni ...

Page 630: ...enzialmente pericolose per il dispositivo stesso e per le persone 5 4 1 Impostazione di data e ora La data e l ora possono essere impostate dalla pagina OROLOGIO Figura 21 Impostazione manuale orologio Impostare correttamente data e ora correnti La corretta impostazione della data e dell ora è fondamentale per la registrazione dello storico eventi Il sistema permette anche l impostazione di un ser...

Page 631: ...figurati dalla sezione Configurazione rete del menu Impostazioni Nel caso non ci sia risposta dal server oppure manchi la connessione LAN apparirà il messaggio di errore ERRORE NTP 5 4 2 Impostazione lingua del display La schermata seguente mostra i linguaggi impostabili per il display Figura 23 Impostazione lingua La selezione della lingua si effettua premendo su una delle bandiere ...

Page 632: ...zione IMPOSTAZIONI BATTERIA permette l impostazione degli stessi Si accede ai singoli parametri impostabili dalla schermata seguente Figura 24 Impostazione parametri batteria Le varie schermate di impostazione dei parametri sono simili fra loro e richiedono l inserimento dei valori e la conferma per riferimento si riporta la schermata di configurazione della capacità di batteria Figura 25 Impostaz...

Page 633: ...parametri di interfaccia utente RS485 All interno del menu MODBUS RS485 possono essere impostati i parametri relativi alla comunicazione tramite supporto RS485 La sezione consente l impostazione dell indirizzo la modalità di comunicazione e la velocità di trasmissione dati della RS485 5 4 6 Impostazione parametri di rete del touch screen Tramite la sezione CONFIGURAZIONE è possibile configurare i ...

Page 634: ...ostazione parametri LAN 5 4 6 2 Impostazione parametri NTP Per quanto riguarda il servizio NTP i parametri configurabili sono Indirizzo server NTP primario Indirizzo server NTP secondario L abilitazione disabilitazione NTP si esegue nel menu IMPOSTAZIONI OROLOGIO Figura 28 Impostazione parametri NTP ...

Page 635: ...rirà su una stringa modificabile in alto nella schermata unitamente ad un tastierino numerico Figura 29 Modifica parametri numerici I campi relativi ai server NTP possono essere numerici indirizzo IP del server remoto oppure formati da testo quando il server remoto è raggiungibile su un indirizzo web In tal caso il tastierino che compare nella schermata è di tipo completo Figura 30 Modifica parame...

Page 636: ... premere sull icona relativa per accedere alla schermata principale Figura 31 Menu INFO Tutti i dati mostrati all interno delle varie sezioni sono impostati in fabbrica tramite apposito software di interfaccia e non possono essere modificati tranne che da parte di personale autorizzato dal costruttore 5 5 1 Informazioni dispositivo Figura 32 Informazioni dispositivo ...

Page 637: ...a macchina OROLOGIO Impostazione attuale della data e ora di sistema 5 5 2 Informazioni parallelo La pagina relativa alle informazioni sul parallelo è abilitata solamente se l UPS è in parallelo con altri sistemi UPS Figura 33 Informazioni parallelo 5 5 2 1 Indice di parallelo Il primo numero identifica la posizione di quel particolare UPS nel sistema di parallelo il secondo numero rappresenta il ...

Page 638: ... il carico RIDONDANTE X significa che il sistema è ridondante e l indice di ridondanza è indicato dal numero X Per esempio in un sistema composto da 3 UPS RIDONDANTE 2 significa che uno solo degli UPS è sufficiente per alimentare il carico 5 5 2 5 Statistiche messaggi La sezione statistiche relative ai messaggi scambiati sui bus di comunicazione si compone di tre diverse parti STAT CAN SSW Numero ...

Page 639: ...a della comunicazione fra gli UPS che compongono il sistema I numeri rappresentano i singoli UPS Le lettere M e S stanno rispettivamente per MASTER e SLAVE Le parentesi intorno ad una lettera indicano che stiamo lavorando su quello specifico UPS Un eventuale punto interrogativo accanto ad un numero indica che quell UPS non sta comunicando sul bus dati 5 5 3 4 Tipo di parallelo La stringa può assum...

Page 640: ...i il numero incrementa su tutti 5 5 4 Informazioni sulla comunicazione RS485 Il menu MODBUS RS485 fornisce informazioni sull impostazione della porta di comunicazione relativamente all indirizzo assegnato alla modalità di comunicazione e alla velocità di trasmissione dati 5 5 5 Versioni firmware Figura 36 Versioni firmware La seconda pagina delle informazioni relative alle versioni firmware instal...

Page 641: ... una breve descrizione dello stesso Pericolo di lesioni a seguito shock elettrico Prima di effettuare qualsiasi intervento sull UPS aver cura di rispettare tutte le indicazioni relative alla sicurezza tutti i lavori sull apparato devono essere svolti da personale qualificato accedere ai componenti interni solo dopo aver disconnesso il dispositivo dalle sorgenti di alimentazione utilizzare sempre i...

Page 642: ...per erogare alimentare il carico Stato S4 INVERTER CARICO Descrizione L inverter alimenta il carico Condizione operativa Il carico è alimentato attraverso l interruttore statico di inverter Stato S5 INVERTER BYPASS SINCRONIZZATI Descrizione L inverter è sincronizzato con il bypass Condizione operativa Il sincronismo fra inverter e bypass è agganciato e l interruttore statico può effettuare commuta...

Page 643: ...vata Condizione operativa L interruttore statico di batteria è chiuso e la batteria è nella seconda e finale fase di carica I U DIN 41773 con tensione costante e corrente decrescente Stato S16 COMMUTAZIONE CON BYP ALTO Descrizione Commutazione con tensione di bypass alta Condizione operativa Commutazione da inverter a bypass con spengimento inverter causato dalla tensione di bypass maggiore o ugua...

Page 644: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 158 OMP06263 REV B ...

Page 645: ...erificare il senso ciclico delle fasi 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A3 RADDRIZZATORE SPENTO Descrizione Il raddrizzatore è stato momentaneamente arrestato e l inverter viene alimentato dalla batteria Possibili cause Instabilità della tensione o della frequenza della rete AC Possibile guasto del circuito di controllo del raddrizzatore Soluzioni 1 Verif...

Page 646: ...atteria Possibili cause E stato avviato un test di batteria automaticamente se impostato oppure manualmente dall operatore Soluzioni 1 Attendere la fine del test e verificare eventuali anomalie della batteria Allarme A7 BCB APERTO Descrizione Il sezionatore di batteria è aperto Possibili cause Sezionatore di batteria aperto Soluzioni 1 Verificare lo stato del sezionatore di batteria 2 Verificare l...

Page 647: ...ia 2 Resettare il sistema 3 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A11 CORTO CIRCUITO Descrizione Il sensore di corrente ha rilevato un corto circuito in uscita Possibili cause Problema sui carichi Guasto del circuito di misura Soluzioni 1 Verificare i carichi connessi all uscita dell UPS 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allar...

Page 648: ...ficare il senso ciclico delle fasi 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A15 BYPASS NON DISPONIBILE Descrizione La tensione o la frequenza della rete di bypass sono fuori dal range di tolleranza Possibili cause Instabilità o mancanza della rete di bypass Errato senso ciclico delle fasi Soluzioni 1 Controllare i collegamenti di connessione alla rete 2 Verifica...

Page 649: ...tore di bypass manuale 2 Verificare la funzionalità del contatto ausiliario del sezionatore 3 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A19 OCB APERTO Descrizione Il sezionatore di uscita è aperto Possibili cause Sezionatore di uscita aperto Soluzioni 1 Verificare lo stato del sezionatore di uscita 2 Verificare la funzionalità del contatto ausiliario del sezionator...

Page 650: ...sistenza Tecnica Allarme A23 EPO CHIUSO Descrizione Il sistema è bloccato in seguito all azionamento del pulsante di arresto di emergenza Possibili cause Azionamento del pulsante di arresto di emergenza locale o remoto Soluzioni 1 Sbloccare l arresto di emergenza e resettare l allarme 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A24 ALTA TEMPERATURA Descrizione Alta...

Page 651: ...lore ha rilevato un errore nei parametri memorizzati in EEPROM Possibili cause Inserimento di parametri errati durante la programmazione Soluzioni 1 Contattare il servizio di Assistenza Tecnica Allarme A28 STOP CRITICO Descrizione E presente un allarme che causa l arresto di una parte dell UPS raddrizzatore inverter interruttore statico Possibili cause Guasto del sistema Soluzioni 1 Verificare qua...

Page 652: ...oluzioni 1 Sbloccare l arresto di emergenza e resettare l allarme 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A33 CARICO ASIMMETRICO Descrizione Le tensioni misurate sui condensatori DC positiva e negativa verso punto centrale sono diverse Possibili cause Possibile guasto del circuito di misura Possibile anomalia dei condensatori DC Soluzioni 1 Resettare il sistema...

Page 653: ...ia batteria Soluzioni 1 Verificare la batteria 2 Resettare il sistema 3 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A37 OCBD APERTO Descrizione Il sezionatore di distribuzione di uscita è aperto Solo su sistemi con Bypass Centralizzato Possibili cause Sezionatore di distribuzione di uscita aperto Soluzioni 1 Verificare lo stato del sezionatore di distribuzione di usc...

Page 654: ... siano cortocircuiti nel bus DC 2 Verificare lo stato dell UPS 3 Verificare i blocchi della batteria 4 Verificare il valore della tensione DC 5 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A41 MASSIMA CORRENTE DC Descrizione La corrente continua supera i limiti Possibili cause L UPS ha rilevato la corrente continua fuori dai limiti e ha spento l inverter il booster e ...

Page 655: ...il servizio di Assistenza Tecnica Allarme A45 ALTA TEMPERATURA SSW Descrizione Alta temperatura del dissipatore di calore del ponte interruttore statico Possibili cause Guasto dei ventilatori di raffreddamento del dissipatore Temperatura dell ambiente o dell aria di raffreddamento troppo elevata Soluzioni 1 Controllare il funzionamento dei ventilatori 2 Pulire le griglie di aerazione e gli eventua...

Page 656: ...li cause Possibile problema al carico Possibile guasto del circuito di misura Soluzioni 1 Controllare i carichi collegati all uscita dell UPS 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A51 TEMPERATURA BATTERIA Descrizione La temperatura della batteria è fuori dai limiti di tolleranza Allarme attivo solo se è installata e abilitata la sonda di temperatura sulla bat...

Page 657: ...municazione del cavo parallelo Possibili cause Cavo di parallelo disconnesso o danneggiato Soluzioni 1 Controllare la connessione del cavo 2 Contattare il servizio di Assistenza Tecnica Allarme A56 TERNA SBILANCIATA Descrizione Terna d ingresso raddrizzatore sbilanciata Possibili cause La terna delle tensioni d ingresso raddrizzatore sono sbilanciate Problema sulla scheda di misura Soluzioni 1 Con...

Page 658: ...ervizio di Assistenza Tecnica Allarme A60 SENSORE DI USCITA Descrizione Il sensore della tensione di uscita ha rilevato una variazione della tensione superiore o inferiore ai limiti Possibili cause Problema di feedback sulla tensione di uscita Soluzioni 1 Ripristinare il sistema 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A61 MASSIMA TENSIONE DC Descrizione L UPS s...

Page 659: ...rretto svolgimento della sequenza Possibili cause Organi di manovra in posizione errata o manovrati in maniera non corretta Possibile guasto interno Soluzioni 1 Verificare che la posizione degli organi di manovra sezionatori selettori sia come specificato nelle procedure vedi sezione Installazione ed avviamento 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A64 UFG MO...

Page 660: ...UPS OPERATING MANUAL MANUEL DE FONCTIONNEMENT DE L UPS MANUALE OPERATIVO UPS KEOR HPE 400 500 kVA ...

Page 661: ...plémentaires peuvent être nécessaires pour éviter les perturbations Catégorie ASI C3 conformément á la norme IEC 62040 2 Questo prodotto è destinato ad applicazioni commerciali e industriali del secondo ambiente durante l installazione può essere necessario introdurre alcune limitazioni ed adottare misure aggiuntive per prevenire i disturbi Classe UPS C3 in accordo alla norma CEI 62040 2 ELECTROMA...

Page 662: ......

Page 663: ...PS OPERATING MANUAL MANUALE OPERATIVO UPS Index of sections Indice delle sezioni Code Codice 1 WARNINGS AND GENERAL INFORMATION AVERTISSEMENTS ET INFORMATIONS GÉNÉRALES AVVERTENZE E INFORMAZIONI GENERALI OMB81276 2 INSTALLATION AND START UP INSTALLATION ET DÉMARRAGE DE L ASI INSTALLAZIONE ED AVVIAMENTO OMT87187 3 UPS USER MANUAL MANUEL DE L UTILISATEUR DE L ASI UTILIZZO DELL UPS OMP06263 ...

Page 664: ...ce Code OMB81276 WARNINGS AND GENERAL INFORMATION AVERTISSEMENTS ET INFORMATIONS GÉNÉRALES AVVERTENZE E INFORMAZIONI GENERALI Index Indice ENGLISH LANGUAGE 4 1 CONVENTIONS USED 5 2 DOCUMENTATION NOTES 6 3 FACTORY WARRANTY 7 4 LIMITATION OF LIABILITY 9 LANGUE FRANÇAIS 10 1 CONVENTIONS UTILISEES 11 2 REMARQUES RELATIVES A LA DOCUMENTATION 12 3 GARANTIE USINE 13 4 LIMITATION DE RESPONSABILITÉ 15 LING...

Page 665: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali 2 OMB81276 REV B ...

Page 666: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali OMB81276 REV B 3 ...

Page 667: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali 4 OMB81276 REV B ENGLISH LANGUAGE ...

Page 668: ...n so as to minimize the risks to persons and property HAZARD HAZARD statements contain characteristics and basic instructions for the safety of persons Non compliance with such indications may cause serious injury or death WARNING WARNING statements contain characteristics and basic instructions for the safety of persons Non compliance with such indications may cause injury CAUTION CAUTION stateme...

Page 669: ...is manual and any other supporting technical documentation relating to the product must be stored and made accessible to personnel in the immediate vicinity of the UPS Further information In the event that the information provided in this manual is not sufficiently exhaustive please contact the manufacturer of the device whose details are available in the Contacts section ...

Page 670: ... and will be charged to the end customer c In case of service performed following a call made by mistake or in case our technicians incur extra time and or costs due to the site inaccessibility or due to work interruptions required by the customer such costs will be invoiced in accordance with ANIE rates CLASS III COLUMN B Modes required a In the event of a fault covered by the warranty the custom...

Page 671: ...nal factors such as dirt fire flooding failed operation of the air conditioning system etc Non compliance with applicable safety standards Force majeure e g lightning surges natural disasters fire acts of war riots etc Fall or displacement due to incorrect installation Ordinary wear caused by proper and continuous use of the device b Protective devices inside the units fuses and dischargers are al...

Page 672: ... use is considered improper and therefore hazardous The manufacturer cannot be held responsible for possible damage arising from improper erroneous or unreasonable usage Legrand assumes responsibility for the equipment in its original configuration Any intervention that alters the structure or the operating cycle of the equipment must be carried out and authorized directly by Legrand Legrand will ...

Page 673: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali 10 OMB81276 REV B LANGUE FRANÇAIS ...

Page 674: ... Les indications DANGER contiennent des caractéristiques et des instructions de base destinées à assurer la sécurité des personnes Le non respect de ces indications peut entraîner des blessures graves voire la mort AVERTISSEMENT Les indications AVERTISSEMENT contiennent des caractéristiques et des instructions de base destinées à assurer la sécurité des personnes Le non respect de ces indications ...

Page 675: ...mentation Ce manuel ainsi que les autres documentations techniques relatives à ce produit doivent être stockés et mis à disposition du personnel à proximité immédiate de l UPS Autres informations Si les informations fournies dans le présent manuel ne sont pas suffisamment complètes veuillez contacter le fabricant de l appareil dont les coordonnées sont indiquées dans la section Contacts ...

Page 676: ...ande effectuée par erreur ou si nos techniciens interviennent plus longtemps que prévu et ou encourent des frais supplémentaires en raison de l inaccessibilité du site ou d interruptions de travail demandées par le client les coûts correspondants seront facturés conformément aux conditions d intervention en vigueur dans le pays d installation Documents requis a Si le client constate un défaut couv...

Page 677: ... la climatisation etc Du non respect des normes de sécurité en vigueur D un événement de force majeure par ex orage surtensions catastrophe naturelle incendie guerre émeute etc D une chute ou d un déplacement dû à une installation incorrecte De l usure ordinaire résultant de l utilisation correcte et continue de l appareil b Les dispositifs de protection inclus dans les unités fusibles et décharge...

Page 678: ...tilisation sera considérée comme inappropriée et dangereuse Le fabricant ne saurait être tenu responsable des éventuels dommages résultant d une utilisation inappropriée incorrecte ou déraisonnable Legrand est responsable de l équipement dans sa configuration d origine Toute intervention modifiant la structure ou le cycle de fonctionnement de l équipement devra être réalisée et autorisée directeme...

Page 679: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali 16 OMB81276 REV B LINGUA ITALIANA ...

Page 680: ...imizzare i rischi per persone e cose PERICOLO Le indicazioni di PERICOLO riportano caratteristiche e istruzioni fondamentali per la sicurezza delle persone L inosservanza di tali indicazioni può causare lesioni gravi o morte AVVERTIMENTO Le indicazioni di AVVERTIMENTO riportano caratteristiche e istruzioni fondamentali per la sicurezza delle persone L inosservanza di tali indicazioni può causare l...

Page 681: ...nuale e tutta la restante documentazione tecnica di supporto al prodotto devono essere conservati e possibilmente resi accessibili al personale nelle immediate vicinanze dell UPS Informazioni aggiuntive Nel caso le informazioni riportate nel presente manuale non fossero abbastanza esaurienti si prega di contattare il costruttore del dispositivo i cui dettagli sono disponibili alla sezione Contatti...

Page 682: ...a e saranno riaddebitati al cliente finale f In caso di intervento in seguito ad una chiamata fatta per errore o nell eventualità in cui i nostri tecnici dovessero incorrere in tempo e o spese aggiuntive a causa di inaccessibilità del sito o sospensioni del lavoro richieste da parte del cliente tali oneri verranno fatturati in accordo alle tariffe ANIE CLASSE III COLONNA B Modalità richieste a In ...

Page 683: ...menti mancato funzionamento dell impianto di condizionamento etc mancato rispetto delle norme di sicurezza pertinenti forza maggiore per es fulmini sovratensioni calamità naturali incendi atti di guerra sommosse etc cadute o spostamenti dovuti ad installazione non corretta normale usura causata da un uso proprio e continuativo dell apparecchio b Sono inoltre esclusi dalla garanzia i dispositivi di...

Page 684: ...epita Ogni altro uso è da considerarsi improprio e quindi pericoloso Il Costruttore non può essere considerato responsabile per eventuali danni causati da usi impropri erronei ed irragionevoli Legrand si ritiene responsabile della macchina nella sua configurazione originale Qualsiasi intervento che alteri la struttura o il ciclo di funzionamento della macchina deve essere eseguito ed autorizzato d...

Page 685: ... ET DÉMARRAGE DE L ASI KEOR HPE 400 500 KVA INSTALLAZIONE E AVVIAMENTO UPS KEOR HPE 400 500 KVA Installation and start up of KEOR HPE UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA Rev Descrizione Description Data Date Emesso Issued Approvato Approved Lingua Language Pagina Page di Pag of Pag A First Issue 04 02 2020 R So...

Page 686: ...ection 16 2 3 6 Operation 17 2 3 7 Maintenance 18 2 3 8 Storage 19 2 4 ENVIRONMENTAL PROTECTION 19 2 4 1 ISO 14001 certification 19 2 4 2 Recycling of packing materials 19 2 4 3 Device disposal 19 3 INSTALLATION 20 3 1 RECEIPT OF THE UPS 20 3 1 1 Storage 20 3 2 HANDLING OF THE UPS 21 3 3 POSITIONING AND INSTALLATION 22 3 3 1 Base plan static load and weights 23 3 3 2 Overall dimensions clearances ...

Page 687: ...CHECKS 41 5 2 START UP PROCEDURE 42 5 3 SHUT DOWN PROCEDURE 46 5 4 SWITCHING PROCEDURE TO MANUAL BYPASS 46 5 5 RESTART FROM MANUAL BYPASS 47 LANGUE FRANÇAIS 51 1 PORTEE 53 1 RÈGLES DE SECURITE ET AVERTISSEMENTS 54 2 1 UTILISATION DE L ASI 54 2 2 VALEURS NOMINALES DE L ASI 55 2 3 AVERTISSEMENTS SPÉCIFIQUES RELATIFS À LA SÉCURITÉ 56 2 3 1 Avertissements généraux 56 2 3 2 Personnel 56 2 3 3 Transport...

Page 688: ...EED 74 4 3 BORNIERS 77 4 4 BATTERIES 78 4 5 RACCORDEMENT DES CABLES AUXILIAIRES 79 4 5 1 By pass manuel externe 79 4 5 2 Commande externe NORMAL BYPASS 79 4 5 3 Interrupteur de sortie ASI 79 4 5 4 Bouton d arrêt d urgence à distance EPO 80 4 5 5 Contact auxiliaire de batterie 80 4 5 6 Contact auxiliaire du Groupe electrogène 80 4 6 INTERFACES DE SERIE ET CONNEXIONS INTERNES 80 4 7 CONNEXION DE LA ...

Page 689: ... 104 3 2 MOVIMENTAZIONE DELL UPS 105 3 3 POSIZIONAMENTO ED INSTALLAZIONE 106 3 3 1 Pianta di base carico statico e pesi 107 3 3 2 Dimensioni di ingombro distanze minime dalle pareti e ventilazione 108 3 3 3 Condizioni ambientali di installazione 110 3 4 POSIZIONAMENTO E ALLACCIAMENTO BATTERIE 112 4 ALLACCIAMENTO ELETTRICO 113 4 1 COLLEGAMENTO CONDUTTORI DI POTENZA 114 4 2 PROTEZIONE CONTRO IL RITO...

Page 690: ...stallazione e avviamento KEOR HPE UPS 400 500 kVA 6 OMT87187 REV A 4 7 COLLEGAMENTO SCHEDA RELÈ OPZIONALE 124 5 AVVIAMENTO E ARRESTO 125 5 1 VERIFICHE PRELIMINARI 125 5 2 PROCEDURA DI AVVIAMENTO 126 5 3 PROCEDURA DI ARRESTO 130 5 4 PROCEDURA DI TRASFERIMENTO SU BYPASS MANUALE 130 5 5 RIAVVIO DA BYPASS MANUALE 131 ...

Page 691: ... start up 43 Picture 13 Inverter start up 44 Picture 14 Bypass start up 44 Picture 15 Battery start up 45 Picture 16 Connecting the UPS to the load 45 Picture 17 Start up end 46 Picture 18 Start up from manual bypass 47 Picture 19 Bypass start up 48 Picture 20 Connecting the battery 48 Picture 21 Closing the UPS output switch 48 Picture 22 Opening the manual bypass switch 49 Picture 23 Inverter st...

Page 692: ...lle 91 Illustration 23 Démarrage de l onduleur 91 Illustration 24 Transférer la charge 92 Illustration 25 Redémarrer à partir du bypass manuel terminé 92 Figura 1 Targhetta caratteristiche KEOR HPE 400 500 kVA 97 Figura 2 Movimentazione UPS KEOR HPE 400 500 kVA 105 Figura 3 Pianta di base 107 Figura 4 Dimensioni di ingombro 108 Figura 5 Distanze di rispetto 108 Figura 6 Schema unifilare KEOR HPE 4...

Page 693: ...ne e avviamento KEOR HPE UPS 400 500 kVA OMT87187 REV A 9 Figura 20 Connessione della batteria 132 Figura 21 Chiusura del sezionatore uscita UPS 132 Figura 22 Apertura del sezionatore di bypass manuale 133 Figura 23 Avvio inverter 133 Figura 24 Trasferimento del carico 134 Figura 25 Avvio da bypass manuale completato 134 ...

Page 694: ...Installation and start up of KEOR HPE UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA 10 OMT87187 REV A ENGLISH LANGUAGE ...

Page 695: ... systems listed below BST87 KEOR HPE 400 kVA BSU14 KEOR HPE 500 kVA Storing documentation This manual and any other supporting technical documentation relating to the product must be stored and made accessible to personnel in the immediate vicinity of the UPS Further information In the event that the information provided in this manual is not sufficiently exhaustive please contact the manufacturer...

Page 696: ...time to read the following manual The purpose of this manual is to give a short description of the parts composing the UPS and to guide the installer or the user through the installation of the unit in its using environment The installer or the user must read and correctly perform the instructions included in the present manual with particular reference to the requirements regarding safety in comp...

Page 697: ... KEOR HPE UPS 400 500 kVA is provided with an identification plate containing the operation ratings The plate is fixed in the inside of the UPS door Picture 1 Rating plate of KEOR HPE 400 500 kVA Check the technical characteristics Before carrying out any installation or start up operation on the UPS make sure its technical characteristics are compatible with the AC supply line and with the output...

Page 698: ...rt regarding safety Such training and qualification shall be considered as such only when certified by the manufacturer 2 3 3 Transport and handling Avoid bending or deforming the components and altering the insulation distances while transporting and handling the product Undistributed weight The weight of the UPS is not uniformly distributed Pay attention when lifting Please inspect the device be...

Page 699: ...er expose the device to direct sunlight or place it near a source of heat Special environmental conditions The UPS is designed for normal climatic and environmental operating conditions as defined in the technical specification altitude ambient operating temperature relative humidity and environmental transport and storage conditions It is necessary to implement specific protective measures in cas...

Page 700: ...tification plate correspond to the AC power system and to the actual electrical consumption of all of the equipment connected Check the conformity to the Standards The UPS must be installed in compliance with the standards in force in the country of installation IT system The UPS is also designed to be connected to an IT power distribution system All the electrical connections must be carried out ...

Page 701: ... installations to which the UPS systems belong must comply with all the current safety standards technical equipment and accident prevention regulations The device can be started operated and disconnected only by authorized personnel The settings can only be changed using the original interface software Injury hazard due to electric shock During operation the UPS converts power characterized by hi...

Page 702: ...fter shutdown and disconnection from the supply sources due to the internal capacitors which discharge slowly Thus we recommend to wait at least 5 minutes before opening the device doors Injury hazard due to electric shock Any operation must be carried out only when voltage is absent and in compliance with safety directives Make sure the battery circuit breaker that may be placed near the battery ...

Page 703: ...temperature variations bad ventilation conductive or radiant heat from other sources fungus insects vermin 2 4 ENVIRONMENTAL PROTECTION 2 4 1 ISO 14001 certification Legrand is particularly sensitive to the environmental impact of its products That is why the UPS has been manufactured with cutting edge eco design criteria ISO 14001 certification Special care was taken in using fully recyclable mat...

Page 704: ... need to be returned to the manufacturer please use the original package Danger to persons due to transport damages Mechanical damage to the electrical components constitutes a serious danger to persons and property In case of doubt regarding the non integrity of the package or of the product contained therein contact the manufacturer before carrying out the installation and or the start up 3 1 1 ...

Page 705: ...ys be handled in upright position During loading and unloading operations always respect the indications regarding the device barycentre marked on the package Before positioning the UPS in order to avoid risks of turnover it s recommended to move the system on the wood pallet on which the UPS is fixed Before the positioning in the final location remove the UPS from the pallet To handle the UPS rem...

Page 706: ...vironmental conditions in the place of installation in compliance with the current legislation please refer to the Overall dimensions minimum distances from the walls and ventilation section Special environmental conditions It is necessary to implement specific protective measures in case of unusual environmental conditions harmful smoke dust abrasive dust humidity vapour salt air bad weather or d...

Page 707: ...3 3 3 1 Base plan static load and weights 1296 190 550 550 180 645 75 855 Ø13 x4 GLAND PLATE Picture 3 Base plan The supporting base of the UPS must be designed to carry the UPS weight and to ensure its steady and safe support Its carrying capacity must be adequate to the static load indicated in the table below Power kVA 400 500 Weight kg 1080 1250 Static load kg m2 1390 1610 ...

Page 708: ...0 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA 24 OMT87187 REV A 3 3 2 Overall dimensions clearances and ventilation Picture 4 Overall dimensions D A B c Picture 5 Clearances ...

Page 709: ...bility and to allow a correct air flow as much as possible With regard to the minimum distances from the walls for all of the UPS sizes the same installation conditions apply as indicated in the table below A mm B mm C mm D mm Recommended clearances 50 1200 50 600 Minimum clearances 0 1200 0 400 The table below shows the air volume required for an optimal ventilation and cooling of the UPS Power k...

Page 710: ... snow hail etc NO Water with an origin other than rain NO Ice formation NO Classification of biological conditions EN 60721 3 3 Environmental parameter Class 3B1 3B2 3B3 a Flora NO Presence of mildew fungus etc Presence of mildew fungus etc b Fauna NO Presence of rodents and other animals that are harmful to products excluding termites Presence of rodents and other animals that are harmful to prod...

Page 711: ... strictly monitored and regulated clean spaces category X Places where atmosphere is permanently monitored X Places located in rural and urban regions where industrial activities are few and where traffic is moderate X Places located in urban regions with industrial activities and or considerable traffic X Places in proximity to industrial sources with chemical emissions X Places located in indust...

Page 712: ...installation instructions For battery installation please respect EN62040 1 strictly and follow the installation manual of the UPS To obtain the battery life indicated by the battery manufacturer the operating temperature must remain between 0 and 25 C However although the battery can operate up to 40 C there will be a significant reduction of the battery life To avoid the formation of any kind of...

Page 713: ...nections in compliance with the local standards Cables must be selected bearing in mind technical financial and safety aspects The selection and the sizing of cables from a technical viewpoint depend on the voltage on the current absorbed by the UPS on the bypass line and on the batteries on the ambient temperature and on the voltage drop Finally the kind of cable laying must be taken into particu...

Page 714: ...ting the UPS to the mains 4 1 CONNECTION OF THE POWER CABLES For the electric connection of the KEOR HPE UPS 400 500 kVA connect the following cables DC supply from the battery if the battery is external AC supply from the rectifier and bypass supply mains AC output to the loads Injury hazard due to electric shock Very high voltages are present at the ends of the cables coming from the battery Iso...

Page 715: ...the table above are indicative only The cables have been designed according to the standard CEI UNEL35024 1 using the following data 70 C rated PVC copper cables ambient temperature equal to 40 C maximum length of the cables equal to 30 m voltage drop 0 5 cables laid in cavities of structures or solid bottom cable trays The given cross sections do not take into account the overload currents allowe...

Page 716: ...nt protection using a MCCB equipped with a shunt trip coil and connected to UPS applying the wiring diagram principle described in Figure 6 6A In case of backfeed failure detected by the UPS the UPS will send a signal to trip the MCCB to isolate the UPS in order to protect the upstream distribution circuits The installer shall apply the following warning label on all primary power isolator that su...

Page 717: ...KEOR HPE UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA OMT87187 REV A 33 Picture 6 Single Line Diagram KEOR HPE 400kVA with connection to external device ...

Page 718: ...EOR HPE UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA 34 OMT87187 REV A Picture 6A Single Line Diagram KEOR HPE 500kVA with connection to external device ...

Page 719: ...ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA OMT87187 REV A 35 4 3 TERMINAL BOARDS The KEOR HPE UPS 400 500 kVA are provided with terminal boards for the connection of power cables and of auxiliary connections Picture 7 Terminal board KEOR HPE 400 500 kVA ...

Page 720: ...shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply circuit Batteries installation For battery installation please respect the prescriptions of the EN62040 1 standard paragraph 7 6 To obtain the battery life indicated by the battery manufacturer the operati...

Page 721: ... auxiliary contacts of the external switches MBCB BCB and OCB if provided must be mandatorily connected to the UPS Picture 8 Auxiliary terminals of KEOR HPE 400 500 kVA 4 5 1 External manual bypass Auxiliary contact of the external Manual Bypass Switch if provided on terminals X10 1 2 A normally open contact is required when the contact is closed see Manual Bypass procedure the microprocessor will...

Page 722: ...xiliary contact Battery auxiliary contact on terminals X10 9 10 This auxiliary contact is necessary to indicate the position of the isolator open closed 4 5 6 Diesel Generator auxiliary contact Auxiliary contact from the Diesel Generator on terminals X10 11 12 A normally open contact must be used the contact must close when the diesel generator is operating The microprocessor will acquire the stat...

Page 723: ... used for the remote signalisations of status and alarms PARALLEL OPTIONAL it is used for communication between paralleled UPS units MODBUS OPTIONAL it is used for the transmission of data to the outside via MODBUS RTU protocol RS485 THERMAL PROBE it is used to acquire the temperature of the battery cabinet room in order to adjust the charging voltage automatically SNMP OPTIONAL it is used for the...

Page 724: ...tatus M1 Led Pins Status in normal operation Name Status in normal operation RL1 Alarm A30 COMMON ALARM Not energized if alarm is present 2 3 Closed DL1 On 1 2 Open RL2 Alarm A1 MAINS FAULT Not energized if alarm is present 5 6 Closed DL2 On 4 5 Open RL3 Alarm A9 BATTERY AUT END Not energized if alarm is present 8 9 Closed DL3 On 7 8 Open RL4 Alarm A13 INV OUT OF TOL Not energized if alarm is pres...

Page 725: ...acts section External isolators All the procedures that follow make reference to the external isolator BCB and are only valid if such device is installed externally and its auxiliary contacts properly wired to the UPS terminals 5 1 PRELIMINARY CHECKS Before starting up the unit make sure that all installation and electric connection works have been performed professionally all power and control ca...

Page 726: ...ry contacts Carry out a proper electrical installation by wiring the auxiliary contacts of the external manual bypass output and battery isolators to the dedicated terminals on board the UPS This will allow the control logic to acquire the status of the switches and guide the operator during the start up and manual bypass procedures The system start up is completely guided the indications availabl...

Page 727: ...kVA OMT87187 REV A 43 1 Close the rectifier input switch RCB After some seconds the touch screen will start and will show the UPS mimic diagram Picture 11 UPS start up page 2 After the software loading phase the control logic will acquire the system status and the operation of the RCB switch and will show the operating sequences Picture 12 Rectifier start up ...

Page 728: ...HPE UPS 400 500 kVA 44 OMT87187 REV A Picture 13 Inverter start up 3 As the inverter is correctly started up close the bypass switch SBCB when indicated by the display The logic will check the correctness of the bypass phase sequence and RMS voltage value Picture 14 Bypass start up 4 Close the battery switch BCB when indicated by the display ...

Page 729: ...e switch BCB located in the external battery cabinet can only be closed if the DC voltage is in tolerance Serious damages both to the battery and the equipment may occur if the breaker is closed before the front panel requires it Close the UPS output switch OCB to connect the UPS to the load bus After this operation the start up is completed and the display will show the final mimic diagram Pictur...

Page 730: ...to Manual Bypass with no interruption of supply to the loads In this configuration the system can be restarted via the return procedure from load on manual bypass without the need to de energize the loads Manual bypass To perform the switching procedure correctly make sure no alarms are present on the system During Manual Bypass the load is supplied directly by the input mains therefore continuous...

Page 731: ... from manual by pass make sure the Bypass_Sw selector is in BYPASS position and the MBCB isolator is closed 1 Close the rectifier input switch RCB After some seconds the touch screen will start and will show the UPS mimic diagram Picture 18 Start up from manual bypass 2 After the software loading phase the control logic will acquire the system status and the operation of the RCB switch and will sh...

Page 732: ...PS 400 500 kVA 48 OMT87187 REV A Picture 19 Bypass start up 3 Close the battery switch BCB when indicated by the display Picture 20 Connecting the battery 4 Close the output switch OCB when required and immediately after the display will require to open the manual bypass switch MBCB The inverter will start Picture 21 Closing the UPS output switch ...

Page 733: ...0 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA OMT87187 REV A 49 Picture 22 Opening the manual bypass switch Picture 23 Inverter start up 5 As soon as the inverter is started it will be possible to transfer the load Move the bypass switch as required by the display to complete the UPS start up ...

Page 734: ...EOR HPE UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA 50 OMT87187 REV A Picture 24 Transferring the load Picture 25 Re start from manual bypass completed ...

Page 735: ...Installation and start up of KEOR HPE UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA OMT87187 REV A 51 LANGUE FRANÇAIS ...

Page 736: ...Installation and start up of KEOR HPE UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA 52 OMT87187 REV A ...

Page 737: ...systèmes ASI telle qu indiquée ci dessous BST87 KEOR HPE 400 kVA BSU14 KEOR HPE 500 kVA Ce manuel ainsi que les autres documentations techniques relatives à ce produit doivent être stockés et mis à disposition du personnel à proximité immédiate de l ASI Si les informations fournies dans le présent manuel ne sont pas suffisamment complètes veuillez contacter le fabricant de l appareil dont les coor...

Page 738: ...vous suggérons de lire attentivement le présentmanuel L objectif de ce manuel est de vous fournir une brève description des éléments composant l ASI et de vous guider dans l installation de l unité dans son environnement d utilisation L installateur ou l utilisateur devra lire et respecter les instructions fournies dans le présent manuel en particulier les exigences relatives à la sécurité conform...

Page 739: ...kVA est fourni avec une plaque signalétique indiquant ses valeurs nominales de fonctionnement Cette plaque est apposée sur la face intérieure de la porte Illustration 1 Plaque signalétique de l ASI KERO HPE 400 500 kVA Avant toute opération d installation ou de démarrage de l ASI assurez vous que ses caractéristiques techniques sont compatibles avec l alimentation CA et les charges en sortie Vérif...

Page 740: ...ntégralité de ce manuel en particulier les exigences relatives à la sécurité La formation et les qualifications du personnel ne seront considérées comme valides que si elles ont été certifiées par le fabricant 2 3 3 Transport et manutention Évitez de tordre ou de déformer les composants ainsi que de modifier les distances d isolement lors du transport et de la manutention du produit Le poids d un ...

Page 741: ...source de chaleur L ASI est conçu pour des conditions de fonctionnement environnementales et climatiques normales telles que définies dans les caractéristiques techniques altitude température ambiante de fonctionnement humidité relative et conditions environnementales de transport et de stockage Il est nécessaire de mettre en œuvre des mesures de protection spécifiques en cas de conditions inhabit...

Page 742: ...ondent au système d alimentation CA et à la consommation électrique réelle de tous les équipements raccordés L ASI doit être installé conformément à la réglementation nationale en vigueur L ASI est également conçu pour être raccordé sur un système d alimentation inormatique Tous les raccordements électriques doivent être réalisés par un personnel autorisé Avant tout raccordement de l appareil véri...

Page 743: ...normes de sécurité en vigueur réglementations relatives aux équipements techniques et à la prévention des accidents L appareil ne peut être mis en marche utilisé et déconnecté que par un personnel autorisé Lorsqu il fonctionne l ASI convertit des puissances caractérisées par des tensions et courants élevés Toutes les portes et tous les capots doivent rester fermés La batterie fournie avec l ASI co...

Page 744: ...exion des sources d alimentation du fait de la décharge lente des condensateurs internes Nous recommandons par conséquent de patienter au moins 5 minutes avant d ouvrir les portes de l appareil Toute opération doit être réalisée uniquement en l absence de tension et dans le respect des directives de sécurité Assurez vous que le disjoncteur de la batterie qui peut se trouver à proximité de celle ci...

Page 745: ... mauvaise ventilation chaleur conduite ou rayonnante en provenance d autres sources moisissures insectes nuisibles 2 4 PROTECTION DE L ENVIRONNEMENT 2 4 1 Certification ISO 14001 Legrand est particulièrement sensible à l impact de ses produits sur l environnement C est pourquoi l ASI est fabriqué en tenant compte de critères d éco conception de pointe certification ISO 14001 Une attention spéciale...

Page 746: ...l emballaged origine Les dommages mécaniques subis par les composants électriques constituent un grave danger pour les personnes et les biens En cas de doute concernant l intégrité de l emballage ou du produit contactez le fabricant avant toute installation et ou démarrage 3 1 1 Stockage L emballage protège normalement l appareil de l humidité et des éventuels dommages pouvant se produire pendant ...

Page 747: ...chargement respectez toujours les indications concernant le barycentre de l appareil qui figurent surl emballage Avant de positionner l onduleur et afin d éviter les risques de bascules il est recommandé de déplacer le système sur la palette de bois sur lequel l onduleur est fixé Avant le positionnement dans l emplacement final retirer l onduleur de la palette Pour manipuler l onduleur supprimer l...

Page 748: ... d installation qui doivent être conformes à la législation en vigueur veuillez vous reporter à la section Ventilation Il est nécessaire de mettre en œuvre des mesures de protection spécifiques en cas de conditions environnementales inhabituelles fumées dangereuses poussières poussières abrasives humidité vapeur air à forte teneur en sel mauvaises conditions météorologiques ou aspersion d eau méla...

Page 749: ...se charge statique et poids 1296 190 550 550 180 645 75 855 Ø13 x4 PLAQUE ENTRÈE CÂBLES llustration 3 Plan de base Le sol soutenant l ASI doit être conçue pour supporter le poids de l ASI et assurer un maintien sûr et stable Sa capacité de soutien doit correspondre aux charges statiques indiquées dans le tableau ci dessous Puissance kVA 400 500 Poids kg 1080 1250 Charge statique kg m2 1390 1610 ...

Page 750: ...tallation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA 66 OMT87187 REV A 3 3 2 Dimensions totales dégagement minimum et ventilation Illustration 4 Dimensions globales D A B c Illustration 5 Dégagement minimum ...

Page 751: ... l air aussi correcte que possible Concernant le dégagement minimum par rapport aux murs les mêmes conditions d installation telles qu indiquées dans le tableau ci dessous s appliquent quelle que soit la taille de l ASI A mm B mm C mm D mm Dégagements recommandés 50 1200 50 600 Dégagement minimum 0 1200 0 400 La table ci dessous indique le volume d air nécessaire pour une ventilation et un refroid...

Page 752: ... Eau provenant d une source autre que la pluie NON Formation de glace NON Classification des conditions biologiques EN 60721 3 3 Agent d environnement Classe 3B1 3B2 3B3 a Flore NON Présence de moisissures champignons etc Présence de moisissures champignons etc b Faune NON Présence de rongeurs et d autres animaux nuisibles aux produits hors termites Présence de rongeurs et d autres animaux nuisibl...

Page 753: ...veillée et régulée de manière stricte catégorie des espaces propres X Sites sur lesquels l atmosphère est surveillée en permanence X Sites situés dans des régions rurales et urbaines présentant une faible activité industrielle et un trafic modéré X Sites situés dans des régions urbaines présentant une activité industrielle et ou un trafic important X Sites à proximité de sources industrielles d ém...

Page 754: ...la terre Pour l installation de la batterie respecter strictement la norme EN62040 1 2 et suivez le manuel d installation de l ASI Pour obtenir la durée de vie de la batterie indiquée par le fabricant de la batterie la température de fonctionnement doit rester comprise entre 0 et 25 C Cependant bien que la batterie puisse fonctionner jusqu à 40 C il y aura une réduction significative de la durée d...

Page 755: ...vue technique dépendent de la tension du courant absorbé par l ASI de la ligne de by pass et des batteries de la température ambiante et de la chute de tension Enfin la façon de poser les câbles doit également faire l objet d une attention particulière Pour plus d explications concernant le choix et le dimensionnement des câbles reportez vous aux normes CEI concernées en particulier la norme CEI 6...

Page 756: ...RACCORDEMENT DES CÂBLES D ALIMENTATION Pour le raccordement électrique de l ASI KEOR HPE 400 500 kVA les câbles suivants doivent être raccordés Alimentation CC depuis la batterie Alimentation CA depuis le secteur avec redresseur et by pass Sortie CA vers les charges Les câbles doivent être protégés contre les courts circuits et les courants de fuite à la terre Les points de raccordement doivent êt...

Page 757: ... selon la norme CEI UNEL35024 1 en utilisant les données suivantes Câbles de cuivre en PVC évalués à 70 température ambiante égale à 40 C longueur maximale des câbles égale à 30 m chute de tension 0 5 câbles posés dans des cavités de structures ou des chemins de câbles à fond plein Les sections transversales données ne prennent pas en compte les courants de surcharge autorisés par chaque ligne qui...

Page 758: ...ensités en utilisant un disjoncteur avec bobine de déclenchement à émission raccordé à l ASI suivant le schéma de principe décrit Illustration 6 6A En cas de défaut de retour de tension de l ASI l ASI enverra un signal de déclenchement au disjoncteur pour isoler l ASI et ainsi protéger les circuits de distribution amont L installateur doit appliquer le marquage d avertissement suivant sur tous les...

Page 759: ...E UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA OMT87187 REV A 75 Illustration 6 Diagramme à une ligne KEOR HPE 400kVA avec connexion à un périphérique externe ...

Page 760: ...E UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA 76 OMT87187 REV A Illustration 6A Diagramme à une ligne KEOR HPE 500kVA avec connexion à un périphérique externe ...

Page 761: ...KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA OMT87187 REV A 77 4 3 BORNIERS L ASI KEOR HPE 400 500 kVA est fourni avec des borniers permettant le raccordement des câbles d alimentation et les raccordements auxiliaires Illustration 7 Borniers KEOR HPE 400 500 kVA ...

Page 762: ... de telles mises à la terre sont supprimées durant l installation ou la maintenance appliquable aux équipements et alimentations à base de batteries ne nécessitant pas d avoir un circuit d alimentation relié à la terre Pour l installation de la batterie respecter strictement la norme EN62040 1 2 et suivez le manuel d installation de l ASI Pour obtenir la durée de vie de la batterie indiquée par le...

Page 763: ...BCB BCB et OCB lorsqu ils ne sont pas fournis sur la carte doivent être obligatoirement connectés à l ASI Illustration 8 Bornes auxiliaires du KEOR HPE 400 500 kVA 4 5 1 By pass manuel externe Contact auxiliaire du commutateur de by pass manuel externe sur les bornes X10 1 2 Un contact normalement ouvert est exigé à la fermeture du contact voir Procédure de by pass manuel le microprocesseur détect...

Page 764: ...batterie Contat auxiliaire de batterie bornes X10 9 10 Ce contact auxiliaire est nécessaire pour indiquer la position de l isolateur ouvert fermé 4 5 6 Contact auxiliaire du Groupe electrogène Contact auxiliaire du Groupe electrogène des bornes X10 11 12 Un contact normalement ouvert doit être utilisé le contact doit être fermé quand le groupe electrogène est actionné en fonctionnement Le micropro...

Page 765: ...utilisée pour les répétitions à distance des statuts et alarmes PARALLEL OPTIONNEL utilisé pour la communication entre des ASI enparallèles MODBUS OPTIONNEL utilisé pour la transmission de données vers l extérieur via le protocole MODBUS RUT RS485 SONDE THERMIQUE utilisé pour connaitre la température de la batterie armoire pièce afin d ajuster automatiquement la tension decharge SNMP OPTIONNEL uti...

Page 766: ...Nom Statuts en fonctionnement normal RL1 Alarme A30 ALARME GENERALE Hors tension si alarme présente 2 3 Fermé DL1 On 1 2 Ouvert RL2 Alarme A1 DEFAUT SECTEUR Hors tension si alarme présente 5 6 Fermé DL2 On 4 5 Ouvert RL3 Allarme A9 FIN AUTONOMIE BATTERIE Hors tension si alarme présente 8 9 Fermé DL3 On 7 8 Ouvert RL4 Alarme A13 ONDULEUR EN DEHORS DES TOLERANCES Hors tension si alarme présente 11 1...

Page 767: ...ls dispositifs sont installés en externe et leurs contacts auxiliaires proprement connectés au bornier de l ASI 5 1 VERIFICATIONS PRELIMINAIRES Avant de démarrer l unité assurez vous que tous les travaux d installation et de raccordement électrique ont été réalisés de manière professionnelle tous les câbles d alimentation et de commande sont correctement raccordés et serrés sur les borniers corres...

Page 768: ...ne soit demandé dans les instructions affichées par le panneau avant Les composants internes de l ASI et ou la batterie pourraient être gravement endommagés Réaliser une installation électrique correcte par le câblage des contacts auxiliaires du bypass manuel de l interrupteur de sortie et de la protection batterie au bornier dédié à l ASI Cela permettra à la logique de commande d acquérir l état ...

Page 769: ...rmer l interrupteur d entrée du redresseur RCB Ovrir quelques secondes l écran tactile démarre et affiche le schéma synoptique de l onduleur Illustration 11 UPS start up page 2 Après la phase de chargement du logiciel la logique de commande acquiert l état du système et le fonctionnement du commutateur RCB et affiche les séquences de fonctionnement Illustration 12 Rectifier start up ...

Page 770: ... Illustration 13 Inverter start up 3 Lorsque l onduleur est correctement démarré fermez l interrupteur de dérivation SBCB lorsque cela est indiqué par l affichage La logique vérifie l exactitude de la séquence de phase de dérivation et de la valeur de tension efficace Illustration 14 Bypass start up 4 Fermer l interrupteur de batterie BCB lorsque cela est indiqué par l affichage ...

Page 771: ... dans l armoire de batteries externe ne peut être fermé que si la tension continue est en tolérance Des dommages sérieux à la fois à la batterie et à l équipement peuvent se produire si le disjoncteur est fermé avant que le panneau avant ne l exige 5 Fermer l interrupteur de sortie de l onduleur OCB pour connecter l onduleur au bus de charge Après cette opération le démarrage est terminé et l écra...

Page 772: ...mentation des charges Dans cette configuration le système peut être redémarré via la procédure de retour depuis la charge en by pass manuel sans qu il soit nécessaire de mettre les charges hors tension Bypass manuel Afin de réaliser correctement la procédure de basculement assurez vous que le système n affiche aucune alarme Lors d un by pass manuel la charge est alimentée directement par le secteu...

Page 773: ...ypass_Sw est en position BYPASS et que l isolateur MBCB est fermé 1 Fermez l interrupteur d entrée du redresseur RCB Après quelques secondes l écran tactile démarre et affiche le schéma synoptique de l onduleur Illustration 18 REDEMARRAGE DEPUIS LE BY PASS MANUEL 2 Après la phase de chargement du logiciel la logique de commande acquiert l état du système et le fonctionnement du commutateur RCB et ...

Page 774: ... A 3 Fermez l interrupteur de batterie BCB lorsque cela est indiqué par l affichage Illustration 20 Connexion de la batterie 4 Fermer le commutateur de sortie OCB lorsque cela est nécessaire et immédiatement après l affichage vous devrez ouvrir le commutateur de dérivation manuelle MBCB L onduleur va démarrer Illustration 21 Fermeture de l interrupteur de sortie de l onduleur ...

Page 775: ...ento KEOR HPE UPS 400 500 kVA OMT87187 REV A 91 Illustration 22 Ouverture du commutateur de dérivation manuelle Illustration 23 Démarrage de l onduleur 5 Dès le démarrage de l onduleur il sera possible de transférer la charge Déplacez le commutateur de dérivation comme requis par l affichage pour terminer le démarrage de l onduleur ...

Page 776: ...UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA 92 OMT87187 REV A Illustration 24 Transférer la charge Illustration 25 Redémarrer à partir du bypass manuel terminé ...

Page 777: ...Installation and start up of KEOR HPE UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA OMT87187 REV A 93 LINGUA ITALIANA ...

Page 778: ...Installation and start up of KEOR HPE UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA 94 OMT87187 REV A ...

Page 779: ...eguito BST87 KEOR HPE 400 kVA BSU14 KEOR HPE 500 kVA Conservazione della documentazione Questo manuale e tutta la restante documentazione tecnica di supporto al prodotto devono essere conservati e possibilmente resi accessibili al personale nelle immediate vicinanze dell UPS Informazioni aggiuntive Nel caso le informazioni riportate nel presente manuale non fossero abbastanza esaurienti si prega d...

Page 780: ...care il tempo per la lettura del seguente manuale Lo scopo di questo manuale è di descrivere brevemente le parti che compongono l UPS e di guidare l installatore o l utente ad una corretta installazione dell apparato nell ambiente di utilizzo L installatore o l utente dovrà leggere ed eseguire correttamente quanto dichiarato nel presente manuale con particolare riguardo alle richieste relative all...

Page 781: ...i una targhetta di identificazione che riporta i dati nominali di funzionamento La targhetta è fissata nella parte interna della porta frontale Figura 1 Targhetta caratteristiche KEOR HPE 400 500 kVA Verificare le caratteristiche tecniche Prima di effettuare qualsiasi operazione di installazione e avviamento del dispositivo verificare che le caratteristiche tecniche siano compatibili con la rete d...

Page 782: ...no da considerarsi tali solo se certificati dall azienda produttrice 2 3 3 Trasporto e movimentazione Durante il trasporto e la movimentazione del prodotto prestare la massima attenzione al fine di evitare di piegare o deformare le parti componenti e di modificare le distanze di isolamento Peso non distribuito Il peso dell UPS non è uniformemente distribuito Prestare particolare attenzione nel sol...

Page 783: ...itivo all esposizione diretta dei raggi solari e non posizionarlo in prossimità di una fonte di calore Condizioni ambientali particolari L UPS è progettato per sopportare condizioni climatiche ed ambientali di esercizio normali come indicato nella specifica tecnica altitudine temperatura ambiente d esercizio umidità relativa condizioni ambientali di trasporto e stoccaggio Si rende necessarie mette...

Page 784: ...ttrica di alimentazione ed al consumo elettrico reale della totalità delle apparecchiature collegate Verificare la conformità alle normative L UPS deve essere installato conformemente alle normative vigenti nel paese di installazione Sistema IT L apparecchiatura è stata progettata anche per essere collegata ad un sistema di distribuzione dell alimentazione IT Tutti i collegamenti elettrici devono ...

Page 785: ...no parte gli UPS devono seguire tutte le norme vigenti riguardanti la sicurezza equipaggiamenti tecnici e regolamenti antinfortunistici Il dispositivo deve essere avviato manovrato e disconnesso solamente da parte di personale autorizzato Le tarature possono essere modificate solo utilizzando il software di interfaccia originale Pericolo di lesioni a seguito shock elettrico Durante il funzionament...

Page 786: ... l eventuale disconnessione dalle sorgenti di alimentazione a causa dei condensatori interni che si scaricano lentamente Si consiglia quindi di attendere almeno 5 minuti prima di aprire le porte del dispositivo Pericolo di lesioni a seguito shock elettrico Eventuali interventi devono essere effettuati solamente in assenza di tensione e nel rispetto delle direttive sulla sicurezza Accertarsi di ave...

Page 787: ...zione calore condotto o irradiato proveniente da altre fonti funghi insetti nocivi parassiti 2 4 TUTELA AMBIENTALE 2 4 1 Certificazione ISO 14001 Legrand è particolarmente sensibile all impatto ambientale dei propri prodotti per questo motivo l UPS è stato realizzato seguendo i più moderni criteri di eco progettazione certificazione ISO 14001 E stata prestata particolare attenzione nell utilizzo d...

Page 788: ... al costruttore si prega di utilizzare l imballaggio originale Pericolo per le persone a seguito di danni da trasporto Il danneggiamento meccanico dei componenti elettrici costituisce un grave pericolo per persone e cose Qualora si abbia il dubbio di una non completa integrità dell imballo o del prodotto entro ad esso contenuto contattare l azienda produttrice prima di effettuare l installazione e...

Page 789: ...tta Durante le manovre di carico e scarico rispettare sempre le indicazioni relative al baricentro del dispositivo contrassegnato sull imballaggio Per gli spostamenti dell UPS prima del posizionamento finale si consiglia di non rimuoverlo dal pancale in legno sul quale è fissato per evitare eventuali rischi di ribaltamento Prima del posizionamento rimuovere l UPS dal pancale togliendo le staffe di...

Page 790: ...le condizioni ambientali nel luogo di installazione in accordo alle normative correnti fare riferimento alla sezione Dimensioni di ingombro distanze minime dalle pareti e ventilazione Condizioni ambientali particolari Si rende necessario mettere in atto misure di protezione specifiche in caso di condizioni ambientali insolite fumi nocivi polveri polvere abrasiva umidità vapore aria salina intemper...

Page 791: ... carico statico e pesi 1296 190 550 550 180 645 75 855 Ø13 x4 PIASTRA INGRESSO CAVI Figura 3 Pianta di base La base di appoggio dell UPS deve essere progettata per sopportare il peso del dispositivo e per garantirne il supporto saldo e sicuro La capacità portante deve essere conforme al carico statico indicato nella tabella seguente Potenza kVA 400 500 Peso kg 1080 1250 Carico statico kg m2 1390 1...

Page 792: ...ation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA 108 OMT87187 REV A 3 3 2 Dimensioni di ingombro distanze minime dalle pareti e ventilazione Figura 4 Dimensioni di ingombro D A B c Figura 5 Distanze di rispetto ...

Page 793: ...e per quanto possibile il corretto flusso di aria Per tutte le taglie di UPS valgono le stesse condizioni di installazione per quanto riguarda le distanze minime dalle pareti come indicate nella tabella seguente A mm B mm C mm D mm Distanze raccomandate 50 1200 50 600 Distanze minime 0 1200 0 400 La tabella seguente mostra il volume d aria richiesto per la ventilazione e il raffreddamento ottimali...

Page 794: ...di origine diversa dalla pioggia NO Formazione di ghiaccio NO Classificazione delle condizioni biologiche EN 60721 3 3 Parametro ambientale Classe 3B1 3B2 3B3 c Flora NO Presenza di muffa funghi ecc Presenza di muffa funghi ecc d Fauna NO Presenza di roditori e altri animali dannosi ai prodotti escludendo le termiti Presenza di roditori e altri animali dannosi ai prodotti includendo le termiti Cla...

Page 795: ...fera strettamente monitorata e controllata categoria camera pulita X Luoghi con atmosfera continuamente controllata X Luoghi posti in zone rurali e urbane dove sono modeste le attività industriali e il traffico è moderato X Luoghi in zone urbane con attività industriali e o grande traffico X Luoghi posti in prossimità di sorgenti industriali con emissioni chimiche X Luoghi posti all interno di ins...

Page 796: ...o a terra Seguire le istruzioni d installazione Per l installazione delle batterie attenersi rigorosamente alle EN62040 1 inoltre dovrà essere seguito il manuale di installazione dell UPS Per ottenere una durata di vita della batteria pari a quella indicata dal costruttore la temperatura di esercizio deve essere compresa fra 0 e 25 C La batteria può comunque operare fino a 40 C con forte riduzione...

Page 797: ...tenendo in considerazione gli aspetti tecnici economici e di sicurezza La scelta e il dimensionamento dei cavi dal punto di vista tecnico è funzione della tensione della corrente assorbita dall UPS dalla rete bypass e dalle batterie della temperatura ambiente e della caduta di tensione infine si deve tenere in particolare considerazione il tipo di posa del cavo Ulteriori chiarimenti sulla scelta e...

Page 798: ...la rete 4 1 COLLEGAMENTO CONDUTTORI DI POTENZA Per il collegamento elettrico dell UPS KEOR HPE 400 500 kVA è necessario allacciare i seguenti conduttori Alimentazione DC da batteria se la batteria è esterna Alimentazione AC dalla rete di alimentazione raddrizzatore e bypass Uscita AC verso i carichi Pericolo di lesioni a seguito shock elettrico Sono presenti tensioni molto elevate ai capi dei cavi...

Page 799: ...ono indicative I cavi sono stati dimensionati in accordo alla norma CEI UNEL35024 1 utilizzando i seguenti dati cavi unipolari in rame con isolamento in PVC e temperatura massima di 70 C temperatura ambiente pari a 40 C massima lunghezza dei cavi pari a 30 m caduta di tensione 0 5 posa dei cavi in cavità di strutture o passerelle non perforate Le sezioni dei cavi non tengono conto dei valori di so...

Page 800: ...pass mediante MCCB dotato di una bobina a lancio di corrente e collegata all UPS secondo lo schema elettrico riportato in Figura 6 6A In caso di guasto di backfeed rilevato dall UPS l UPS invierà alla bobina un segnale di 230 Vac impulsivo che farà trippare il MCCB quindi isolerà l UPS al fine di proteggere i circuiti di distribuzione a monte dell UPS L installatore deve applicare la seguente etic...

Page 801: ...EOR HPE UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA OMT87187 REV A 117 Figura 6 Schema unifilare KEOR HPE 400kVA con collegamento al dispositivo esterno ...

Page 802: ...OR HPE UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA 118 OMT87187 REV A Figura 6A Schema unifilare KEOR HPE 500kVA con collegamento al dispositivo esterno ...

Page 803: ...e l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA OMT87187 REV A 119 4 3 MORSETTIERE L UPS KEOR HPE 400 500 kVA è provvisto di morsettiere per l allacciamento dei cavi di potenza e delle connessioni ausiliarie Figura 7 Morsettiera KEOR HPE 400 500 kVA ...

Page 804: ...a scossa elettrica La probabilità può essere ridotta se i collegamenti di terra vengono interrotti durante l installazione e la manutenzione applicabile ad apparecchiature e ad alimentazioni a batteria poste a distanza prive di circuito di alimentazione messo a terra Installazione batterie Per l installazione delle batterie attenersi rigorosamente alle EN62040 1 paragrafo 7 6 Per ottenere una dura...

Page 805: ... degli interruttori MBCB BCB e OCB esterni se previsti devono obbligatoriamente essere collegati all UPS Figura 8 Morsetti ausiliari KEOR HPE 400 500 kVA 4 5 1 Bypass manuale esterno Contatto ausiliario dell interruttore di bypass manuale esterno se previsto morsetti X10 1 2 Un contatto normalmente aperto deve essere utilizzato alla chiusura del contatto vedere procedura di Bypass Manuale il micro...

Page 806: ...ontatto ausiliario sezionatore di batteria Contatto ausiliario del sezionatore di Batteria morsetti X10 9 10 Contatto ausiliario necessario per l indicazione della posizione del sezionatore aperto chiuso 4 5 6 Contatto ausiliario Generatore Diesel Contatto ausiliario proveniente da gruppo elettrogeno morsetti X10 11 12 Deve essere utilizzato un contatto normalmente aperto il contatto deve chiuders...

Page 807: ... per la ripetizione a distanza di stati di funzionamento e allarmi PARALLELO OPZIONALE utilizzata per la comunicazione tra UPS in configurazione parallelo MODBUS utilizzata per la trasmissione dei dati all esterno per mezzo di protocollo MODBUS RUT RS485 SONDA TERMICA utilizzata per l acquisizione della temperatura della batteria e la regolazione automatica della tensione di carica SNMP OPZIONALE ...

Page 808: ...M1 Led Pin Stato in funzionamento normale Nome Stato in funzionamento normale RL1 Allarme A30 ALLARME GENERALE Non energ se allarme presente 2 3 Chiuso DL1 On 1 2 Aperto RL2 Allarme A1 MANCANZA RETE Non energ se allarme presente 5 6 Chiuso DL2 On 4 5 Aperto RL3 Allarme A9 FINE AUT BATTERIA Non energ se allarme presente 8 9 Chiuso DL3 On 7 8 Aperto RL4 Allarme A13 INV FUORI TOL Non energ se allarme...

Page 809: ...i Tutte le procedure che seguono fanno riferimento al dispositivo di interruzione BCB e sono valide solamente se tale dispositivo è installato esternamente e i suoi contatti ausiliari opportunamente cablati agli appositi morsetti nell UPS 5 1 VERIFICHE PRELIMINARI Prima di iniziare la procedura di avvio verificare che tutti i lavori di installazione e allacciamento elettrico siano stati eseguiti a...

Page 810: ...ontatti ausiliari Durante l installazione elettrica prestare cura al cablaggio dei contatti ausiliari degli isolatori di bypass manuale uscita e batteria che vanno collegati agli appositi morsetti sull UPS In questo modo la logica di controllo acquisisce lo stato degli interruttori per guidare l operatore durante le procedure di avvio e bypass manuale L avviamento del sistema è completamente guida...

Page 811: ...A 127 1 Chiudere il sezionatore di ingresso raddrizzatore RCB Dopo alcuni secondi il touch screen si avvierà e mostrerà il diagramma sinottico dell UPS Figura 11 Schermata avvio UPS 2 Dopo la fase di caricamento del software la logica di controllo acquisisce lo stato del sistema a seguito della chiusura di RCB e mostra le sequenze di avviamento Figura 12 Avvio raddrizzatore ...

Page 812: ...PS 400 500 kVA 128 OMT87187 REV A Figura 13 Avvio inverter 3 Appena l inverter è correttamente avviato chiudere il sezionatore SBCB quando indicato dal display La logica controlla che la sequenza fasi e il valore RMS della tensione di bypass siano corrette Figura 14 Avvio bypass 4 Chiudere il sezionatore di batteria BCB quando indicato dal display ...

Page 813: ...el sezionatore BCB posto nell armadio esterno può essere effettuata solamente se la tensione DC è in tolleranza Se effettuata prima che venga richiesta dal pannello frontale può causare seri danni all apparecchiatura e o alla batteria 5 Chiudere il sezionatore di uscita OCB per connettere l UPS alla sbarra di carico Dopo questa operazione l avviamento è completo e il display mostra il sinottico fi...

Page 814: ...ntinuità di alimentazione sui carichi In questa configurazione tramite la procedura di ritorno da carico su bypass manuale è anche possibile riavviare il sistema senza dover disalimentare i carichi Bypass manuale Per eseguire la procedura di trasferimento in modo corretto verificare che non siano presenti allarmi sul sistema In bypass manuale il carico è alimentato direttamente dalla rete d ingres...

Page 815: ...tore Bypass_Sw sia in posizione BYPASS e il sezionatore MBCB Chiuso 1 Chiudere il sezionatore di ingresso raddrizzatore RCB Dopo alcuni secondi il touch screen si avvierà e mostrerà il diagramma sinottico dell UPS Figura 18 Avvio da bypass manuale 2 Dopo la fase di caricamento del software la logica di controllo acquisisce lo stato del sistema a seguito della chiusura di RCB e mostra le sequenze d...

Page 816: ...A 132 OMT87187 REV A 3 Chiudere il sezionatore di batteria BCB quando indicato dal display Figura 20 Connessione della batteria 4 Chiudere il sezionatore OCB quando richiesto immediatamente dopo il display richiederà di aprire il sezionatore di bypass manuale MBCB A seguito di tale operazione l inverter si avvierà Figura 21 Chiusura del sezionatore uscita UPS ...

Page 817: ...Installazione e avviamento KEOR HPE UPS 400 500 kVA OMT87187 REV A 133 Figura 22 Apertura del sezionatore di bypass manuale Figura 23 Avvio inverter 5 Appena l inverter è correttamente avviato sarà possibile trasferire il carico Muovere il selettore Bypass SW come richiesto per completare l avviamento dell UPS ...

Page 818: ...KEOR HPE UPS 400 500 kVA Installation et démarrage de l ASI KEOR HPE 400 500 kVA Installazione e avviamento KEOR HPE UPS 400 500 kVA 134 OMT87187 REV A Figura 24 Trasferimento del carico Figura 25 Avvio da bypass manuale completato ...

Page 819: ... L ASI UTILIZZO DELL UPS Index Indice ENGLISH LANGUAGE 11 1 SCOPE 12 2 SAFETY RULES AND WARNINGS 13 3 GENERAL UPS DESCRIPTION 14 3 1 TYPOLOGY 14 3 2 SYSTEM DESCRIPTION 14 3 2 1 Rectifier 14 3 2 2 Inverter 15 3 2 3 Battery and battery charger 15 3 2 4 Static bypass 15 3 2 5 Manual bypass 15 3 3 OPERATING STATUS 16 3 3 1 Normal operation 16 3 3 2 Green Conversion 16 3 3 3 Bypass operation 17 3 3 4 B...

Page 820: ...tery test 33 5 3 3 Resetting the history log 34 5 3 4 Modifying the operating mode ECO MODE 34 5 4 SETTINGS AND ADVANCED OPERATIONS 35 5 4 1 Setting date and time 36 5 4 2 Setting the display language 37 5 4 3 Setting the battery 38 5 4 4 New battery 39 5 4 5 Setting the RS485 user interface parameters 39 5 4 6 Setting the display network parameters 39 5 4 6 1 Setting the LAN parameters 39 5 4 6 2...

Page 821: ...É ET AVERTISSEMENTS 67 3 DESCRIPTION GÉNÉRALE DE L ALIMENTATION SANS COUPURE UPS 68 3 1 TYPOLOGIE 68 3 2 DESCRIPTION DU SYSTÈME 68 3 2 1 Redresseur 68 3 2 2 Onduleur 69 3 2 3 Batterie et chargeur de batterie 69 3 2 4 Commutateur de dérivation statique 69 3 2 5 Commutateur de dérivation manuelle 69 3 3 ÉTAT D EXPLOITATION 70 3 3 1 Fonctionnement normal 70 3 3 2 Conversion écologique 70 3 3 3 Foncti...

Page 822: ...9 5 4 1 Configuration de la date et de l heure 90 5 4 2 Configuration de la langue d affichage 91 5 4 3 Configuration de la batterie 92 5 4 4 Nouvelle batterie 93 5 4 5 Configuration des paramètres de l interface utilisateur RS485 93 5 4 6 Configuration des paramètres réseau d affichage 93 5 4 6 1 Configuration des paramètres LAN 93 5 4 6 2 Configuration des paramètres NTP 94 5 4 6 3 Modification ...

Page 823: ...LE E AVVERTENZE DI SICUREZZA 121 3 DESCRIZIONE GENERALE DELL UPS 122 3 1 TIPOLOGIA 122 3 2 DESCRIZIONE DEL SISTEMA 122 3 2 1 Raddrizzatore 122 3 2 2 Inverter 123 3 2 3 Batteria e carica batteria 123 3 2 4 Bypass statico 123 3 2 5 Bypass manuale 123 3 3 STATI DI FUNZIONAMENTO 124 3 3 1 Funzionamento normale 124 3 3 2 Green Conversion 124 3 3 3 Funzionamento da bypass 125 3 3 4 Funzionamento da batt...

Page 824: ...splay 145 5 4 3 Impostazioni batteria 146 5 4 4 Nuova batteria 147 5 4 5 Impostazione parametri di interfaccia utente RS485 147 5 4 6 Impostazione parametri di rete del touch screen 147 5 4 6 1 Impostazione parametri LAN 147 5 4 6 2 Impostazione parametri NTP 148 5 4 6 3 Modifica dei parametri 149 5 5 INFORMAZIONI SUL SISTEMA 150 5 5 1 Informazioni dispositivo 150 5 5 2 Informazioni parallelo 151 ...

Page 825: ...izzo dell UPS OMP06263 REV B 7 5 5 4 Informazioni sulla comunicazione RS485 154 5 5 5 Versioni firmware 154 5 5 6 Informazioni relative all assistenza 154 6 GUASTI E ALLARMI 155 6 1 DEFINIZIONE DEGLI STATI DI FUNZIONAMENTO 156 6 2 CONTROLLO DEI GUASTI 159 ...

Page 826: ...ory log page 2 29 Picture 16 Saving the history log 29 Picture 17 Access password to the Controls section 32 Picture 18 Controls section 32 Picture 19 Access password to the Settings section 35 Picture 20 Settings section 35 Picture 21 Clock manual setting 36 Picture 22 Clock automatic setting 37 Picture 23 Language setting 37 Picture 24 Battery parameters setting 38 Picture 25 Battery parameters ...

Page 827: ... journal des historiques 83 Image 17 Mot de passe d accès à la section Controles 86 Image 18 Section Controles 86 Image 19 Mot de passe d accès à la section Reglages 89 Image 20 Section Reglages 89 Image 21 Configuration manuelle de l horloge 90 Image 22 Configuration automatique de l horloge 91 Image 23 Configuration de la langue 91 Image 24 Configuration des paramètres de la batterie 92 Image 25...

Page 828: ...37 Figura 17 Password di accesso alla sezione Controlli 140 Figura 18 Sezione Controlli 140 Figura 19 Password di accesso alla sezione Impostazioni 143 Figura 20 Sezione Impostazioni 143 Figura 21 Impostazione manuale orologio 144 Figura 22 Impostazione automatica orologio 145 Figura 23 Impostazione lingua 145 Figura 24 Impostazione parametri batteria 146 Figura 25 Impostazione capacità batteria c...

Page 829: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMP06263 REV B 11 ENGLISH LANGUAGE ...

Page 830: ... 300 kVA BST87 KEOR HPE 400 kVA BSU14 KEOR HPE 500 kVA Storing documentation This manual and any other supporting technical documentation relating to the product must be stored and made accessible to personnel in the immediate vicinity of the UPS Further information In the event that the information provided in this manual is not sufficiently exhaustive please contact the manufacturer of the devic...

Page 831: ...ned in the manuals must be strictly followed Injury hazard due to device failure Potentially hazardous situations may arise in case of UPS failure Do not use the device if visibly damaged Maintain the device regularly to identify possible failure Possible device damage Whenever work is carried out on the device make sure all actions are taken in order to avoid electrostatic discharges which might ...

Page 832: ...e line or the plugs supplied by the UPS making the User aware of this fact Picture 1 Block diagram The UPS uses IGBT technology with a high switching frequency in order to allow a low distortion of the current re injected into the supply line as well as high quality and stability of output voltage The components used assure high reliability very high efficiency and maintenance easiness 3 2 SYSTEM ...

Page 833: ...ectifier s control electronics The battery is charged according to the DIN 41773 Standard every time it has been partially or completely discharged When its full capacity is restored it is disconnected from the DC bus by means of a static switch in order to save energy reduce the stress due to the AC ripple thus increasing the lifetime This operating mode is called Green Conversion It is however p...

Page 834: ...the inverter and compensates mains voltage as well as load variations keeping the DC voltage constant At the same time it provides to charge the battery The inverter converts the DC voltage into an AC sine wave with stabilized voltage and frequency and also supplies the load via its static switch SSI Picture 2 Normal operation 3 3 2 Green Conversion During the operation in Green Conversion mode th...

Page 835: ... 48 hours Lost capacity 20 Additional charge for 96 hours Such values complies with the recommendations of the main battery manufacturers Set the right battery capacity The UPS front panel allows the setting of the battery parameters including the rated capacity Considering the importance that such value assumes for the correct execution of the charge control algorithm it is highly recommended to ...

Page 836: ...y The system restart from the black out condition can be customized based on the requirements of the plant in three different modes Bypass loads are supplied as soon as the bypass line is available factory configuration Inverter loads are supplied by the inverter even if the bypass line is available when the battery voltage has reached a programmed threshold after the rectifier restart Man Inverte...

Page 837: ...auxiliary contacts Carry out a proper electrical installation by wiring the auxiliary contacts of the manual bypass and output isolators to the dedicated terminals on board the UPS This will allow the control logic to acquire the status of the switches and guide the operator during the start up and manual bypass procedures For further information refer to the section Installation and start up Duri...

Page 838: ...n and control devices of the UPS is intended for authorized personnel only We recommend to check the training of the personnel responsible for the use and maintenance of the system 3 4 1 Isolators The isolators provided on the UPS are used to isolate the power components of the device from the AC supply line from the storage battery and from the load Voltage present on terminals The isolators do n...

Page 839: ...d you are sure that there is no hazard to persons and things 3 4 3 Normal Bypass selector It is used during the manual bypass procedure when it is necessary to isolate the UPS for maintenance or repair Follow the procedures contained in the manual The Normal Bypass selector shall only be operated in accordance with the procedures specified in the installation and start up section The manufacturer ...

Page 840: ...ng through the pages of the touch screen is possible through the seven icons provided on the right hand side the icon with the up down arrows controls the display communication Description of the icon Icon Assigned functions Home Goes back to the Home page Measures Enters the Measures section A page of the Measures section is currently displayed Controls Enters the Controls section A page of the C...

Page 841: ...section A page of the Info section is currently displayed Back Goes back one page Communication Controls the communication between the panel and the UPS electronics Communication Ok Controls the communication between the panel and the UPS electronics Communication Ko in case of communication error between the touch screen and the UPS control logic 4 2 STATUS BAR The status bar at the bottom provid...

Page 842: ...sections of the control panel from the Home page directly 5 1 DISPLAYING THE MEASURES Pressing on a specific object gives access to the display of the measurements of that specific section of the UPS Picture 9 UPS front panel Home page For example by clicking on the object indicated in the figure above you access the Measures Inverter screen visible below Picture 10 Measures Inverter ...

Page 843: ... is given below Sub page Displayed data Accuracy INPUT Rectifier input voltage 1 1 V Rectifier input current 1 A Frequency 0 1 Hz Input power 1 kVA OUTPUT Voltage 1 1 V Current 1 A Load percentage 1 Active power 1 kW Apparente power 1 kVA Frequency 0 1 Hz BYPASS Voltage 1 1 V Frequency 0 1 Hz INVERTER Voltage 1 1 V Frequency 0 1 Hz AC DC Rectifier output voltage 1 V BATTERY Voltage and current 1 V...

Page 844: ...izzo dell UPS 26 OMP06263 REV B Sub page Displayed data Accuracy TEMPERATURE 2 Battery 0 1 C UPS 0 1 C 1 The voltage measures are always given referred to the phase to neutral value 2 The temperatures are displayed only if the relevant probe is installed ...

Page 845: ...perating status or the history log can be selected Picture 12 Alarms section 5 2 1 Displaying the operating status Press UPS status to show the UPS operating status which includes possible active alarms Picture 13 Alarms section The current system status is shown in case the list is longer than the page capacity 8 lines it can be scrolled by sliding a finger on the screen ...

Page 846: ...ory Picture 14 History log page 1 The first event shown is the latest one in order of time a new event makes all the other events automatically shift one position clearing the oldest event Each line shows the number of the event position within the list the alarm code and date and time an asterisk indicates the automatic reset of the alarm The maximum number of events which can be shown is equal t...

Page 847: ...ing page Picture 16 Saving the history log The touch screen automatically recognizes when an external memory support USB stick or SD card is inserted and changes the colour of the relevant icon from grey disabled to white enabled The text file that will be saved contains the same information available on the History pages completed with the decription of each event ...

Page 848: ... OVER CURRENT A16 BYPASS LOAD A50 CURRENT INVERTER SATURED A17 RETRANSFER BLOCKED A51 BATTERY TEMPERATURE A18 MBCB CLOSED MBCB BUS CLOSED A52 UNDER VOLTAGE LOCKOUT A19 OCB OPEN A53 FIRMWARE ERROR A20 OVERLOAD A54 CAN ERROR A21 THERMAL IMAGE A55 PARALLEL CABLE DISCONNECTED A22 BYPASS SWITCH A56 MAINS UNBALANCED A23 EPO PRESSED A57 CONTACTOR FAILURE A24 HIGH TEMPERATURE A58 INVERTER CURRENT UNBALANC...

Page 849: ...e ALARMS STATUS menu is entered The alarms are shown when they are present and must be silenced with the buzzer The alarms remain displayed whilst they are present and they are automatically stored in the event log with date and time Description of alarms and statuses For a more detailed description of the alarms and statuses see the Faults and alarms section of the present manual ...

Page 850: ...icon will show the control section access page protected by password Picture 17 Access password to the Controls section Picture 18 Controls section Password protected access The CONTROLS menu is protected by a password set by the factory in order to prevent access to unauthorized personnel We recommend minimum disclosure of the access password ...

Page 851: ... A44 INVERTER DESATURATION A50 CURRENT INVERTER SATURED A52 UNDER VOLTAGE LOCKOUT A55 PARALLEL CABLE DISCONNECTED System restart after a shutdown due to EPO activation For a description of the UPS status in each of the failure conditions listed above please refer to the Faults and alarms section A28 CRITICAL STOP NOTE Reccomended to performe the service test before restart the UPS The UPS is equip...

Page 852: ...rter is turned on ready to take over in case of anomalies of the mains The transfer occurs in a maximum time of 10 ms The stability of the AC mains is controlled bu a specific algorithm which provides to automatically de activate the ECO MODE mode in case the voltage or frequency are not compliant with the programmed requirements Modifying the UPS operating mode ECO MODE The modification of the UP...

Page 853: ...icon will show the setting section access page protected by password Picture 19 Access password to the Settings section Picture 20 Settings section Password protected access The SETTINGS menu is protected by a password set by the factory in order to prevent access to unauthorized personnel We recommend minimum disclosure of the access password ...

Page 854: ...ime Date and time may be set via the CLOCK page Picture 21 Clock manual setting Setting the current date and time correctly The correct setting of the date and time is essential for the recording of the event log The system also allows the setting of a NTP server for the synchronization of date and time Such configuration mode is enabled by pressing the label Disabled As the NTP server is enabled ...

Page 855: ...e configured via the Network configuration pages in the Settings section In case the server does not respond or the LAN connection is lacking the message NTP ERROR will be displayed 5 4 2 Setting the display language The following picture shows the languages that can be set Picture 23 Language setting The language selection is made pressing one of the flags ...

Page 856: ...ge battery the BATTERY PARAM section allows to set such data Each single settable parameter can be accessed via the following page Picture 24 Battery parameters setting The various parameters setting pages are similar to each other and requires the operator to enter and confirm the value the setting page of the battery capacity is given below as a reference Picture 25 Battery parameters setting ...

Page 857: ...tting the RS485 user interface parameters The parameters regarding the communication via RS485 interface can be set in the MODBUS RS485 section This section allows to set the ModBus address the communication mode and the data transmission speed 5 4 6 Setting the display network parameters The NETWORK CONFIG section allows to configure the parameters related to the LAN network and to the system tim...

Page 858: ...B Picture 27 LAN parameters setting 5 4 6 2 Setting the NTP parameters The NTP service parameters which can be set are the following Primary NTP server address Secondary NTP server address NTP Enabling Disabling is performed in the menu SETTINGS CLOCK Picture 28 NTP parameters setting ...

Page 859: ... will be displayed on the editable string in the upper part of the page together with a keypad Picture 29 Modification of numerical parameters The fields related to the NTP servers may either be numerical IP address of the remote server or alphanumerical when the remote server can be reached via a web address In such case the keypad that will appear in the page is complete Picture 30 Modification ...

Page 860: ... information about the UPS press the related icon to open the main page Picture 31 Info section All the data shown in the varius sections are set during the factory test via a specific interface software and cannot be modified by anyone except for personnel authorized by the manufacturer 5 5 1 Device information Picture 32 Device information ...

Page 861: ...rrent system date and time setting 5 5 2 Parallel information The page containing the information about the parallel is only enabled if the UPS is in parallel with others UPS Picture 33 Parallel information 5 5 2 1 Parallel index The first number identifies the position of that specific UPS within the parallel system The second number represents the total number of UPS units 5 5 2 2 Master Slave p...

Page 862: ...s that the system is redundant and the redundancy index is indicated by number X For example in a system composed of 3 UPS units REDUNDANT 2 means that only one of the UPS units is sufficient to feed the load 5 5 2 5 Message statistics The statistics section regarding the messages exchanged on the communication buses consists of three different parts CAN STAT SSW Number of messages received and pe...

Page 863: ...ectively The brackets around a letter indicate that we are working on that specific UPS unit A question mark next to a number indicates that that UPS unit is not communicating on the data bus 5 5 3 4 Parallel type The string may have two values POWER or REDUNDANT x POWER means that the parallel system is so set as to require the presence of all the UPS units to feed the load REDUNDANT x means that...

Page 864: ... the settings of the communication port as regards the assigned ModBus address the communication mode and the data transmission speed 5 5 5 Firmware release Picture 36 Firmware release The second page of the firmware release info contains the license contract related to the touch screen operating software 5 5 6 Service information The SERVICE menu provides important information regarding the techn...

Page 865: ...larm code and a brief description are shown Injury hazard due to electric shock Before carrying out any operation on the UPS make sure that all the safety precautions are adhered to Any work on the unit must be carried out by qualified personnel Internal components can only be accessed after disconnecting the device from supply sources Always use protective devices designed for each type of activi...

Page 866: ...e inverter is ready to feed the load Status S4 INVERTER LOAD Description The inverter feeds the load Operating condition The load is fed via the static inverter switch Status S5 INVERTER BYPASS SYNCHRONIZED Description The inverter is synchronized with the bypass Operating condition The synchronization between the inverter and the bypass is locked and the static switch can change over from one sou...

Page 867: ...on The battery is charging Operating condition The battery static switch is closed and the battery is in the second and final phase of the I U charging mode DIN 41773 with constant voltage and decreasing current Status S16 HIGH BYPASS COMMUTATION Description Switching with high bypass voltage Operating condition Switching from inverter to bypass with inverter switch off caused by the bypass voltag...

Page 868: ... the phase rotation 2 If the alarm persists contact our Technical Support Service Alarm A3 BOOSTER STOPPED Description The rectifier has been temporarily disconnected and the inverter is fed by the battery Possible causes Instability of the AC line voltage or frequency Possible fault in the rectifier control circuit Solutions 1 Check the parameters of the AC line voltage 2 Restart the device 3 If ...

Page 869: ...of the battery Possible causes A battery test has been started automatically if set or manually by the user Solutions 1 Wait for the test to end and check possible battery faults Alarm A7 BCB OPEN Description The battery isolator is open Possible causes Battery isolator open Solutions 1 Check the status of the battery isolator 2 Check the functionality of the auxiliary contact of the isolator 3 Ch...

Page 870: ...ery 2 Reset the system 3 If the alarm persists contact our Technical Support Service Alarm A11 SHORT CIRCUIT Description The current sensor has detected a short circuit at the output Possible causes Load problem Measuring circuit failure Solutions 1 Check the loads connected to the UPS output 2 If the alarm persists contact our Technical Support Service Alarm A12 STOP TIMEOUT SHORT CIRCUIT Descrip...

Page 871: ...nection of power cables Solutions 1 Check the phase rotation 2 If the alarm persists contact our Technical Support Service Alarm A15 BYPASS FAULT Description The voltage or frequency of the bypass line are out of tolerance Possible causes Bypass line instability or failure Wrong phase rotation Solutions 1 Check the connections to the mains 2 Check the stability of mains voltage 3 If the alarm pers...

Page 872: ...f the manual bypass isolator 2 Check the functionality of the auxiliary contact of the isolator 3 If the alarm persists contact our Technical Support Service Alarm A19 OCB OPEN Description The output isolator is open Possible causes Output isolator open Solutions 1 Check the status of the output isolator 2 Check the functionality of the auxiliary contact of the isolator 3 If the alarm persists con...

Page 873: ...chnical Support Service Alarm A23 EPO PRESSED Description The system is blocked due to the activation of the emergency power off button Possible causes Activation of the local or remote emergency power off button Solutions 1 Release the emergency power off button and reset the alarm 2 If the alarm persists contact our Technical Support Service Alarm A24 HIGH TEMPERATURE Description High temperatur...

Page 874: ...controller has detected an error in the parameters stored in EEPROM Possible causes Wrong parameters entered during programming Solutions 1 Contact our Technical Support Service Alarm A28 CRITICAL STOP Description An alarm has been activated which causes the shutdown of part of the UPS rectifier inverter static switch Possible causes System failure Solutions 1 Check which alarms are present and ca...

Page 875: ...capacitors towards the middle point are different Possible causes Possible failure on the measuring circuit Possible fault of DC capacitors Solutions 1 Reset the system 2 If the alarm persists contact our Technical Support Service Alarm A34 SERVICE REQUIRED Description A UPS check is necessary Possible causes Possible UPS fault Solutions 1 If the alarm persists contact our Technical Support Servic...

Page 876: ... isolator 2 Check the functionality of the auxiliary contact of the isolator 3 If the alarm persists contact our Technical Support Service Alarm A38 INVERTER LOAD Description The load is fed by the inverter This alarm is active for UPS systems in ECO mode where the preferential supply is from the bypass line Possible causes Temporary changeover due to bypass line failure Solutions 1 Verify the sta...

Page 877: ...auses The UPS detected the DC current out of limits and switch off the inverter booster and disconnected the battery from the UPS Solutions 1 Check that there aren t short circuit in DC bus 2 Check the battery current sensor 3 Check the battery blocks 4 If the alarm persists contact our Technical Support Service Alarm A42 LOST OF REDUND POWER SUPPLY Description Failure of the redundant auxiliary p...

Page 878: ...k the air conditioning system if present 4 If the alarm persists contact our Technical Support Service Alarm A46 LOST OF REDUNDANCY Description This alarm is only active on PARALLEL systems Continuity is not ensured in the event of a fault on one of the UPS units Possible causes The total load is higher than the maximum expected value Possible failure on the measuring circuit Solutions 1 Check the...

Page 879: ...alous temperature in the battery cabinet Possible failure on the measuring circuit Solutions 1 Check the temperature on the batteries and remove the cause of the alarm if any 2 If the alarm persists contact our Technical Support Service 3 Alarm A52 UNDER VOLTAGE LOCKOUT Description The inverter is blocked because of an anomaly on the control power supply Possible causes Internal error Solutions 1 ...

Page 880: ...ter conctactor is fault This alarm is only active when the contactor is installed an anabled through eeprom manager Possible causes Aux contactor Fault Wiring circuit Fault or PCB Fault Solutions 1 Check the auxiliary contact functions check the interconnection cables or PCB 2 Contact our Technical Support Service Alarm A58 INVERTER CURRENT UNBALANCED Description The inverter s bridge currents are...

Page 881: ...S 3 Verify the battery blocks 4 Verify the status of the UPS 5 Verify the DC voltage value 6 If the alarm persists contact our Technical Support Service Alarm A62 MAINS OVERVOLTAGE Description Sudden increase of the AC input voltage fast sensor Possible causes Voltage spike on the AC mains Possible internal fault Solutions 1 Check the mains voltage 2 If the alarm persists contact our Technical Sup...

Page 882: ...3 REV B Alarm A64 ULTRA FAST GRID MONITOR Description Sudden drop of the AC input voltage fast sensor Possible causes Voltage drop on the AC mains brown out Possible internal fault Solutions 1 Check the mains voltage 2 If the alarm persists contact our Technical Support Service ...

Page 883: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMP06263 REV B 65 LANGUE FRANÇAIS ...

Page 884: ... 300 kVA BST87 KEOR HPE 400 kVA BSU14 KEOR HPE 500 kVA Documentation à mettre en réserve Ce manuel et toute autre documentation d appui technique relative au produit doivent être entreposés et rendus accessibles au personnel dans le voisinage immédiat de l UPS Informations complémentaires Dans le cas où les informations fournies dans ce manuel ne sont pas suffisamment exhaustives veuillez contacte...

Page 885: ...être strictement suivies Risque de blessure dû à une panne du dispositif Des situations potentiellement dangereuses peuvent survenir en cas de panne de l alimentation sans coupure UPS Ne pas utiliser l appareil si visiblement endommagé Faire l entretien de l appareil régulièrement pour identifier la panne possible Dommage du dispositif possible Chaque fois que le travail est effectué sur l apparei...

Page 886: ...onscient de ce fait Image 1 Schéma fonctionnel Le système d alimentation sans coupure UPS et la technologie du transistor bipolaire à porte isolée IGBT avec une fréquence élevée de commutation de façon à permettre une faible distorsion du courant réinjecté dans la ligne d alimentation ainsi qu une qualité et stabilité élevées de la tension de sortie de courant Les composantes utilisées garantissen...

Page 887: ...resseur La batterie est chargée selon la norme DIN 41773 chaque fois qu elle a été partiellement ou complètement déchargée Lorsque sa pleine capacité est restaurée elle est débranchée de la barre omnibus pour courant continu au moyen d un commutateur statique afin d économiser l énergie réduire la contrainte due à l ondulation du courant alternatif augmentant ainsi la durée de vie Ce mode de fonct...

Page 888: ...variations de charge en maintenant constante la tension continue En même temps il permet le chargement de la batterie L onduleur convertit la tension de courant continu en un courant alternatif en régime sinusoïdal avec fréquence et courant stabilisé et alimente également la charge par l intermédiaire de son commutateur statique SSI Image 2 Fonctionnement normal 3 3 2 Conversion écologique Lors du...

Page 889: ... référant à la valeur nominale Capacité perdue 10 Charge supplémentaire pendant 12 heures Capacité perdue entre 10 et 20 Charge supplémentaire pendant 48 heures Capacité perdue 20 Charge supplémentaire pendant 96 heures Ces valeurs se conforment aux recommandations des fabricants de la batterie principale Définir la bonne capacité de la batterie Le panneau frontal de l UPS permet de régler les par...

Page 890: ...a partiellement restauré sa capacité Le redémarrage du système à partir de la condition d interruption peut être personnalisé selon les exigences de l installation en trois modes différents Les charges de dérivation sont fournies dès que la ligne de dérivation est disponible configuration à l usine Les charges de l onduleur sont fournies par l onduleur même si la ligne de dérivation est disponible...

Page 891: ...ectrique adaptée en branchant les contacts auxiliaires des sectionneurs de dérivation manuelle et de sortie aux bornes dédiées à bord de l UPS Ceci permettra à la logique de contrôle d acquérir l état des commutateurs et de guider l opérateur lors des procédures de démarrage et de dérivation manuelle Pour plus de renseignements reportez vous à la partie Installation et démarrage Lors de la dérivat...

Page 892: ...ontrôle de l unité d alimentation sans coupure UPS s adresse au personnel autorisé seulement Nous recommandons de vérifier la formation du personnel chargé de l utilisation et de la maintenance du système 3 4 1 Isolateurs Les sectionneurs prévus sur l unité d alimentation sans coupure UPS sont utilisés pour isoler les composantes d alimentation du dispositif à partir de la ligne d alimentation en ...

Page 893: ... a aucun danger pour les personnes et les choses 3 4 3 Sélecteur normal de dérivation Il est utilisé au cours de la procédure de dérivation manuelle quand il est nécessaire d isoler l unité d alimentation sans coupure UPS pour entretien ou réparation Suivre les procédures contenues dans le manuel Le sélecteur normal de dérivation ne doit être utilisé que conformément aux procédures spécifiées dans...

Page 894: ...ge d Accueil 4 1 ICÔNES Le parcours des pages de l écran tactile est possible par le biais de sept icônes fournies à droite l icône avec les flèches haut bas contrôle la communication d affichage Description de l icône Icône Fonctions attribuées Accueil Retourne à la page d Accueil Mesures Entre dans la section Mesures Une page de la section Mesures est actuellement affichée Contrôles Entre dans l...

Page 895: ...ction Info Une page de la section Info est actuellement affichée Précédent Recule d une page Communication Contrôle la communication entre le panneau et les composants électroniques de l UPS Communication OK Contrôle la communication entre le panneau et les composants électroniques de l UPS Communication Ko en cas d erreur de communication entre l écran tactile et la logique de commande de l UPS 4...

Page 896: ...ions du panneau de commande de la page d Accueil directement 5 1 AFFICHAGE DES MESURES Appuyer sur un objet spécifique donne accès à l affichage des mesures de cette section spécifique de l UPS Image 9 Panneau de commande UPS page d Accueil Par exemple en cliquant sur l objet indiqué dans la figure ci dessus vous accédez à l écran Onduleur de mesures visible ci dessous Image 10 Page des mesures de...

Page 897: ...esures disponibles est donnée ci dessous Sous page Données affichées Exactitude ENTRÉE Tension d entrée du redresseur 1 1 V Courant d entrée du redresseur 1 A Fréquence 0 1 Hz Puissance d entrée 1 kVA SORTIE Tension 1 1 V Courant 1 A Pourcentage de charge 1 Puissance active 1 kW Puissance apparente 1 kVA Fréquence 0 1 Hz DÉRIVATION Tension 1 1 V Fréquence 0 1 Hz ONDULEUR Tension 1 1 V Fréquence 0 ...

Page 898: ... Exactitude BATTERIE Tension et courant 1 V 1 A Capacité nominale 1 Ah Autonomie résiduelle 1 min 1 TEMPÉRATURE 2 Batterie 0 1 C UPS 0 1 C 1 Les mesures de la tension sont toujours données en référence à la valeur phase à neutre 2 Les températures sont affichées seulement si la sonde correspondante est installée ...

Page 899: ...ment de l UPS ou soit le journal des historiques Image 12 Section ALARMES 5 2 1 Affichage de l état de fonctionnement Appuyez sur état UPS pour afficher l état de fonctionnement de l UPS qui comprend des alarmes actives possibles Image 13 Section ALARMES L état du système actuel est indiqué si la liste est plus longue que la capacité de la page 8 lignes elle peut être défilée en faisant glisser un...

Page 900: ...Le premier événement montré est le dernier dans l ordre chronologique un nouvel événement fait changer automatiquement de position tous les autres événements en effaçant l évènement le plus ancien Chaque ligne montre le numéro de l événement position dans la liste le code d alarme et la date et l heure un astérisque indique la réinitialisation automatique de l alarme Le nombre maximal d événements...

Page 901: ...z la page suivante Image 16 Enregistrer le journal des historiques L écran tactile reconnaît automatiquement quand un support de mémoire externe clé USB ou carte SD est inséré e et change la couleur de l icône correspondante de gris désactivé à bleu activé Le fichier texte sera sauvegardé contenant les mêmes informations disponibles sur les pages Historique accompagnées de la description de chaque...

Page 902: ...RANT BATTERIE CRETE MAX A16 BYPASS CHARGE A50 LIMITATION COURANT ONDULEUR A17 RETRANSFERT BLOQUÉ A51 TEMPERATURE BATTERIE A18 MBCB FERMÉ MBCB BUS FERMÉ A52 DEFAUT TENSION MINI A19 OCB OUVERT A53 DÉFAUT LOGICIEL A20 SURCHAGE EN SORTIE A54 DÉFAUT CAN BUS A21 IMAGE THERMIQUE A55 CABLE PARALLELE DECONNECTE A22 BYPASS SWITCH A56 TENS ALIM DESEQUILIBREES A23 ARRÊT D URGENCE A57 DEFAUT CONTACTEUR ONDULEU...

Page 903: ...ES ÉTATS est entré Les alarmes s affichent quand ils sont présents et doivent être interrompues avec l avertisseur Les alarmes restent affichées quand ils sont présents et sont automatiquement enregistrés dans le journal des événements avec la date et l heure Description des alarmes et états Pour une description plus détaillée des alarmes et des états consultez la section Pannes et alarmes du prés...

Page 904: ... de l icône Controles affichera la page d accès à la section de configuration protégée par mot de passe Image 17 Mot de passe d accès à la section Controles Image 18 Section Controles Accès protégé par mot de passe Le menu CONTROLES est protégé par un mot de passe défini par l usine afin de prévenir l accès au personnel non autorisé ...

Page 905: ...ance puis l unité d alimentation sans coupure ASI reprendra son fonctionnement Les conditions de défaillance qui imposent un réarmement manuel sont A10 BATTERIES DÉFECTUEUSES A12 ARRET PAR COURT CIRCUIT A29 MAINTENANCE À PRÉVOIR A33 UTIL A COMPOS CONTINUE A40 TENSION VDC MIN A44 DÉSATURATION ONDULEUR A50 LIMITATION COURANT ONDULEUR A52 DEFAUT TENSION MINI A55 CABLE PARALLELE DECONNECTE Redémarrage...

Page 906: ...onctionnement en Fréquence de tension indépendante VFI Voltage Frequency Independent double conversion en ligne à la Fréquence de tension dépendante VFD Voltage Frequency Dependent Dans ce mode la charge est directement fournie par le CA et l onduleur est activé prêt à prendre la relève en cas d anomalies des réseaux de distribution Le transfert se produit en un temps maximal de 10 ms La stabilité...

Page 907: ... OPERATIONS La pression de l icône Reglages affichera la page d accès à la section de configuration protégée par mot de passe Image 19 Mot de passe d accès à la section Reglages Image 20 Section Reglages Accès protégé par mot de passe Le menu CONTROLES est protégé par un mot de passe défini par l usine afin de ...

Page 908: ...Configuration de la date et de l heure La date et l heure peuvent être réglées au moyen du menu HORLOGE Image 21 Configuration manuelle de l horloge Configuration de la date et de l heure courantes correctement Le réglage exact de la date et de l heure est essentiel pour l enregistrement du journal des événements Le système permet également de configurer un serveur NTP pour la synchronisation de l...

Page 909: ...nfigurés via les pages de Configuration réseau dans la section Reglages Si le serveur ne répond pas ou que la connexion LAN est manquante le message ERREUR NTP s affichera 5 4 2 Configuration de la langue d affichage L image suivante montre les langues qui peuvent être définies Image 23 Configuration de la langue La sélection de la langue est effectuée en appuyant sur l un des drapeaux ...

Page 910: ...ATION DE BATTERIE permet de configurer ces données Chaque paramètre configurable simple est accessible via la page suivante Image 24 Configuration des paramètres de la batterie Les différentes pages de configuration des paramètres sont semblables les unes aux autres et nécessitent que l opérateur saisit et confirme la valeur la page de configuration de la capacité de la batterie est indiquée ci de...

Page 911: ...es de l interface utilisateur RS485 Les paramètres concernant la communication au moyen de l interface RS485 peuvent être configurés dans la section MODBUS RS485 Cette section permet de définir l adresse ModBus le mode de communication et la vitesse de transmission des données 5 4 6 Configuration des paramètres réseau d affichage La section CONFIG RÉSEAU permet de configurer les paramètres se rapp...

Page 912: ...ation du DHCP Image 27 Configuration des paramètres LAN 5 4 6 2 Configuration des paramètres NTP Les paramètres du service NTP configurables sont les suivants Adresse du serveur NTP primaire Adresse du serveur NTP secondarie L activation désactivation NTP s effectue dans le menu RÉGLAGES HORLOGE Image 28 Configuration des paramètres NTP ...

Page 913: ...ramètre s affichera sur la chaîne modifiable en haut de la page avec un clavier Image 29 Modification des paramètres numériques Les champs liés aux serveurs NTP peuvent être soit numériques adresse IP du serveur distant ou alphanumériques quand le serveur distant peut être atteint via une adresse Web Auquel cas le clavier qui apparaîtra dans la page est complet Image 30 Modification des paramètres...

Page 914: ...n sans coupure ASI appuyez sur l icône correspondante pour ouvrir la page principale Image 31 Section INFO Toutes les données affichées dans les diverses sections sont définies lors de l essai en usine via un logiciel d interface spécifique et ne peuvent être modifiées par quiconque sauf le personnel autorisé par le fabricant 5 5 1 Informations sur le dispositif Image 32 Informations sur le dispos...

Page 915: ... de l heure du système actuel 5 5 2 Informations parallèles La page contenant les informations sur le parallèle est seulement activée si l alimentation sans coupure ASI est parallèle aux autres ASI Image 33 Informations parallèles 5 5 2 1 Indice parallèle Le premier chiffre identifie la position de cette alimentation sans coupure ASI spécifique dans le système parallèle Le second chiffre représent...

Page 916: ...demander la présence de toutes les unités d alimentation sans coupure ASI pour alimenter la charge REDONDANT x signifie que le système est redondant et l index de redondance est indiqué par le numéro x Par exemple dans un système composé de 3 unités d alimentation sans coupure ASI REDONDANT 2 signifie que seulement une des unités d alimentation sans coupure est suffisante pour alimenter la charge ...

Page 917: ...sinon il y aura un conflit sur le bus de communication des données 5 5 3 3 État du système surveillance du bus de communication Ce champ donne une indication générale concernant la communication entre les unités de l alimentation sans coupure ASI composant le système Les numéros représentent les unités d alimentation sans coupure ASI individuelles Les lettres M et S sont pour MAÎTRE et ESCLAVE res...

Page 918: ...re de messages reçus et pourcentage de précision de réception en ce qui concerne l état du système Les messages sont échangés entre toutes les unités d alimentation sans coupure ASI donc le nombre va augmenter sur chacun d eux 5 5 4 Informations de communication RS485 La section MODBUS RS485 fournit des informations sur les paramètres du port de communication concernant l adresse ModBus attribuée ...

Page 919: ...larme sont affichés Risque de blessure dû à un choc électrique Avant d effectuer toute opération sur l ASI s assurer que toutes les précautions de sécurité soient respectées Tout travail sur l unité doit être effectué par un personnel qualifié Les composantes internes ne peuvent être accessibles qu après avoir débranché l appareil à partir de sources d alimentation Toujours utiliser les dispositif...

Page 920: ...t prêt à alimenter la charge État S4 ONDULEUR CHARGE Description L onduleur alimente la charge Condition de fonctionnem ent La charge est alimentée par le commutateur d onduleur statique État S5 OND BYPASS SYNCHRO Description L onduleur est synchronisé avec la dérivation Condition de fonctionnem ent La synchronisation entre l onduleur et la dérivation est verrouillée et le commutateur statique peu...

Page 921: ... Condition de fonctionnem ent L interrupteur statique de la batterie est fermé et la batterie se trouve dans la deuxième et dernière phase du mode de charge I U DIN 41773 avec une tension constante et un courant décroissant Status S16 TRANSFERT SUR BY PASS VR2max Description Commutation avec tension de dérivation élevée Operating condition Commutation de l onduleur au bypass avec coupure de l ondu...

Page 922: ...e phase 2 Si l alarme persiste contacter notre service d assistance technique Alarme A3 REDRESSEUR À L ÂRRET Description Le redresseur a été temporairement déconnecté et l onduleur est alimenté par la batterie Causes possibles L instabilité de la fréquence ou de la tension de la ligne à courant alternatif Panne possible sur le circuit de contrôle du redresseur Solutions 1 Vérifier les paramètres d...

Page 923: ...uses possibles Un test de la batterie a été démarré automatiquement si activé ou manuellement par l utilisateur Solutions 1 Attendre la fin du test et vérifier les éventuels défauts de batterie Alarme A7 BCB OUVERT Description Le sectionneur de la batterie est ouvert Causes possibles Sectionneur de la batterie ouvert Solutions 1 Vérifier l état du sectionneur de la batterie 2 Vérifier le fonctionn...

Page 924: ...alarme persiste contacter notre service d assistance technique Alarme A11 COURT CIRCUIT Description Le capteur de courant a détecté un court circuit à la sortie Causes possibles Problème de charge Mesure de défaillance du circuit Solutions 1 Vérifier les charges connectées à la sortie de l unité d alimentation sans coupure ASI 2 Si l alarme persiste contacter notre service d assistance technique A...

Page 925: ...Solutions 1 Vérifier la rotation de phase 2 Si l alarme persiste contacter notre service d assistance technique Alarme A15 DÉFAUT BYPASS Description La tension ou la fréquence de la ligne de dérivation est hors tolérance Causes possibles Panne ou instabilité de la ligne de dérivation Mauvaise rotation de phase Solutions 1 Vérifier les connexions au réseau 2 Vérifier la stabilité de la tension d al...

Page 926: ... dérivation manuel 2 Vérifier le fonctionnement du contact auxiliaire du sectionneur 3 Si l alarme persiste contacter notre service d assistance technique Alarme A19 OCB OUVERT Description Le sectionneur de sortie est ouvert Causes possibles Isolateur de sortie ouvert Solutions 1 Vérifier l état du sectionneur de sortie 2 Vérifier le fonctionnement du contact auxiliaire du sectionneur 3 Si l alarm...

Page 927: ...n Le système est bloqué en raison de l activation de la touche de mise hors tension d urgence Causes possibles Activation du bouton de mise hors tension d urgence local ou distant Solutions 1 Relâcher le bouton d arrêt d urgence et réinitialiser l alarme 2 Si l alarme persiste contacter notre service d assistance technique Alarme A24 SURCHAUFFE Description Température élevée du dissipateur de chal...

Page 928: ...erreur dans les paramètres mémorisés dans EEPROM Causes possibles Mauvais paramètres entrés lors de la programmation Solutions 1 Contacter notre service de support technique Alarm A28 ARRET CRITIQUE Description Une alarme a été activée ce qui provoque la fermeture d une partie de l unité d alimentation sans coupure ASI redresseur onduleur commutateur statique Possible causes Panne du système Solut...

Page 929: ...nce sur le circuit de mesure Cause possible de condensateurs à courant continu Solutions 1 Réinitialiser le système 2 Si l alarme persiste contacter notre service d assistance technique Alarme A34 APPEL SERVICE APRÈS VENTE Description Une vérification de l unité d alimentation sans coupure ASI est nécessaire Causes possibles Possible défaillance de l unité d alimentation sans coupure ASI Solutions...

Page 930: ...e fonctionnement du contact auxiliaire du sectionneur 3 Si l alarme persiste contactez notre Service d assistance technique Alarme A38 ONDULEUR CHARGE Description La charge est alimentée par l onduleur Cette alarme est active pour les systèmes d unité d alimentation sans coupure ASI en mode ÉCO où l approvisionnement préférentiel est de la ligne de dérivation Causes possibles Passage temporaire du...

Page 931: ... continu hors des limites et a éteint l onduleur le booster et a déconnecté la batterie de l ASI Solutions 1 Vérifiez qu il n y a pas de court circuit dans le bus DC 2 Vérifier le capteur actuel de la batterie 3 Vérifier les blocs de la batterie 4 Si l alarme persiste contactez notre Service d assistance technique Alarme A42 PERTE REDONDANCE ALIM Description Défaillance de l alimentation électriqu...

Page 932: ...ifier le système de conditionnement d air si présent 4 Si l alarme persiste contacter notre service d assistance technique Alarme A46 PERTE DE REDONDANCE Description Cette alarme n est active que sur les systèmes PARALLÈLES La continuité n est pas assurée dans le cas d un défaut sur l une des unités d alimentation sans coupure ASI Causes possibles La charge totale est supérieure à la valeur maxima...

Page 933: ...ue la sonde de température est installée et activée sur la batterie Causes possibles Température anormale dans la batterie du cabinet Éventuelle défaillance sur le circuit de mesure Solutions 1 Vérifier la température sur les batteries et éliminer la cause de l alarme le cas échéant 2 Si l alarme persiste contacter notre service d assistance technique Alarme A52 DEFAUT TENSION MINI Description L o...

Page 934: ...ion BT ou de moyenne tension MT Défaut du circuit de mesure Solutions 1 Vérifier la tension d entrée 2 Contacter notre service de support technique Alarme A57 DEFAUT CONTACTEUR ONDULEUR Description Le contacteur de l onduleur est défectueux Cette alarme n est active que lorsque le contacteur est installé et activé via eeprom manager Causes possibles Défaillance du contacteur auxiliaire Défaillance...

Page 935: ...e 2 Si l alarme persiste contactez notre Service d assistance technique Alarme A61 TENSION VDC MAX Description L ASI s est arrêté en raison du fonctionnement du capteur de protection comme résultat de fortes variations soudaines de tension DC au dessus des limites Causes possibles Problème de tension bus DC Solutions 1 Vérifiez qu il n y a pas de court circuit dans le bus DC 2 Vérifiez l état de l...

Page 936: ...interne Solutions 1 S assurer que la position des dispositifs de contrôle sectionneurs sélecteurs est telle que spécifiée dans les procédures voir section Installation et démarrage 2 Si l alarme persiste contacter notre service d assistance technique Alarme A64 TRANSITOIRE TENSION RESEAU Description Détection d un abaissement rapide AC sur l entrée Causes possibles Lower Abaissement brutal du rése...

Page 937: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMP06263 REV B 119 LINGUA ITALIANA ...

Page 938: ... KEOR HPE 400 kVA BSU14 KEOR HPE 500 kVA Conservazione della documentazione Questo manuale e tutta la restante documentazione tecnica di supporto al prodotto devono essere conservati e possibilmente resi accessibili al personale nelle immediate vicinanze dell UPS Informazioni aggiuntive Nel caso le informazioni riportate nel presente manuale non fossero abbastanza esaurienti si prega di contattare...

Page 939: ...riportate nei manuali Pericolo di lesioni a seguito di guasti al dispositivo In caso di guasto dell UPS si possono creare situazioni potenzialmente pericolose Non utilizzare il dispositivo se presenta danni visibili Effettuare regolarmente interventi di manutenzione al fine di rilevare possibili anomalie Possibile danneggiamento del dispositivo Prima di qualsiasi intervento sul dispositivo aver cu...

Page 940: ...e dall UPS richiamando l attenzione dell utente Figura 1 Schema a blocchi L UPS è realizzato con tecnologia ad IGBT ad elevata frequenza di commutazione per consentire una bassa distorsione della corrente re iniettata nella rete di alimentazione e un alta qualità e stabilità della tensione di uscita La componentistica utilizzata garantisce elevata affidabilità altissima efficienza e facilità di ma...

Page 941: ...ca di controllo del raddrizzatore La batteria viene sottoposta ad un ciclo di carica in accordo alle DIN41773 ogni volta che avviene una scarica parziale o totale Al ripristino della completa capacità viene disconnessa dal bus DC per mezzo di un interruttore statico a SCR per di risparmiare energia e ridurre lo stress dovuto al ripple AC tutto al fine di aumentare la vita attesa Tale modalità oper...

Page 942: ... compensa le variazione della tensione di rete così come quelle di carico mantenendo la tensione DC costante Allo stesso tempo provvede a caricare la batteria L inverter converte la tensione DC in una sinusoide AC stabilizzata in tensione e frequenza e provvede ad alimentare il carico tramite il suo static switch SSI Figura 2 Funzionamento normale 3 3 2 Green Conversion Durante il funzionamento in...

Page 943: ...pacità persa è 10 Carica mantenimento per 12 ore Capacità persa è compresa tra il 10 e il 20 Carica mantenimento per 48 ore Capacità persa è 20 Carica mantenimento per 96 ore Tali valori sono conformi alle raccomandazioni dei principali produttori di batterie Impostare il corretto valore di capacità Il pannello frontale dell UPS permette l impostazione dei parametri di batteria inclusa la capacità...

Page 944: ...vvio dell inverter avviene quando la batteria ha ripristinato parte della sua capacità La ripartenza del sistema dalla condizione di black out può essere personalizzata sulla base delle esigenze dell impianto in tre modalità differenti Bypass i carichi vengono alimentati appena la rete di bypass è disponibile configurazione di fabbrica Inverter i carichi vengono alimentati dall inverter anche se l...

Page 945: ...lazione elettrica prestare cura al cablaggio dei contatti ausiliari degli isolatori di bypass manuale uscita e batteria che vanno collegati agli appositi morsetti sull UPS In questo modo la logica di controllo acquisisce lo stato degli interruttori per guidare l operatore durante le procedure di avvio e bypass manuale Per maggiori informazioni fare riferimento alla sezione Installazione e avviamen...

Page 946: ... comando dell UPS è destinato a personale autorizzato Si consiglia di verificare l addestramento del personale addetto all utilizzo e alla manutenzione del sistema 3 4 1 Sezionatori I sezionatori previsti sull UPS servono per isolare la parte di potenza del dispositivo dalla rete AC di alimentazione dalla batteria di accumulatori e dai carichi Presenza di tensione sui terminali I sezionatori non i...

Page 947: ...ll arresto di emergenza sono state eliminate e si è certi che non ci siano pericoli per le persone o le cose 3 4 3 Selettore Normale Bypass Viene utilizzato durante la procedura di bypass manuale quando è necessario isolare l UPS per manutenzione o riparazione Seguire le procedure riportate nel manuale Il selettore Normale Bypass deve essere manovrato solamente in accordo alle procedure riportate ...

Page 948: ...ll UPS Figura 8 Pannello frontale UPS schermata Home 4 1 ICONE Il touch screen è provvisto di 7 icone sulla parte destra dello schermo che permettono la navigazione e di un icona di controllo della comunicazione Description of the icon Icon Assigned functions Home Torna alla pagina Home Misure Entra nella sezione Misure Si è all interno della sezione Misure Controlli Entra nella sezione Controlli ...

Page 949: ... Info Entra nella sezione Info Si è all interno della sezione Info Indietro Torna indietro di una pagina Comunicazione Comunicazione Ok fra il pannello e la logica di controllo dell UPS Comunicazione Ko fra il pannello e la logica di controllo dell UPS errore di comunicazione tra touch screen e UPS 4 2 BARRA DI STATO La barra di stato in basso dà un indicazione dello stato di alimentazione del car...

Page 950: ...el pannello di controllo direttamente dalla pagina Home 5 1 VISUALIZZAZIONE DELLE MISURE Premendo su un determinato oggetto si accede alla visualizzazione delle misure di quella specifica sezione dell UPS Figura 9 Pannello frontale UPS schermata Home Per esempio cliccando sull oggetto indicato in figura sopra si accede alla schermata Misure Inverter visibile di seguito Figura 10 Misure Inverter ...

Page 951: ... di tutte le misure disponibili Sotto menu Dati visualizzati Accuratezza INGRESSO Tensione ingresso raddrizzatore 1 1 V Corrente ingresso raddrizzatore 1 A Frequenza 0 1 Hz Potenza di ingresso 1 kVA USCITA Tensione 1 1 V Corrente 1 A Percentuale di carico 1 Potenza attiva 1 kW Potenza apparente 1 kVA Frequenza 0 1 Hz BYPASS Tensione 1 1 V Frequenza 0 1 Hz INVERTER Tensione 1 1 V Frequenza 0 1 Hz A...

Page 952: ...enu Dati visualizzati Accuratezza BATTERIA Tensione e corrente 1 V 1 A Capacità nominale 1 Ah Autonomia residua 1 min 1 TEMPERATURE 2 Batteria 0 1 C UPS 0 1 C 1 Le misure di tensione sono sempre riferite tra fase e neutro 2 Le temperature sono visualizzate solo se la relativa sonda è installata ...

Page 953: ...unzionamento dell UPS o dello storico eventi Figura 12 Sezione ALLARMI 5 2 1 Visualizzazione dello stato di funzionamento Premere su Stato UPS per visualizzare lo stato di funzionamento dell UPS inclusi eventuali allarmi presenti Figura 13 Sezione ALLARMI Viene visualizzato lo stato attuale del sistema che può essere scorso con uno slide sullo schermo nel caso le righe non entrino nella prima sche...

Page 954: ...armi pagina 1 Il primo evento visualizzato è l ultimo in ordine di tempo un nuovo evento fa scorrere automaticamente gli altri di una posizione ed elimina l evento più vecchio Su ogni riga sono riportati rispettivamente il dato visualizzato al momento posizione nella lista il codice dell allarme e data e ora un asterisco indica il reset automatico dell allarme Il numero massimo di eventi visualizz...

Page 955: ...ina Figura 16 Storico allarmi salvataggio file Il touch screen riconosce automaticamente l inserimento di un supporto di memoria esterno USB stick o scheda SD e cambia il colore della rispettiva icona da grigio disabilitato a bianco abilitato Viene salvato un file di testo che riporta tutte le stesse informazioni disponibili nelle schermate integrate dalla descrizione dell evento ...

Page 956: ...ACORRENTE BATTERIA A16 BYPASS CARICO A50 SATURAZIONE CORRENTE INVERTER A17 RITRASFERIMENTO BLOCCATO A51 TEMPERATURA BATTERIA A18 MBCB CHIUSO MBCB BUS CHIUSO A52 INVERTER BLOCCATO UVL A19 OCB APERTO A53 ERRORE COMPATIBILITÀ FIRMWARE A20 SOVRACCARICO A54 ERRORE COMUNIC CAN PARALLELO A21 IMMAGINE TERMICA A55 CAVO PARALLELO DISCONNESSO A22 BYPASS SWITCH A56 TERNA SBILANCIATA A23 EPO CHIUSO A57 TELERUT...

Page 957: ...zzati sempre in ordine crescente Gli allarmi vengono mostrati quando si presentano e devono essere tacitati con il buzzer Gli allarmi restano visibili finché sono presenti e vengono registrati automaticamente nello storico eventi con data e ora Descrizione degli allarmi e degli stati Per una descrizione più approfondita degli allarmi e degli stati vedere la sezione del presente manuale Guasti e al...

Page 958: ...zo dell UPS 140 OMP06263 REV B 5 3 CONTROLLI E OPERAZIONI AVANZATE La pressione sull icona Controlli visualizza la pagina di accesso alla sezione controlli protetto da password Figura 17 Password di accesso alla sezione Controlli Figura 18 Sezione Controlli ...

Page 959: ...T è necessario per ripristinare semplicemente una segnalazione di anomalia quindi l UPS continua a funzionare Le condizioni di blocco che impongono un reset manuale sono A10 ANOMALIA BATTERIA A12 STOP TIMEOUT CORTO CIRCUITO A29 MANUTENZIONE PROGRAMMATA A33 CARICO ASIMMETRICO A40 MINIMA TENSIONE DC A44 DESATURAZIONE INVERTER A50 SATURAZIONE CORRENTE INVERTER A52 INVERTER BLOCCATO UVL A55 CAVO PARAL...

Page 960: ...al funzionamento VFI Voltage Frequency Independent on line doppia conversione a quello VFD Voltage Frequency Dependent In tale modalità il carico è alimentato direttamente dalla rete AC e l inverter è acceso pronto a subentrare in caso di anomalia della rete La commutazione avviene in un tempo massimo pari a 10 ms La stabilità delle rete AC è controllata da uno specifico algoritmo che provvede a d...

Page 961: ...UPS OMP06263 REV B 143 5 4 IMPOSTAZIONI E OPERAZIONI AVANZATE La pressione sull icona Impostazioni visualizza la pagina di accesso alla sezione impostazioni protetto da password Figura 19 Password di accesso alla sezione Impostazioni Figura 20 Sezione Impostazioni ...

Page 962: ...enzialmente pericolose per il dispositivo stesso e per le persone 5 4 1 Impostazione di data e ora La data e l ora possono essere impostate dalla pagina OROLOGIO Figura 21 Impostazione manuale orologio Impostare correttamente data e ora correnti La corretta impostazione della data e dell ora è fondamentale per la registrazione dello storico eventi Il sistema permette anche l impostazione di un ser...

Page 963: ...figurati dalla sezione Configurazione rete del menu Impostazioni Nel caso non ci sia risposta dal server oppure manchi la connessione LAN apparirà il messaggio di errore ERRORE NTP 5 4 2 Impostazione lingua del display La schermata seguente mostra i linguaggi impostabili per il display Figura 23 Impostazione lingua La selezione della lingua si effettua premendo su una delle bandiere ...

Page 964: ...zione IMPOSTAZIONI BATTERIA permette l impostazione degli stessi Si accede ai singoli parametri impostabili dalla schermata seguente Figura 24 Impostazione parametri batteria Le varie schermate di impostazione dei parametri sono simili fra loro e richiedono l inserimento dei valori e la conferma per riferimento si riporta la schermata di configurazione della capacità di batteria Figura 25 Impostaz...

Page 965: ...parametri di interfaccia utente RS485 All interno del menu MODBUS RS485 possono essere impostati i parametri relativi alla comunicazione tramite supporto RS485 La sezione consente l impostazione dell indirizzo la modalità di comunicazione e la velocità di trasmissione dati della RS485 5 4 6 Impostazione parametri di rete del touch screen Tramite la sezione CONFIGURAZIONE è possibile configurare i ...

Page 966: ...ostazione parametri LAN 5 4 6 2 Impostazione parametri NTP Per quanto riguarda il servizio NTP i parametri configurabili sono Indirizzo server NTP primario Indirizzo server NTP secondario L abilitazione disabilitazione NTP si esegue nel menu IMPOSTAZIONI OROLOGIO Figura 28 Impostazione parametri NTP ...

Page 967: ...rirà su una stringa modificabile in alto nella schermata unitamente ad un tastierino numerico Figura 29 Modifica parametri numerici I campi relativi ai server NTP possono essere numerici indirizzo IP del server remoto oppure formati da testo quando il server remoto è raggiungibile su un indirizzo web In tal caso il tastierino che compare nella schermata è di tipo completo Figura 30 Modifica parame...

Page 968: ... premere sull icona relativa per accedere alla schermata principale Figura 31 Menu INFO Tutti i dati mostrati all interno delle varie sezioni sono impostati in fabbrica tramite apposito software di interfaccia e non possono essere modificati tranne che da parte di personale autorizzato dal costruttore 5 5 1 Informazioni dispositivo Figura 32 Informazioni dispositivo ...

Page 969: ...a macchina OROLOGIO Impostazione attuale della data e ora di sistema 5 5 2 Informazioni parallelo La pagina relativa alle informazioni sul parallelo è abilitata solamente se l UPS è in parallelo con altri sistemi UPS Figura 33 Informazioni parallelo 5 5 2 1 Indice di parallelo Il primo numero identifica la posizione di quel particolare UPS nel sistema di parallelo il secondo numero rappresenta il ...

Page 970: ... il carico RIDONDANTE X significa che il sistema è ridondante e l indice di ridondanza è indicato dal numero X Per esempio in un sistema composto da 3 UPS RIDONDANTE 2 significa che uno solo degli UPS è sufficiente per alimentare il carico 5 5 2 5 Statistiche messaggi La sezione statistiche relative ai messaggi scambiati sui bus di comunicazione si compone di tre diverse parti STAT CAN SSW Numero ...

Page 971: ...a della comunicazione fra gli UPS che compongono il sistema I numeri rappresentano i singoli UPS Le lettere M e S stanno rispettivamente per MASTER e SLAVE Le parentesi intorno ad una lettera indicano che stiamo lavorando su quello specifico UPS Un eventuale punto interrogativo accanto ad un numero indica che quell UPS non sta comunicando sul bus dati 5 5 3 4 Tipo di parallelo La stringa può assum...

Page 972: ...i il numero incrementa su tutti 5 5 4 Informazioni sulla comunicazione RS485 Il menu MODBUS RS485 fornisce informazioni sull impostazione della porta di comunicazione relativamente all indirizzo assegnato alla modalità di comunicazione e alla velocità di trasmissione dati 5 5 5 Versioni firmware Figura 36 Versioni firmware La seconda pagina delle informazioni relative alle versioni firmware instal...

Page 973: ... una breve descrizione dello stesso Pericolo di lesioni a seguito shock elettrico Prima di effettuare qualsiasi intervento sull UPS aver cura di rispettare tutte le indicazioni relative alla sicurezza tutti i lavori sull apparato devono essere svolti da personale qualificato accedere ai componenti interni solo dopo aver disconnesso il dispositivo dalle sorgenti di alimentazione utilizzare sempre i...

Page 974: ...per erogare alimentare il carico Stato S4 INVERTER CARICO Descrizione L inverter alimenta il carico Condizione operativa Il carico è alimentato attraverso l interruttore statico di inverter Stato S5 INVERTER BYPASS SINCRONIZZATI Descrizione L inverter è sincronizzato con il bypass Condizione operativa Il sincronismo fra inverter e bypass è agganciato e l interruttore statico può effettuare commuta...

Page 975: ...vata Condizione operativa L interruttore statico di batteria è chiuso e la batteria è nella seconda e finale fase di carica I U DIN 41773 con tensione costante e corrente decrescente Stato S16 COMMUTAZIONE CON BYP ALTO Descrizione Commutazione con tensione di bypass alta Condizione operativa Commutazione da inverter a bypass con spengimento inverter causato dalla tensione di bypass maggiore o ugua...

Page 976: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 158 OMP06263 REV B ...

Page 977: ...erificare il senso ciclico delle fasi 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A3 RADDRIZZATORE SPENTO Descrizione Il raddrizzatore è stato momentaneamente arrestato e l inverter viene alimentato dalla batteria Possibili cause Instabilità della tensione o della frequenza della rete AC Possibile guasto del circuito di controllo del raddrizzatore Soluzioni 1 Verif...

Page 978: ...atteria Possibili cause E stato avviato un test di batteria automaticamente se impostato oppure manualmente dall operatore Soluzioni 1 Attendere la fine del test e verificare eventuali anomalie della batteria Allarme A7 BCB APERTO Descrizione Il sezionatore di batteria è aperto Possibili cause Sezionatore di batteria aperto Soluzioni 1 Verificare lo stato del sezionatore di batteria 2 Verificare l...

Page 979: ...ia 2 Resettare il sistema 3 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A11 CORTO CIRCUITO Descrizione Il sensore di corrente ha rilevato un corto circuito in uscita Possibili cause Problema sui carichi Guasto del circuito di misura Soluzioni 1 Verificare i carichi connessi all uscita dell UPS 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allar...

Page 980: ...ficare il senso ciclico delle fasi 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A15 BYPASS NON DISPONIBILE Descrizione La tensione o la frequenza della rete di bypass sono fuori dal range di tolleranza Possibili cause Instabilità o mancanza della rete di bypass Errato senso ciclico delle fasi Soluzioni 1 Controllare i collegamenti di connessione alla rete 2 Verifica...

Page 981: ...tore di bypass manuale 2 Verificare la funzionalità del contatto ausiliario del sezionatore 3 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A19 OCB APERTO Descrizione Il sezionatore di uscita è aperto Possibili cause Sezionatore di uscita aperto Soluzioni 1 Verificare lo stato del sezionatore di uscita 2 Verificare la funzionalità del contatto ausiliario del sezionator...

Page 982: ...sistenza Tecnica Allarme A23 EPO CHIUSO Descrizione Il sistema è bloccato in seguito all azionamento del pulsante di arresto di emergenza Possibili cause Azionamento del pulsante di arresto di emergenza locale o remoto Soluzioni 1 Sbloccare l arresto di emergenza e resettare l allarme 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A24 ALTA TEMPERATURA Descrizione Alta...

Page 983: ...lore ha rilevato un errore nei parametri memorizzati in EEPROM Possibili cause Inserimento di parametri errati durante la programmazione Soluzioni 1 Contattare il servizio di Assistenza Tecnica Allarme A28 STOP CRITICO Descrizione E presente un allarme che causa l arresto di una parte dell UPS raddrizzatore inverter interruttore statico Possibili cause Guasto del sistema Soluzioni 1 Verificare qua...

Page 984: ...oluzioni 1 Sbloccare l arresto di emergenza e resettare l allarme 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A33 CARICO ASIMMETRICO Descrizione Le tensioni misurate sui condensatori DC positiva e negativa verso punto centrale sono diverse Possibili cause Possibile guasto del circuito di misura Possibile anomalia dei condensatori DC Soluzioni 1 Resettare il sistema...

Page 985: ...ia batteria Soluzioni 1 Verificare la batteria 2 Resettare il sistema 3 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A37 OCBD APERTO Descrizione Il sezionatore di distribuzione di uscita è aperto Solo su sistemi con Bypass Centralizzato Possibili cause Sezionatore di distribuzione di uscita aperto Soluzioni 1 Verificare lo stato del sezionatore di distribuzione di usc...

Page 986: ... siano cortocircuiti nel bus DC 2 Verificare lo stato dell UPS 3 Verificare i blocchi della batteria 4 Verificare il valore della tensione DC 5 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A41 MASSIMA CORRENTE DC Descrizione La corrente continua supera i limiti Possibili cause L UPS ha rilevato la corrente continua fuori dai limiti e ha spento l inverter il booster e ...

Page 987: ...il servizio di Assistenza Tecnica Allarme A45 ALTA TEMPERATURA SSW Descrizione Alta temperatura del dissipatore di calore del ponte interruttore statico Possibili cause Guasto dei ventilatori di raffreddamento del dissipatore Temperatura dell ambiente o dell aria di raffreddamento troppo elevata Soluzioni 1 Controllare il funzionamento dei ventilatori 2 Pulire le griglie di aerazione e gli eventua...

Page 988: ...li cause Possibile problema al carico Possibile guasto del circuito di misura Soluzioni 1 Controllare i carichi collegati all uscita dell UPS 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A51 TEMPERATURA BATTERIA Descrizione La temperatura della batteria è fuori dai limiti di tolleranza Allarme attivo solo se è installata e abilitata la sonda di temperatura sulla bat...

Page 989: ...municazione del cavo parallelo Possibili cause Cavo di parallelo disconnesso o danneggiato Soluzioni 1 Controllare la connessione del cavo 2 Contattare il servizio di Assistenza Tecnica Allarme A56 TERNA SBILANCIATA Descrizione Terna d ingresso raddrizzatore sbilanciata Possibili cause La terna delle tensioni d ingresso raddrizzatore sono sbilanciate Problema sulla scheda di misura Soluzioni 1 Con...

Page 990: ...ervizio di Assistenza Tecnica Allarme A60 SENSORE DI USCITA Descrizione Il sensore della tensione di uscita ha rilevato una variazione della tensione superiore o inferiore ai limiti Possibili cause Problema di feedback sulla tensione di uscita Soluzioni 1 Ripristinare il sistema 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A61 MASSIMA TENSIONE DC Descrizione L UPS s...

Page 991: ...rretto svolgimento della sequenza Possibili cause Organi di manovra in posizione errata o manovrati in maniera non corretta Possibile guasto interno Soluzioni 1 Verificare che la posizione degli organi di manovra sezionatori selettori sia come specificato nelle procedure vedi sezione Installazione ed avviamento 2 Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A64 UFG MO...

Page 992: ...UPS OPERATING MANUAL MANUEL DE FONCTIONNEMENT DE L ASI MANUALE OPERATIVO UPS KEOR HPE 60 80 kVA ...

Page 993: ...plémentaires peuvent être nécessaires pour éviter les perturbations Catégorie ASI C3 conformément á la norme IEC 62040 2 Questo prodotto è destinato ad applicazioni commerciali e industriali del secondo ambiente durante l installazione può essere necessario introdurre alcune limitazioni ed adottare misure aggiuntive per prevenire i disturbi Classe UPS C3 in accordo alla norma CEI 62040 2 ELECTROMA...

Page 994: ......

Page 995: ...L MANUEL DE FONCTIONNEMENT DE L ASI MANUALE OPERATIVO UPS Index of sections Indice delle sezioni Code Codice 1 WARNINGS AND GENERAL INFORMATION AVERTISSEMENTS ET INFORMATIONS GÉNÉRALES AVVERTENZE E INFORMAZIONI GENERALI OMB81275 2 INSTALLATION AND START UP INSTALLATION ET DÉMARRAGE DE L ASI INSTALLAZIONE ED AVVIAMENTO OMW07096 3 UPS USER MANUAL Manuel de l utilisateur de l ASI UTILIZZO DELL UPS OM...

Page 996: ......

Page 997: ...NÉRALES AVVERTENZE E INFORMAZIONI GENERALI Index Sommaire Indice ENGLISH LANGUAGE 3 1 CONVENTIONS USED 4 2 DOCUMENTATION NOTES 5 3 USAGE OF LION BATTERY FOR ENERGY STORAGE 6 4 FACTORY WARRANTY 6 5 LIMITATION OF LIABILITY 8 LANGUE FRANÇAIS 9 1 CONVENTIONS UTILISEES 10 2 REMARQUES RELATIVES A LA DOCUMENTATION 11 3 UTILISATION D UN SYSTEME DE STOCKAGE D ENERGIE LION12 4 GARANTIE USINE 12 5 LIMITATION...

Page 998: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali 2 OMB81275 REV D ...

Page 999: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali OMB81275 REV D 3 ENGLISH LANGUAGE ...

Page 1000: ...n so as to minimize the risks to persons and property HAZARD HAZARD statements contain characteristics and basic instructions for the safety of persons Non compliance with such indications may cause serious injury or death WARNING WARNING statements contain characteristics and basic instructions for the safety of persons Non compliance with such indications may cause injury CAUTION CAUTION stateme...

Page 1001: ...is manual and any other supporting technical documentation relating to the product must be stored and made accessible to personnel in the immediate vicinity of the UPS Further information In the event that the information provided in this manual is not sufficiently exhaustive please contact the manufacturer of the device whose details are available in the Contacts section ...

Page 1002: ...for on site repairs as well as costs for the customer s own employees will not be covered by the factory warranty and will be charged to the end customer c In case of service performed following a call made by mistake or in case our technicians incur extra time and or costs due to the site inaccessibility or due to work interruptions required by the customer such costs will be invoiced in accordan...

Page 1003: ...e air conditioning system etc Non compliance with applicable safety standards Force majeure e g lightning surges natural disasters fire acts of war riots etc Fall or displacement due to incorrect installation Ordinary wear caused by proper and continuous use of the device Usage with a LION battery energy storage system not approved by Legrand and not commissioned by Legrand Technical service b Pro...

Page 1004: ...nsible for possible damage arising from improper erroneous or unreasonable usage Legrand assumes responsibility for the equipment in its original configuration Any intervention that alters the structure or the operating cycle of the equipment must be carried out and authorized directly by Legrand Legrand will not be held responsible for the consequences arising from the use of non original spare p...

Page 1005: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali OMB81275 REV D 9 LANGUE FRANÇAIS ...

Page 1006: ... Les indications DANGER contiennent des caractéristiques et des instructions de base destinées à assurer la sécurité des personnes Le non respect de ces indications peut entraîner des blessures graves voire la mort AVERTISSEMENT Les indications AVERTISSEMENT contiennent des caractéristiques et des instructions de base destinées à assurer la sécurité des personnes Le non respect de ces indications ...

Page 1007: ...mentation Ce manuel ainsi que les autres documentations techniques relatives à ce produit doivent être stockés et mis à disposition du personnel à proximité immédiate de l UPS Autres informations Si les informations fournies dans le présent manuel ne sont pas suffisamment complètes veuillez contacter le fabricant de l appareil dont les coordonnées sont indiquées dans la section Contacts ...

Page 1008: ...and dans le cas de réparations sur site ainsi que les frais encourus par les propres employés du client ne sont pas couverts par la garantie usine et seront facturés au client final c Si une opération de maintenance est réalisée suite à une demande effectuée par erreur ou si nos techniciens interviennent plus longtemps que prévu et ou encourent des frais supplémentaires en raison de l inaccessibil...

Page 1009: ... vigueur D un événement de force majeure par ex orage surtensions catastrophe naturelle incendie guerre émeute etc D une chute ou d un déplacement dû à une installation incorrecte De l usure ordinaire résultant de l utilisation correcte et continue de l appareil Utilisation avec un système de stockage d énergie LION non approuvé et non mis en service par le Service technique Legrand b Les disposit...

Page 1010: ...tenu responsable des éventuels dommages résultant d une utilisation inappropriée incorrecte ou déraisonnable Legrand est responsable de l équipement dans sa configuration d origine Toute intervention modifiant la structure ou le cycle de fonctionnement de l équipement devra être réalisée et autorisée directement par Legrand Legrand ne pourra être tenue responsable des conséquences résultant de l u...

Page 1011: ...Warnings and general information Avertissements et informations générales Avvertenze e informazioni generali OMB81275 REV D 15 LINGUA ITALIANA ...

Page 1012: ...imizzare i rischi per persone e cose PERICOLO Le indicazioni di PERICOLO riportano caratteristiche e istruzioni fondamentali per la sicurezza delle persone L inosservanza di tali indicazioni può causare lesioni gravi o morte AVVERTIMENTO Le indicazioni di AVVERTIMENTO riportano caratteristiche e istruzioni fondamentali per la sicurezza delle persone L inosservanza di tali indicazioni può causare l...

Page 1013: ...nuale e tutta la restante documentazione tecnica di supporto al prodotto devono essere conservati e possibilmente resi accessibili al personale nelle immediate vicinanze dell UPS Informazioni aggiuntive Nel caso le informazioni riportate nel presente manuale non fossero abbastanza esaurienti si prega di contattare il costruttore del dispositivo i cui dettagli sono disponibili alla sezione Contatti...

Page 1014: ...istenza della Legrand per riparazioni da effettuare sul posto nonché costi per i dipendenti stessi del cliente non saranno coperti dalla garanzia di fabbrica e saranno riaddebitati al cliente finale c In caso di intervento in seguito ad una chiamata fatta per errore o nell eventualità in cui i nostri tecnici dovessero incorrere in tempo e o spese aggiuntive a causa di inaccessibilità del sito o so...

Page 1015: ...to rispetto delle norme di sicurezza pertinenti forza maggiore per es fulmini sovratensioni calamità naturali incendi atti di guerra sommosse etc cadute o spostamenti dovuti ad installazione non corretta normale usura causata da un uso proprio e continuativo dell apparecchio Utilizzo con un sistema di accumulo energia con batterie al LITIO non approvato da Legrand e non commissionato dal servizio ...

Page 1016: ...onsiderato responsabile per eventuali danni causati da usi impropri erronei ed irragionevoli Legrand si ritiene responsabile della macchina nella sua configurazione originale Qualsiasi intervento che alteri la struttura o il ciclo di funzionamento della macchina deve essere eseguito ed autorizzato direttamente da Legrand Legrand non si ritiene responsabile delle conseguenze derivanti dall utilizzo...

Page 1017: ...MW07096 REV E 1 INSTALLATION AND START UP OF KEOR HPE UPS 60 80 KVA INSTALLATION ET DÉMARRAGE DE L ASI KEOR HPE 60 80 KVA INSTALLAZIONE E AVVIAMENTO UPS KEOR HPE 60 80 KVA Rev Descrizione Description Data Date Emesso Issued Approvato Approved Lingua Language Pagina Page di Pag of Pag E VR72 2020 08 06 2020 R Soldani F Berti E F I 1 209 Codice Code OMW07096 ...

Page 1018: ...6 Operation 20 2 3 7 Maintenance 21 2 3 8 Storage 22 2 4 ENVIRONMENTAL PROTECTION 22 2 4 1 ISO 14001 certification 22 2 4 2 Recycling of packing materials 22 2 4 3 Device disposal 22 3 INSTALLATION 23 3 1 RECEIPT OF THE UPS 23 3 1 1 Storage 23 3 2 HANDLING OF THE UPS 24 3 3 POSITIONING AND INSTALLATION 25 3 3 1 Base plan static load and weights 26 3 3 2 Overall dimensions clearances and ventilatio...

Page 1019: ...ontact 66 4 7 2 Diesel Generator auxiliary contact 66 4 7 3 Backfeed 66 4 8 PROVISION FOR COLD START FUNCTION 66 4 9 INTERFACES AND EXTERNAL CONNECTIONS 67 4 10 RELAY CARD CONNECTION 68 4 11 CONNEXION DE LA EXT INP 69 5 STARTUP AND SHUTDOWN 70 5 1 PRELIMINARY CHECKS 70 5 2 START UP PROCEDURE 71 5 3 BASIC TROUBLESHOOTING 73 5 4 SHUT DOWN PROCEDURE 73 5 5 SWITCHING PROCEDURE TO MANUAL BYPASS 74 5 6 ...

Page 1020: ... DES BATTERIES 96 4 RACCORDEMENT ELECTRIQUE 97 4 1 RACCORDEMENT DES CÂBLES D ALIMENTATION 98 4 2 DISPOSITIF DE PROTECTION CONTRE LE RETOUR DE TENSION EN ENTREE BACKFEED 100 4 3 BORNIERS 102 4 4 BATTERIES 103 4 4 1 Emplacement et conexion des batteries 104 4 5 PROCÉDURE D ASSEMBLAGE BATTERIE INTERNE UPS 105 4 5 1 1 Installation batteries 9 11Ah 12V KEOR HPE 60 80kVA 105 4 5 1 2 Installation batteri...

Page 1021: ...IVO 147 2 2 DATI NOMINALI UPS 148 2 3 INDICAZIONI PARTICOLARI SULLA SICUREZZA 149 2 3 1 Avvertenze generali 149 2 3 2 Personale 149 2 3 3 Trasporto e movimentazione 149 2 3 4 Installazione 150 2 3 5 Collegamento elettrico 151 2 3 6 Funzionamento 152 2 3 7 Manutenzione 153 2 3 8 Immagazzinamento 154 2 4 TUTELA AMBIENTALE 154 2 4 1 Certificazione ISO 14001 154 2 4 2 Riciclaggio dei materiali di imba...

Page 1022: ...Ah 12V KEOR HPE 60 80kVA 172 4 5 1 2 Installazione batterie 12 14Ah 12V KEOR HPE 60 80kVA 183 4 6 INSTALLAZIONE BATTERIE ESTERNE 194 4 6 1 Connessione batterie esterne 195 4 6 1 1 Installazione batterie esterne 196 4 7 COLLEGAMENTO CAVI AUSILIARI 198 4 7 1 Contatto ausiliario sezionatore di batteria 198 4 7 2 Contatto ausiliario Generatore Diesel 198 4 7 3 BACKFEED 198 4 8 PREDISPOSIZIONE PER COLD...

Page 1023: ...rom above Level No 2 43 Picture 15 View from above Level No 2 with battery connections 43 Picture 16 View from above Level No 3 44 Picture 17 View from above Level No 3 with battery connections 44 Picture 18 View from above Level No 4 45 Picture 19 View from above Level No 4 with battery connections 45 Picture 20 View from above Level No 5 46 Picture 21 View from above Level No 5 with battery conn...

Page 1024: ...cks of 12V VRLA batteries 64 Picture 49 Cabling battery external option 65 Picture 50 Auxiliary terminals of KEOR HPE 60 80 kVA 66 Picture 51 Position of the serial interfaces of KEOR HPE 60 80 kVA 67 Picture 52 Relay card terminals 68 Picture 53 EXT INP terminals 69 Illustration 1 Plaque signalétique de l ASI KERO HPE 60 80 kVA 81 Illustration 2 Manutention de l ASI KEOR HPE 60 80 kVA 89 Illustra...

Page 1025: ...s Plateau N 1 119 Illustration 32 Vue de dessus Plateau N 1 avec connexion des batteries 119 Illustration 33 Vue de dessus Plateau N 2 120 Illustration 34 Vue de dessus Plateau N 2 avec connexion des batteries 120 Illustration 35 Vue de dessus Plateau N 3 121 Illustration 36 Vue de dessus Plateau N 3 avec connexion des batteries 121 Illustration 37 Vue de dessus Plateau N 4 122 Illustration 38 Vue...

Page 1026: ...Piano N 1 con connessioni batterie 174 Figura 14 Vista dall alto Piano N 2 175 Figura 15 Vista dall alto Piano N 2 con connessioni batterie 175 Figura 16 Vista dall alto Piano N 3 176 Figura 17 Vista dall alto Piano N 3 con connessioni batterie 176 Figura 18 Vista dall alto Piano N 4 177 Figura 19 Vista dall alto Piano N 4 con connessioni batterie 177 Figura 20 Vista dall alto piano N 5 178 Figura...

Page 1027: ...Piano N 5 con connessioni batterie 189 Figura 41 Vista dall alto piano N 6 190 Figura 42 Vista dall alto piano N 6 cassetti 16 17 190 Figura 43 Vista dall alto piano N 6 con connesioni batterie 191 Figura 44 Vista dall alto piano N 1 con connessioni batterie 192 Figura 45 Vista dall alto piano N 1 con connessioni batterie 193 Figura 46 Terminali batteria 193 Figura 47 Schema collegamento batterie ...

Page 1028: ...Installation and start up of KEOR HPE UPS 60 80 kVA Installation et démarrage de l ASI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA 12 OMW07096 REV E ENGLISH LANGUAGE ...

Page 1029: ...Installation and start up of KEOR HPE UPS 60 80 kVA Installation et démarrage de l ASI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA OMW07096 REV E 13 ...

Page 1030: ...ystems listed below BSW07 KEOR HPE 60 kVA BSX46 KEOR HPE 80 kVA Storing documentation This manual and any other supporting technical documentation relating to the product must be stored and made accessible to personnel in the immediate vicinity of the UPS Further information In the event that the information provided in this manual is not sufficiently exhaustive please contact the manufacturer of ...

Page 1031: ... to read the following manual The purpose of this manual is to give a short description of the parts composing the UPS and to guide the installer or the user through the installation of the unit in its using environment The installer or the user must read and correctly perform the instructions included in the present manual with particular reference to the requirements regarding safety in complian...

Page 1032: ...KEOR HPE UPS 60 80 kVA is provided with an identification plate containing the operation ratings The plate is fixed in the inside of the UPS door Picture 1 Rating plate of KEOR HPE 60 80 kVA Check the technical characteristics Before carrying out any installation or start up operation on the UPS make sure its technical characteristics are compatible with the AC supply line and with the output load...

Page 1033: ...regarding safety Such training and qualification shall be considered as such only when certified by the manufacturer 2 3 3 Transport and handling Avoid bending or deforming the components and altering the insulation distances while transporting and handling the product Undistributed weight The weight of the UPS is not uniformly distributed Pay attention when lifting Please inspect the device befor...

Page 1034: ...expose the device to direct sunlight or place it near a source of heat Special environmental conditions The UPS is designed for normal climatic and environmental operating conditions as defined in the technical specification altitude ambient operating temperature relative humidity and environmental transport and storage conditions It is necessary to implement specific protective measures in case o...

Page 1035: ...ication plate correspond to the AC power system and to the actual electrical consumption of all of the equipment connected Check the conformity to the Standards The UPS must be installed in compliance with the standards in force in the country of installation IT system The UPS is also designed to be connected to an IT power distribution system All the electrical connections must be carried out by ...

Page 1036: ...stallations to which the UPS systems belong must comply with all the current safety standards technical equipment and accident prevention regulations The device can be started operated and disconnected only by authorized personnel The settings can only be changed using the original interface software Injury hazard due to electric shock During operation the UPS converts power characterized by high ...

Page 1037: ...e supply sources due to the internal capacitors which discharge slowly Thus we recommend to wait at least 5 minutes before opening the device doors Injury hazard due to electric shock Any operation must be carried out only when voltage is absent and in compliance with safety directives Make sure the battery circuit breaker that may be placed near the battery has been opened Isolate the device comp...

Page 1038: ...perature variations bad ventilation conductive or radiant heat from other sources fungus insects vermin 2 4 ENVIRONMENTAL PROTECTION 2 4 1 ISO 14001 certification Legrand is particularly sensitive to the environmental impact of its products That is why the UPS has been manufactured with cutting edge eco design criteria ISO 14001 certification Special care was taken in using fully recyclable materi...

Page 1039: ...d to be returned to the manufacturer please use the original package Danger to persons due to transport damages Mechanical damage to the electrical components constitutes a serious danger to persons and property In case of doubt regarding the non integrity of the package or of the product contained therein contact the manufacturer before carrying out the installation and or the start up 3 1 1 Stor...

Page 1040: ...must always be handled in upright position During loading and unloading operations always respect the indications regarding the device barycentre marked on the package Before positioning the UPS in order to avoid risks of turnover it s recommended to move the system on the wood pallet on which the UPS is fixed Before the positioning in the final location remove the UPS from the pallet Once downloa...

Page 1041: ... the place of installation in compliance with the current legislation please refer to the Overall dimensions minimum distances from the walls and ventilation section Special environmental conditions It is necessary to implement specific protective measures in case of unusual environmental conditions harmful smoke dust abrasive dust humidity vapour salt air bad weather or dripping explosive dust an...

Page 1042: ...LATE 118 494 24 24 582 Ø 8 387 387 57 Picture 3 Base plan The supporting base of the UPS must be designed to carry the UPS weight and to ensure its steady and safe support Its carrying capacity must be adequate to the static loads indicated in the table below Power kVA 60 80 Weight w o batteries kg 225 250 Static load w o batteries kg m2 430 480 Weight with batteries kg 780 800 Static load with ba...

Page 1043: ... UPS 60 80 kVA Installation et démarrage de l ASI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA OMW07096 REV E 27 3 3 2 Overall dimensions clearances and ventilation Picture 4 Overall dimensions Picture 5 Clearances ...

Page 1044: ... the walls for all of the UPS sizes the same installation conditions apply as indicated in the table below UPS with internal batteries A mm B mm C mm E mm D mm Recommended clearances 50 1200 600 600 Minimum clearances 0 1200 600 400 E valid only with internal battery UPS with external battery cabinet A mm B mm C mm D mm Recommended clearances 50 1200 400 600 Minimum clearances 0 1200 0 400 The tab...

Page 1045: ...in snow hail etc NO Water with an origin other than rain NO Ice formation NO Classification of biological conditions EN 60721 3 3 Environmental parameter Class 3B1 3B2 3B3 Flora NO Presence of mildew fungus etc Presence of mildew fungus etc Fauna NO Presence of rodents and other animals that are harmful to products excluding termites Presence of rodents and other animals that are harmful to produc...

Page 1046: ...onitored and regulated clean spaces category X Places where atmosphere is permanently monitored X Places located in rural and urban regions where industrial activities are few and where traffic is moderate X Places located in urban regions with industrial activities and or considerable traffic X Places in proximity to industrial sources with chemical emissions X Places located in industrial instal...

Page 1047: ...allation instructions For battery installation please respect EN62040 1 strictly and follow the installation manual of the UPS To obtain the battery life indicated by the battery manufacturer the operating temperature must remain between 0 and 25 C However although the battery can operate up to 40 C there will be a significant reduction of the battery life To avoid the formation of any kind of pot...

Page 1048: ...ions in compliance with the local standards Cables must be selected bearing in mind technical financial and safety aspects The selection and the sizing of cables from a technical viewpoint depend on the voltage on the current absorbed by the UPS on the bypass line and on the batteries on the ambient temperature and on the voltage drop Finally the kind of cable laying must be taken into particular ...

Page 1049: ...onnecting the UPS to the mains 4 1CONNECTION OF THE POWER CABLES For the electric connection of the KEOR HPE UPS 60 80 kVA connect the following cables following the below indications AC power supply rectifier input AC power supply bypass input UPS output DC power supply from battery Injury hazard due to electric shock Very high voltages are present at the ends of the cables coming from the batter...

Page 1050: ...above are indicative only The cables have been designed according to the standard CEI UNEL35024 1 using the following data 70 C rated PVC copper cables ambient temperature equal to 40 C maximum length of the cables equal to 30 m voltage drop 0 5 cables laid in cavities of structures or solid bottom cable trays The given cross sections do not take into account the overload currents allowed by each ...

Page 1051: ...ercurrent protection using a MCCB equipped with a shunt trip coil and connected to UPS applying the wiring diagram principle described in Figure 6 In case of backfeed failure detected by the UPS the UPS will send a signal to trip the MCCB to isolate the UPS in order to protect the upstream distribution circuits The installer shall apply the following warning label on all primary power isolator tha...

Page 1052: ...f KEOR HPE UPS 60 80 kVA Installation et démarrage de l ASI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA 36 OMW07096 REV E Picture 6 Single Line Diagram KEOR HPE 60 80kVA with connection to external device ...

Page 1053: ...e l ASI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA OMW07096 REV E 37 4 3TERMINAL BOARDS The KEOR HPE UPS 60 80 kVA is provided with terminal boards for the connection of power cables and of auxiliary connections Picture 7 Terminal board KEOR HPE 60 80 kVA ...

Page 1054: ...cal shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply circuit Batteries installation For battery installation please respect the prescriptions of the EN62040 1 standard paragraph 7 6 To obtain the battery life indicated by the battery manufacturer the ope...

Page 1055: ...ed electrolyte is harmful to the skin and eyes It may be toxic CAUTION do not dump the exhausted batteries in the environment 4 4 1 Battery connection and positioning Battery voltage The battery installation must be performed after connecting the following conductors AC power supply rectifier input AC power supply bypass input UPS output In case of not directly supplied cabling please connect the ...

Page 1056: ...ROCEDURE 4 5 1 1 Installation of 9 11Ah 12V KEOR HPE 60 80kVA 1 Remove the six screws to open the side panels right left and access the battery trays Total shelves 6 and each one is composed of three battery drawers Pict 9 10 1a Remove carton transport protection above all battery shelves Picture 9 9 11Ah 12V battery trays side view KEOR HPE 60kVA Picture 10 9 11Ah 12V battery trays side view KEOR...

Page 1057: ...ng indications for internal battery B Follow the instructions from point 18 to point 23 of this chapter 2 Connect the 3 cables B on the battery terminal 180 186 batteries 2A Connect the 2 cables B on the battery terminal 120 124 batteries 3 Connect the 3 cables N on the battery neutral terminal 180 186 batteries 3A Connect the 2 cables N on the battery terminal 120 124 batteries 4 Connect the 3 ca...

Page 1058: ...1 insert trays no 1 2 3 in compliance with the position as demonstrated in Picture 12 NOTES On trays no 1 and no 3 check the circled jumper are not connected leave the circled jumper disconnected 6 Wire level no 1 as indicated in Picture 13 Leave the circled jumpers disconnected Figure 13 Picture 12 View from above Level No 1 Picture 13 View from above Level No 1 with battery connections ...

Page 1059: ...l no 2 insert trays no 4 5 6 in compliance with the position as demonstrated in Picture 14 NOTES On trays no 4 and no 6 check the circled jumper are not connected leave the circled jumper disconnected 8 Wire level no 2 as indicated in Figure 15 Leave the circled jumpers disconnected Picture 14 View from above Level No 2 Picture 15 View from above Level No 2 with battery connections ...

Page 1060: ...l no 3 insert trays no 7 8 9 in compliance with the position as demonstrated in Picture 16 NOTES On trays no 7 and no 9 check the circled jumper are not connected leave the circled jumper disconnected 10 Wire the level as indicated in Picture 17 Leave the circled jumpers disconnected Picture 16 View from above Level No 3 Picture 17 View from above Level No 3 with battery connections ...

Page 1061: ...no 4 insert trays no 10 11 12 in compliance with the position as demonstrared in Picture 18 NOTES On trays no 10 and no 12 check the circled jumper are not connected leave the circled jumper disconnected 12 Wire the level as indicated in Picture 19 Leave the circled jumpers disconnected Picture 18 View from above Level No 4 Picture 19 View from above Level No 4 with battery connections ...

Page 1062: ...no 5 insert trays no 13 14 15 in compliance with the position as demonstrated in Picture 20 NOTES On trays no 13 and no 15 check the circled jumper are not connected leave the circled jumper disconnected 14 Wire the level as indicated in Picture 21 Leave the circled jumpers disconnected Picture 20 View from above Level No 5 Picture 21 View from above Level No 5 with battery connections ...

Page 1063: ...sert tray no 17 in compliance with the position and cabling as demonstrated in Picture 22 16 Insert tray no 16 by removing the circled jumper and inserting the jumpers as demonstrated in Figure 23 NOTES on tray 16 check the circled jumper is not connected leave the circled jumper disconnected Picture 22 View from above Level No 6 tray no 17 Picture 23 View from above Level No 6 trays no 16 17 ...

Page 1064: ...e avviamento KEOR HPE UPS 60 80 kVA 48 OMW07096 REV E 17 Insert tray no 18 by removing the circled jumper and inserting the jumpers as demonstrated in Picture 24 NOTES on tray 18 check the circled jumper is not connected leave the circled jumper disconnected Picture 24 View from above Level No 6 with battery connections ...

Page 1065: ...ttery voltage Ensure the BCB switch is open 19 From the right hand side of the UPS partially extract tray no 1 and insert the missing jumper as indicated in the Picture 25 Picture 25 View from above Level No 1 with battery connections Battery voltage ATTENTION DANGEROUS VOLTAGE After closing the jumper dangerous voltage will be present on the battery terminals represented in Picture 11 20 Repeat t...

Page 1066: ...S partially extract tray no 3 and before closing the jumper in Picture 26 use a multimeter to check there is no DC voltage between the battery block terminals to shunt with the jumper 22 Repeat the operation indicated in point no 21 for the trays no 6 9 12 15 18 Pict 9 10 Check correct polarity on the battery terminals Figure 27 Battery terminals Picture 26 View from above Level No 1 with battery ...

Page 1067: ...lation of 12 14Ah 12V KEOR HPE 60 80kVA 1 Remove the 6 screws to open the side panels right left and access the battery trays Total shelves 6 and each one is composed of three battery drawers Pict 28 29 1a Remove carton transport protection above all battery shelves Picture 28 12 14Ah 12V battery trays side view KEOR HPE 60kVA Picture 29 12 14Ah 12V battery trays side view KEOR HPE 80kVA ...

Page 1068: ... installed inside the UPS C Carry out the operations as indicated in the following label installed inside the UPS Figure 30 Warning indications for internal battery D Follow the instructions from point 18 to point 23 of this chapter 2 Connect the 2 cables B on the battery terminal 3 Connect the 2 cables N on the battery neutral terminal 4 Connect the 2 cables B on the battery terminal Picture 30A ...

Page 1069: ...e position as demonstrated in Picture 31 NOTES On trays no 1 and no 3 check the circled jumper are not connected leave the circled jumper disconnected 6 Wire level no 1 as indicated in Picture 32 Leave the circled jumpers disconnected 7 On Level no 2 insert trays no 4 5 6 in compliance with the position as demonstrated in Picture 33 Picture 31 View fro above Level No 1 Picture 32 View from above L...

Page 1070: ...trays no 4 and no 6 check the circled jumper are not connected leave the circled jumper disconnected 8 Wire level no 2 as indicated in Picture 34 Leave the circled jumpers disconnected 9 On Level no 3 insert trays no 7 8 9 in compliance with the position as demonstrated in Picture 35 Picture 33 View from above Level No 2 Picture 34 View from above Level No 2 with battery connections ...

Page 1071: ...umper are not connected leave the circled jumper disconnected 9 Wire the level as indicated in Picture 36 Leave the circled jumpers disconnected 11 On Level no 4 insert trays no 10 11 12 in compliance with the position as demonstrated in Picture 37 NOTES On trays no 10 and no 12 check the circled jumper are not connected Picture 35 View from above Level No 3 Picture 36 View from above Level No 3 w...

Page 1072: ...0 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA 56 OMW07096 REV E leave the circled jumper disconnected 12 Wire the level as indicated in Picture 38 Leave the circled jumpers disconnected Picture 37 View from above Level No 4 Picture 38 View from above Level No 4 with battery connections ...

Page 1073: ...nsert tray no 13 14 15 in compliance with the position and cabling as demonstrated in Picture 39 NOTES On trays no 13 and no 15 check the circled jumper are not connected leave the circled jumper disconnected Picture 39 View from above Level No 5 14 Wire the level as indicated in Picture 40 Leave the circled jumpers disconnected Picture 40 View from above Level No 5 with battery connections ...

Page 1074: ...nce with the position and cabling as demonstrated in Picture 41 Picture 41 View from above Level No 6 tray no 17 NOTES On tray no 16 check the circled jumper is not connected leave the circled jumper disconnected 16 Insert tray no 16 by removing the circled jumper and inserting the jumpers as demonstrated in Picture 42 Picture 42 View from above Level No 6 trays no 16 17 Interconnection link betwe...

Page 1075: ...PE UPS 60 80 kVA OMW07096 REV E 59 17 Insert tray no 18 by removing the circled jumper and inserting the jumpers as demonstrated Picture 43 NOTES On tray 18 check the circled jumper is not connected leave the circled jumper disconnected Picture 43 View from above No 6 with battery connections Interconnection link between tray 15 to tray 16 ...

Page 1076: ... From the right hand side of the UPS partially extract tray no 1 and before closing the jumper in Picture 44 use a multimeter to check there is no DC voltage between the battery block terminals to shunt with the jumper Picture 44 View from above Level No 1 with battery connections Battery voltage ATTENTION DANGEROUS VOLTAGE After closing the jumper dangerous voltage will be present on the battery ...

Page 1077: ...partially extract tray no 3 and before closing the jumper in Picture 45 use a multimeter to check there is no DC voltage between the battery block terminals to shunt with the jumper 22 Repeat the operation indicated in point no 21 for the trays no 6 9 12 15 18 Pict 28 29 23 Check correct polarity on the battery terminals Picture 46 Battery terminals Picture 45 View from above Level No 1 with batte...

Page 1078: ...trical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply circuit Batteries installation For battery installation please respect the prescriptions of the EN62040 1 standard paragraph 7 6 To obtain the battery life indicated by the battery manufacturer the ...

Page 1079: ...tteries in fire The battery may explode CAUTION do not open or mutilate batteries Released electrolyte is harmful to the skin and eyes It may be toxic CAUTION do not dump the exhausted batteries in the environment 4 6 1 External Battery connection and positioning Battery voltage The battery installation must be performed after connecting the following conductors AC power supply rectifier input AC ...

Page 1080: ...ibility to check the electrical compatibility and the presence of appropriate protection devices between the cabinet and KEOR HPE11 111 Read the section Installation carefully for assembly procedure of Battery To avoid risk of electromagnetic interference separate the battery cables from Input and Output cables 1 LETHAL VOLATGE of nominal 720 VDC is present when the external battery connection are...

Page 1081: ...battery terminal 4 Connect the auxiliary contact of the EXTERNAL BCB switch on the specific terminal X10 1 2 inside the UPS see photo below 5 After connection and cabling check of the external battery cabinet close the BCB protection of the external battery cabinet and check that voltage and polarity are correct on the battery terminals of the UPS B N B 6 Open the EXTERNAL BCB and check there is n...

Page 1082: ... the UPS on the EXT INP pcb Picture 50 Auxiliary terminals of KEOR HPE 60 80 kVA 4 7 1 Battery auxiliary contact Battery auxiliary contact on terminals X10 1 2 This auxiliary contact is necessary to indicate the position of the isolator open closed 4 7 2 Diesel Generator auxiliary contact Auxiliary contact from the Diesel Generator on terminals X10 3 4 A normally open contact must be used the cont...

Page 1083: ...R HPE 60 80 kVA RS232 USB it is used for connection to the proprietary programming and control software SRC 2 relay card used for the remote signalisations of status and alarms EXT INP it is used for the connection of the external contacts PARALLEL OPTIONAL it is used for communication between paralleled UPS units MODBUS OPTIONAL it is used for the transmission of data to the outside via MODBUS RT...

Page 1084: ...1 Led Pins Status in normal operation Name Status in normal operation RL1 Alarm A30 COMMON ALARM Not energized if alarm is present 2 3 Closed DL1 On 1 2 Open RL2 Alarm A1 MAINS FAULT Not energized if alarm is present 5 6 Closed DL2 On 4 5 Open RL3 Alarm A9 BATTERY AUT END Not energized if alarm is present 8 9 Closed DL3 On 7 8 Open RL4 Alarm A13 INV OUT OF TOL Not energized if alarm is present 11 ...

Page 1085: ... HPE UPS 60 80 kVA OMW07096 REV E 69 4 11 CONNEXION DE LA EXT INP The KEOR HPE UPS 60 80 kVA in its full configuration is provided with a relay card for the connection of the external contacts The electric connection is carried out directly on the terminals located on the front of the interfaces slot EXT INP Picture 53 EXT INP terminals ...

Page 1086: ... to internal battery circuit breaker when the configuration is for internal batteries BCB refers to both internal and external battery circuit breaker when the configuration is with external batteries and its auxiliary contacts properly wired to the UPS terminals 5 1 PRELIMINARY CHECKS Before starting up the unit make sure that all installation and electric connection works have been performed pro...

Page 1087: ...ls on board the UPS This will allow the control logic to acquire the status of the switches and guide the operator during the start up and manual bypass procedures No LCD DISPLAY ACTION OPERATING CHECKS 1 BLANK Close RCB After operating switch RCB the pre charging phase of the capacitive bank will start The control logic will be started and the front panel is activated 2 BOOT LOADER BOOT phase whe...

Page 1088: ...TART UP PLEASE WAIT The control logic checks that all the bypass parameters voltage phase rotation frequency are correct LED 2 is lit green bypass voltage present 11 BATTERY START UP CLOSE BCB Close BCB 12 BATTERY START UP PLEASE WAIT The control logic checks the closing of the circuit breaker to go to the following step Led 4 lit green 13 UPS START UP CLOSE OCB Close OCB 14 START UP END PLEASE WA...

Page 1089: ...2 the unit shows the alarm A15 Byp fault Make sure the switch SBCB is closed Check the protection fuses of the static bypass switch they are inside the unit Check the phase rotation of the bypass voltage Make sure voltage and frequency are within tolerance After step 3 the unit shows the alarm A7 BCB open Make sure you have closed the battery circuit breaker the circuit breaker or the fuse holder ...

Page 1090: ...not be guaranteed to the loads No ACTION LCD DISPLAY OPERATING CHECKS 1 Move the bypass selector SW to BYPASS A30 GENERAL ALARM The load is transferred to the bypass line LED 5 off LED 6 lit orange 2 Close MBCB A30 GENERAL ALARM The inverter is switched off The load is supplied by the input mains through the manual bypass switch The static bypass switch is still closed Led 8 lit orange 3 Open BCB ...

Page 1091: ...e start up conditions are good for restart Led 1 lit green Led 8 lit orange 5 RECTIFIER START UP WAIT PLEASE The IGBT rectifier bridge starts to modulate VDC voltage reaches the nominal value LED 3 is lit green DC voltage present 6 START UP FROM MBCB CLOSE SBCB Close SBCB 7 BYPASS START UP WAIT PLEASE The microprocessor checks that all the bypass parameters voltage phase rotation frequency are wit...

Page 1092: ...PE UPS 60 80 kVA 76 OMW07096 REV E 12 START UP FROM MBCB MOVE BYP SWITCH Move the selector NORMAL BYPASS to NORMAL The load is transferred to the inverter Led 5 lit green 13 START UP END WAIT PLEASE The microprocessor checks that all the output parameters voltage current frequency are within the tolerance limits 14 UPS MODEL OUTPUT VOLTAGE ...

Page 1093: ...Installation and start up of KEOR HPE UPS 60 80 kVA Installation et démarrage de l ASI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA OMW07096 REV E 77 LANGUE FRANÇAIS ...

Page 1094: ...Installation and start up of KEOR HPE UPS 60 80 kVA Installation et démarrage de l ASI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA 78 OMW07096 REV E ...

Page 1095: ...tèmes ASI telle qu indiquée ci dessous BSW07 KEOR HPE 60 kVA BSX46 KEOR HPE 80 kVA Ce manuel ainsi que les autres documentations techniques relatives à ce produit doivent être stockés et mis à disposition du personnel à proximité immédiate de l ASI Si les informations fournies dans le présent manuel ne sont pas suffisamment complètes veuillez contacter le fabricant de l appareil dont les coordonné...

Page 1096: ...uggérons de lire attentivement le présentmanuel L objectif de ce manuel est de vous fournir une brève description des éléments composant l ASI et de vous guider dans l installation de l unité dans son environnement d utilisation L installateur ou l utilisateur devra lire et respecter les instructions fournies dans le présent manuel en particulier les exigences relatives à la sécurité conformément ...

Page 1097: ... est fourni avec une plaque signalétique indiquant ses valeurs nominales de fonctionnement Cette plaque est apposée sur la face intérieure de la porte Illustration 1 Plaque signalétique de l ASI KERO HPE 60 80 kVA Avant toute opération d installation ou de démarrage de l ASI assurez vous que ses caractéristiques techniques sont compatibles avec l alimentation CA et les charges en sortie Vérifiez l...

Page 1098: ...gralité de ce manuel en particulier les exigences relatives à la sécurité La formation et les qualifications du personnel ne seront considérées comme valides que si elles ont été certifiées par le fabricant 2 3 3 Transport et manutention Évitez de tordre ou de déformer les composants ainsi que de modifier les distances d isolement lors du transport et de la manutention du produit Le poids d un ASI...

Page 1099: ...une source de chaleur L ASI est conçu pour des conditions de fonctionnement environnementales et climatiques normales telles que définies dans les caractéristiques techniques altitude température ambiante de fonctionnement humidité relative et conditions environnementales de transport et de stockage Il est nécessaire de mettre en œuvre des mesures de protection spécifiques en cas de conditions inh...

Page 1100: ...rrespondent au système d alimentation CA et à la consommation électrique réelle de tous les équipements raccordés L ASI doit être installé conformément à la réglementation nationale en vigueur L ASI est également prévue pour fonctionner avec un régime de neutre IT Tous les raccordements électriques doivent être réalisés par un personnel autorisé Avant tout raccordement de l appareil vérifiez que l...

Page 1101: ...mes de sécurité en vigueur réglementations relatives aux équipements techniques et à la prévention des accidents L appareil ne peut être mis en marche utilisé et déconnecté que par un personnel autorisé Lorsqu il fonctionne l ASI convertit des puissances caractérisées par des tensions et courants élevés Toutes les portes et tous les capots doivent rester fermés La batterie fournie avec l ASI conti...

Page 1102: ... décharge lente des condensateurs internes Nous recommandons par conséquent de patienter au moins 5 minutes avant d ouvrir les portes de l appareil Toute opération doit être réalisée uniquement en l absence de tension et dans le respect des directives de sécurité Assurez vous que le disjoncteur de la batterie qui peut se trouver à proximité de celle ci est en position ouverte Isolez complètement l...

Page 1103: ...uvaise ventilation chaleur conduite ou rayonnante en provenance d autres sources moisissures insectes nuisibles 2 4 PROTECTION DE L ENVIRONNEMENT 2 4 1 Certification ISO 14001 Legrand est particulièrement sensible à l impact de ses produits sur l environnement C est pourquoi l ASI est fabriqué en tenant compte de critères d éco conception de pointe certification ISO 14001 Une attention spéciale a ...

Page 1104: ...mballaged origine Les dommages mécaniques subis par les composants électriques constituent un grave danger pour les personnes et les biens En cas de doute concernant l intégrité de l emballage ou du produit contactez le fabricant avant toute installation et ou démarrage 3 1 1 Stockage L emballage protège normalement l appareil de l humidité et des éventuels dommages pouvant se produire pendant le ...

Page 1105: ...s des opérations de chargement et de déchargement respectez toujours les indications concernant le barycentre de l appareil qui figurent surl emballage Avant de positionner l onduleur et afin d éviter les risques de bascules il est recommandé de déplacer le système sur la palette de bois sur lequel l onduleur est fixé Avant le positionnement dans l emplacement final retirer l onduleur de la palett...

Page 1106: ...ent être conformes à la législation en vigueur veuillez vous reporter à la section Ventilation Il est nécessaire de mettre en œuvre des mesures de protection spécifiques en cas de conditions environnementales inhabituelles fumées dangereuses poussières poussières abrasives humidité vapeur air à forte teneur en sel mauvaises conditions météorologiques ou aspersion d eau mélange de poussières et de ...

Page 1107: ...24 24 582 Ø 8 387 387 57 Illustration 3 Plan de base Le sol soutenant l ASI doit être conçu pour supporter le poids de l ASI et assurer un maintien sûr et stable Sa capacité de soutien doit correspondre aux charges statiques indiquées dans le tableau ci dessous Puissance kVA 60 80 Poids des batteries kg 225 250 Charge statique sans les batteries kg m2 430 480 Poids avec les batteries kg 780 800 Ch...

Page 1108: ...A Installation et démarrage de l ASI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA 92 OMW07096 REV E 3 3 2 Dimensions totales dégagement minimum et ventilation Illustration 4 Dimensions globales Illustration 5 Dégagement minimum ...

Page 1109: ...tions d installation telles qu indiquées dans le tableau ci dessous s appliquent quelle que soit la taille de l ASI ASI avec batteries internes A mm B mm C mm E D mm Dégagements recommandés 50 1200 600 600 Dégagement minimum 0 1200 600 400 E valide uniquement pour ASI avec batteries internes ASI avec batteries externes A mm B mm C mm D mm Dégagements recommandés 50 1200 400 600 Dégagement minimum ...

Page 1110: ...rovenant d une source autre que la pluie NON Formation de glace NON Classification des conditions biologiques EN 60721 3 3 Agent d environnement Classe 3B1 3B2 3B3 a Flore NON Présence de moisissures champignons etc Présence de moisissures champignons etc b Faune NON Présence de rongeurs et d autres animaux nuisibles aux produits hors termites Présence de rongeurs et d autres animaux nuisibles aux...

Page 1111: ...illée et régulée de manière stricte catégorie des espaces propres X Sites sur lesquels l atmosphère est surveillée en permanence X Sites situés dans des régions rurales et urbaines présentant une faible activité industrielle et un trafic modéré X Sites situés dans des régions urbaines présentant une activité industrielle et ou un trafic important X Sites à proximité de sources industrielles d émis...

Page 1112: ...à la terre Pour l installation de la batterie respecter strictement la norme EN62040 1 et suivez le manuel d installation de l ASI Pour obtenir la durée de vie de la batterie indiquée par le fabricant de la batterie la température de fonctionnement doit rester comprise entre 0 et 25 C Cependant bien que la batterie puisse fonctionner jusqu à 40 C il y aura une réduction significative de la durée d...

Page 1113: ...technique dépendent de la tension du courant absorbé par l ASI de la ligne de by pass et des batteries de la température ambiante et de la chute de tension Enfin la façon de poser les câbles doit également faire l objet d une attention particulière Pour plus d explications concernant le choix et le dimensionnement des câbles reportez vous aux normes CEI concernées en particulier la norme CEI 64 8 ...

Page 1114: ... les câbles suivants doivent être raccordés suivre l ordre ci dessous Entrée redresseur alimentation AC Alimentation électrique de Bypass input AC Sortie ASI Alimentation DC Batterie Dans le cas d une batterie externe les câbles qui en sortent ont des tensions élevées et dangereuses Les câbles doivent être protégés contre les courts circuits et les courants de fuite à la terre Les points de raccor...

Page 1115: ...onformément à la norme CEI UNEL35024 1 en utilisant les données suivantes câbles en cuivre PVC cotés 70 C température ambiante égale à 40 C longueur maximale des câbles égale à 30 m chute de tension 0 5 câbles placés dans les cavités de structures ou chemins de câbles inférieurs solides Les sections transversales données ne tiennent pas compte des courants de surcharge autorisés par chaque ligne q...

Page 1116: ...tre les surintensités en utilisant un disjoncteur avec bobine de déclenchement à émission raccordé à l ASI suivant le schéma de principe décrit Illustration 6 En cas de défaut de retour de tension de l ASI l ASI enverra un signal de déclenchement au disjoncteur pour isoler l ASI et ainsi protéger les circuits de distribution amont L installateur doit appliquer le marquage d avertissement suivant s...

Page 1117: ...tion and start up of KEOR HPE UPS 60 80 kVA Installation et démarrage de l ASI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA OMW07096 REV E 101 Illustration 6 Borniers KEOR HPE 60 80 kVA ...

Page 1118: ...SI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA 102 OMW07096 REV E 4 3 BORNIERS L ASI KEOR HPE 60 80 kVA est fourni avec des borniers permettant le raccordement des câbles d alimentation et les raccordements auxiliaires Illustration 7 Borniers KEOR HPE 60 80 kVA ...

Page 1119: ... de telles mises à la terre sont supprimées durant l installation ou la maintenance appliquable aux équipements et alimentations à base de batteries ne nécessitant pas d avoir un circuit d alimentation relié à la terre Pour l installation de la batterie respecter strictement la norme EN62040 1 et suivez le manuel d installation de l ASI Pour obtenir la durée de vie de la batterie indiquée par le f...

Page 1120: ...ux ATTENTION ne pas décharger les batteries dansl environnement 4 4 1 Emplacement et conexion des batteries L installation de la batterie doit être effectuée après avoir connecté les conducteurs suivants Entrée redresseur alimentation AC Alimentation électrique de Bypass input AC Sortie ASI Dans le cas ou les câblages ne sont pas directement fournis connecter les câbles au bornier batterie de l AS...

Page 1121: ...es 9 11Ah 12V KEOR HPE 60 80kVA 1 Retirer les six vis pour ouvrir les panneaux latéraux droit gauche et accéder aux plateaux des batteries Au total 6 plateaux chacun composé de trois tiroirs de batterie Illustration 9 10 1a Déposez les protections de transport en carton au dessus de chaque plateau batterie Illustration 9 Tiroirs batteries 9 11Ah 12V vue latérale KEOR HPE 60kVA Illustration 10 Tiro...

Page 1122: ...ie B suivre les instructions du point 18 au point 23 de ce chapitre 2 Brancher les 3 câbles B sur la borne B du bornier batterie 180 186 batteries 2A Brancher les 2 câbles B sur la borne B du bornier batterie 120 124 batteries 3 Brancher les 3 câbles N sur la borne N du bornier batterie 180 186 batteries 3A Brancher les 2 câbles N sur la borne N du bornier batterie 120 124 batteries 4 Brancher les...

Page 1123: ...érifiez que les ponts cerclés ne soient pas connectés le cas échéant déconnectez les 6 Câbler le plateau N 1 comme indiqué dans l Illustrat 13 Laisser les ponts cerclés déconnectés Figure 23 Illustration 12 Vue de dessus Plateau N 1 Illustration 13 Vue de dessus Plateau N 1 avec connexion des batteries CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI CÔTÉ ARRIÈRE ASI CÔTÉ AVANT ASI UNIQUEMENT POUR 31 BATTERIES I I...

Page 1124: ...r les tiroirs n 4 et n 6 vérifiez que les ponts cerclés ne soient pas connectés le cas échéant déconnectez les 8 Câbler le plateau N 2 comme indiqué dans l Illustrat 15 Laisser les ponts cerclés déconnectés Illustration 14 Vue de dessus Plateau N 2 Illustration 15 Vue de dessus Plateau N 2 avec connexion des batteries CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI CÔTÉ AVANT ASI UNIQUEMENT POUR 31 BATTERIES UNIQ...

Page 1125: ...n 9 vérifiez que les ponts cerclés ne soient pas connectés le cas échéant déconnectez les 10 Câbler le plateau N 3 comme indiqué dans l Illustrat 17 Laisser les ponts cerclés déconnectés Illustration 16 Vue de dessus Plateau N 3 Illustration 17 Vue de dessus Plateau N 3 avec connexion des batteries CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI CÔTÉ ARRIÈRE ASI UNIQUEMENT POUR 31 BATTERIES Interconnexion liaison...

Page 1126: ...fiez que les ponts cerclés ne soient pas connectés le cas échéant déconnectez les 12 Câbler le plateau N 4 comme indiqué dans l Illustrat 19 Laisser les ponts cerclés déconnectés Illustration 18 Vue de dessus Plateau N 4 Illustration 19 Vue de dessus Plateau N 4 avec connexion des batteries CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI CÔTÉ AVANT ASI CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASIUNIQUEMENT POUR 31 BATTERIES U...

Page 1127: ...t n 15 vérifiez que les ponts cerclés ne soient pas connectés le cas échéant déconnectez les 14 Câbler le plateau N 5 comme indiqué dans l Illustrat 21 Laisser les ponts cerclés déconnectés Illustration 20 Vue de dessus Plateau N 5 Illustration 21 Vue de dessus Plateau N 5 avec connexion des batteries CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI UNIQUEMENT POUR 31 BATTERIES UNIQ...

Page 1128: ...nt cerclé et en introduisant les ponts comme l indique l illustration 23 NOTES Sur le tiroir n 16 vérifiez que le pont cerclé ne soit pas connecté le cas échéant deconnectez le Illustration 22 Vue de dessus Plateau N 6 tiroir N 17 Illustration 23 Vue de dessus Plateau N 6 tiroir N 16 17 CÔTÉ ARRIÈRE ASI CÔTÉ ARRIÈRE ASI CÔTÉ AVANT ASI CÔTÉ AVANT ASI Interconnexion liaison Interconnexion liaison UN...

Page 1129: ...levant le pont cerclé et en introduisant les ponts comme l indique l illustration 24 NOTE Sur les tiroirs n 18 vérifiez que le pont cerclé ne soit pas connecté le cas échéant déconnectez le Illustration 24 Vue de dessus Plateau N 6 avec connexion des batteries CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI Interconnexion liaison UNIQUEMENT POUR 31 BATTERIES Interconnexion entre rangée 16 et rangée 15 Interconnex...

Page 1130: ...our terminer la connexion Tension de batterie Assurez vous que l interrupteur BCB soit ouvert 19 Du côté droit de l UPS extraire partiellement le tiroir n 1 et introduire le pont manquant comme l indique l illustration 25 Illustration 25 Vue de dessus Plateau N 1 avec connexion des batteries CÔTÉ ARRIÈRE ASI CÔTÉ AVANT ASI Interconnexion liaison Interconnexion liaison UNIQUEMENT POUR 31 BATTERIES ...

Page 1131: ...tion 11 20 Répéter l opération indiquée au point n 19 pour les tiroirs n 4 7 10 13 16 Illustrat 9 10 21 Du côté gauche de l UPS extraire partiellement le tiroir n 3 avant de raccorder le pont fig 26 utilisez un multimetre tension continue pour verifier qu il n y ait pas de tension entre les bornes des blocs batterie à shunter avec le pont Illustration 26 Vue de dessus Plateau N 1 avec connexion de...

Page 1132: ...stallazione e avviamento KEOR HPE UPS 60 80 kVA 116 OMW07096 REV E 22 Répéter l opération indiquée au point n 21 pour les tiroirs n 6 9 12 15 18 Illustrastr 9 10 23 Vérifier que les tensions et polarités soient correctes sur le bornier batterie de l ASI B N B Illustration 27 Bornier batterie de l ASI BATTERIE ...

Page 1133: ...PE 60 80kVA 1 Retirer les six vis pour ouvrir les panneaux latéraux droit gauche et accéder aux plateaux des batteries Au total 6 plateaux chacun composé de trois tiroirs de batterie Fig 28 29 1a Déposez les protections de transport en carton au dessus de chaque plateau batterie Illustration 28 Tiroirs batteries 12 14Ah 12V vue latérale KEOR HPE 60kVA Illustration 29 Tiroirs batteries 9 11Ah 12V v...

Page 1134: ...I A Effectuez les operations comme indiqué sur l étiquette suivante installée à l intérieur de l ASI Figure 30 Attention le indications internal batterie B suivre les instructions du point 18 au point 23 de ce chapitre 2 Brancher les 2 câbles B sur la borne B du bornier batterie 3 Brancher les 2 câbles N sur la borne N du bornier batterie 4 Brancher les 2 câbles B sur la borne B du bornier batteri...

Page 1135: ...3 vérifiez que les ponts cerclés ne soient pas connectés le cas échéant déconnectez les 6 Câbler le plateau N 1 comme indiqué dans l Illustrat 32 Laisser les ponts cerclés déconnectés Illustration 31 Vue de dessus Plateau N 1 Illustration 32 Vue de dessus Plateau N 1 avec connexion des batteries CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI CÔTÉ ARRIÈRE ASI CÔTÉ AVANT ASI UNIQUEMENT POUR 31 BATTERIES UNIQUEMENT...

Page 1136: ...erclés ne soient pas connectés le cas échéant déconnectez les 8 Câbler le plateau N 2 comme indiqué dans l Illustrat 32 Laisser les ponts cerclés déconnectés Illustration 33 Vue de dessus Plateau N 2 Illustration 34 Vue de dessus Plateau N 2 avec connexion des batteries CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI UNIQUEMENT POUR 31 BATTERIES UNIQUEMENT POUR 31 BATTERIES Interco...

Page 1137: ...E Sur les tiroirs n 7 et n 9 vérifiez que les ponts cerclés ne soient pas connectés le cas échéant déconnectez les 10 Câbler le plateau N 3 comme indiqué dans l Illustration 36 Laisser les ponts cerclés déconnectés Illustration 35 Vue de dessus Plateau N 3 Illustration 36 Vue de dessus Plateau N 3 avec connexion des batteries CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI Intercon...

Page 1138: ... 12 vérifiez que les ponts cerclés ne soient pas connectés le cas échéant déconnectez les 12 Câbler le plateau N 4 comme indiqué dans l Illustrat 38 Laisser les ponts cerclés déconnectés Illustration 37 Vue de dessus Plateau N 4 Illustration 38 Vue de dessus Plateau N 4 avec connexion des batteries CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI CÔTÉ ARRIÈRE ASI CÔTÉ AVANT ASI UNIQUEMENT POUR 31 BATTERIES UNIQUEM...

Page 1139: ... Illustration 39 Vue de dessus Plateau N 5 14 Câbler le plateau N 5 comme indiqué dans l Illustrat 40 Laisser les ponts cerclés déconnectés Illustration 40 Vue de dessus Plateau N 5 avec connexion des batteries CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI CÔTÉ ARRIÈRE ASI CÔTÉ AVANT ASI UNIQUEMENT POUR 31 BATTERIES UNIQUEMENT POUR 31 BATTERIES Interconnexion liaison Interconnexion liaison Interconnexion liaiso...

Page 1140: ...n 41 Vue de dessus Plateau N 6 tirroir n 17 NOTE Sur les tiroirs n 16 vérifiez que le pont cerclé ne soit pas connecté le cas échéant déconnectez le 16 Introduire le tiroir n 16 en enlevant pont cerclé et en introduisant les ponts et interconnexions comme l indique l illustration 42 Illustration 42 Vue de dessus Plateau N 6 avec tiroirs n 16 et n 17 CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI CÔTÉ ARRIÈRE ASI...

Page 1141: ... enlevant le pont cerclé et en introduisant les ponts et interconnections comme l indique l illustration 43 NOTE Sur les tiroirs n 18 vérifiez que le le pont cerclé ne soit pas connecté le cas échéant déconnectez le Illustration 43 Vue de dessus Plateau N 6 avec connexion des batteries CÔTÉ AVANT ASI CÔTÉ ARRIÈRE ASI Interconnexion liaison Interconnexion liaison Interconnexion entre rangée 15 et r...

Page 1142: ... UPS extraire partiellement le tiroir n 1 et introduire le pont manquant comme l indique la figure 44 Illustration 44 Vue de dessus Plateau N 1 avec connexion des batteries Tension de batterie ATTENTION TENSION DANGEREUSE Après la fermeture du pont une tension dangereuse sera présente sur le bornier batterie de l ASI représenté en Figure 30 20 Répéter l opération indiquée au point n 19 pour les ti...

Page 1143: ...y ait pas de tension entre les bornes des blocs batterie à shunter avec le pont 22 Répéter l opération indiquée au point n 21 pour les tiroirs n 6 9 12 15 18 Illustration 28 29 23 Vérifier que les tensions et polarités soient correctes sur le bornier batterie de l ASI B N B Illustration 46 Bornier batterie de l ASI Illustration 45 Vue de dessus Plateau N 1 avec connexion des batteries CÔTÉ AVANT A...

Page 1144: ...éer une électrocution La probabilité d un tel choc électrique peut être réduite si de telles mises à la terre sont supprimées durant l installation ou la maintenance appliquable aux équipements et alimentations à base de batteries ne nécessitant pas d avoir un circuit d alimentation relié à la terre Installation des batteries Pour l installation de la batterie respecter strictement la norme EN6204...

Page 1145: ... feu La batterie peut exploser ATTENTION ne pas ouvrir ou dégrader les batteries L electrolyte libéré est nocif pour la peau et les yeux ATTENTION ne pas décharger les batteries dansl environnement 4 6 1 Emplacement et connexion des batteries externes Tension batterie L installation de la batterie doit être effectuée après avoir connecté les conducteurs suivants Entrée redresseur alimentation AC A...

Page 1146: ... de la compatibilité des batteries avec le Keor HPE ainsi que du câblage et de la protection appropriée entre l armoire batterie et le Keor HPE 111 Lire attentivement le manuel d installation pour le schéma de câblage des batteries Pour éviter les risques de perturbation électromagnétique séparez les câbles batterie des câbles d entrée sortie 1 Tension léthale de 720VDC présente lorsque la batteri...

Page 1147: ...du bornier batterie de l ASI iIlustration 46 4 Brancher le contact auxiliaire du sectionneur BCB EXTERNE sur la borne X10 1 2 prévue à l intérieur de l UPS voir photo ci dessous 5 Après raccordement et vérification du câblage de la batterie externe fermez uniquement la protection BCB de l armoire batterie externe vérifiez que les tensions et les polarités soient correctes sur le bornier batterie d...

Page 1148: ...0 kVA 4 7 1 Contact auxiliaire de batterie Contat auxiliaire de batterie bornes X10 1 2 Ce contact auxiliaire est nécessaire pour indiquer la position de l isolateur ouvert fermé 4 7 2 Contact auxiliaire du Groupe electrogène Contact auxiliaire du Groupe electrogène des bornes X10 3 4 Un contact normalement ouvert doit être utilisé le contact doit être fermé quand le groupe electrogène est actionn...

Page 1149: ...es de série du KEORHPE 60 80 kVA RS232 USB il est pour la connexion du logiciel propriétaire de programmation et configuration SRC 2 carte relais pour le report à distance des statuts et alarmes EXT INP il est utilisé pour la connexion des contacts externes PARALLEL OPTIONNEL utilisé pour la communication entre des ASI enparallèles MODBUS OPTIONNEL utilisé pour la transmission de données vers l ex...

Page 1150: ... Broches Statuts en fonctionnement normal Nom Statuts en fonctionnement normal RL1 Alarme A30 ALARME GENERALE Hors tension si alarme présente 2 3 Fermé DL1 On 1 2 Ouvert RL2 Alarme A1 DEFAUT SECTEUR Hors tension si alarme présente 5 6 Fermé DL2 On 4 5 Ouvert RL3 Allarme A9 FIN AUTONOMIE BATTERIE Hors tension si alarme présente 8 9 Fermé DL3 On 7 8 Ouvert RL4 Alarme A13 ONDULEUR EN DEHORS DES TOLER...

Page 1151: ...OMW07096 REV E 135 4 11 CONNEXION DES CONTACTS EXTERNES EXT INP L ASI KEOR HPE 60 80 kVA dans sa configuration complète est fournie avec une carte EXT INP pour la connexion de contacts externes La connection électrique est directement mise en oeuvre sur les bornes situées en face des fentes des interfaces EXT INP Illustration 53 Bornes de la carte EXT INP ...

Page 1152: ...tterie interne et externe lorsque la configuration est avec batteries externes et leurs contacts auxiliaires proprement connectés au bornier de l ASI 5 1VERIFICATIONS PRELIMINAIRES Avant de démarrer l unité assurez vous que tous les travaux d installation et de raccordement électrique ont été réalisés de manière professionnelle tous les câbles d alimentation et de commande sont correctement raccor...

Page 1153: ...que de commande d acquérir l état des commutateurs et de guider l opérateur lors des procédures de mise en route et de bypass manuel No AFFICHEUR LCD ACTION VÉRIFICATIONS DE FONCTIONNEMENT 1 VIDE Fermer le RCB Quelques secondes après la fermeture du disjoncteur d entrée RCB la phase de pré charge de la banque de condensateurs commence La logique de contrôle démarre et le panneau avant est activé 2...

Page 1154: ... START UP CLOSE SBCB Démarrage du by pass Fermer le SBCB Fermer le SBCB 10 BYPASS START UP WAIT PLEASE Démarrage du by pass Veuillez patienter La logique de contrôle vérifie que tous les paramètres du by pass tension rotation de phases fréquence sont corrects La LED 2 est allumée en vert tension by pass présente 11 BATTERY START UP CLOSE BCB Démarrage de la batterie Fermer le BCB Fermer BCB 12 BAT...

Page 1155: ...marrage et affiche un ou plusieurs messages d alarme Vérifiez les alarmes indiquées à l écran et résolvez lesproblèmes Fermez RCB et essayez de redémarrer l ASI Après l étape n 2 l unité affiche l alarme A15 Byp fault Défaut duby pass Assurez vous que le commutateur SBCB soit fermé Vérifiez les fusibles de protection du commutateur de by pass statique qui se trouvent à l intérieur de l unité Vérif...

Page 1156: ... VÉRIFICATIONS DE FONCTIONNEMENT 1 Ouvrir OCB A30 GENERAL ALARM L alimentation de la charge est coupée La LED 7est éteinte 2 Ouvrir BCB A30 GENERAL ALARM La batterie est déconnectée du redresseur La LED 4 est rouge clignotante 3 Ouvrir SBCB A30 GENERAL ALARM L alimentation du bypass est déconnectée La LED 2 est éteinte 4 Ouvrir S2 A30 GENERAL ALARM Redresseur et onduleur sont coupés 5 BLANK Fin de...

Page 1157: ... sélecteur de by pass SW sur BYPASS A30 GENERAL ALARM A30 Alarme générale La charge est transférée sur la ligne de by pass La LED 5 est éteinte la LED 6 est allumée en orange 2 Fermer MBCB A30 GENERAL ALARM A30 Alarme générale L onduleur est arrêté La charge est alimentée par le secteur via le commutateur de by pass manuel Le commutateur de by pass statique reste fermé La LED 8 est allumée en oran...

Page 1158: ...Toutes les LED du panneau avant sont éteintes 4 UPS START UP WAIT PLEASE Démarrage de l ASI Veuillez patienter Le redresseur est alimenté et la tension CC atteint sa valeur nominale Toutes les LED du panneau avant sont allumées Le microprocesseur vérifie que toutes les conditions de démarrage sont bonnes pour le redémarrage La LED 1 est allumée en vert La LED 8 est allumée en orange 5 RECTIFIER ST...

Page 1159: ...CB Ouvrir MBCB La charge est alimentée par le commutateur de by pass statique et l onduleur peut être démarré La LED 8 est éteinte 11 INVERTER START WAIT PLEASE Démarrage de l onduleur Veuillez patienter La modulation du pont de l onduleur démarre La tension CA atteint sa valeur nominale Le microprocesseur vérifie la synchronisation avec la ligne de by pass 12 START UP FROM MBCB MOVE BYP SWITCH Dé...

Page 1160: ...Installation and start up of KEOR HPE UPS 60 80 kVA Installation et démarrage de l ASI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA 144 OMW07096 REV E LINGUA ITALIANA ...

Page 1161: ...Installation and start up of KEOR HPE UPS 60 80 kVA Installation et démarrage de l ASI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA 145 OMW07096 REV E ...

Page 1162: ...guito BSW07 KEOR HPE 60 kVA BSX46 KEOR HPE 80 kVA Conservazione della documentazione Questo manuale e tutta la restante documentazione tecnica di supporto al prodotto devono essere conservati e possibilmente resi accessibili al personale nelle immediate vicinanze dell UPS Informazioni aggiuntive Nel caso le informazioni riportate nel presente manuale non fossero abbastanza esaurienti si prega di c...

Page 1163: ... il tempo per la lettura del seguente manuale Lo scopo di questo manuale è di descrivere brevemente le parti che compongono l UPS e di guidare l installatore o l utente ad una corretta installazione dell apparato nell ambiente di utilizzo L installatore o l utente dovrà leggere ed eseguire correttamente quanto dichiarato nel presente manuale con particolare riguardo alle richieste relative alla si...

Page 1164: ...na targhetta di identificazione che riporta i dati nominali di funzionamento La targhetta è fissata nella parte interna della porta frontale Figura 1 Targhetta caratteristiche KEOR HPE 60 80 kVA Verificare le caratteristiche tecniche Prima di effettuare qualsiasi operazione di installazione e avviamento del dispositivo verificare che le caratteristiche tecniche siano compatibili con la rete di ali...

Page 1165: ...da considerarsi tali solo se certificati dall azienda produttrice 2 3 3 Trasporto e movimentazione Durante il trasporto e la movimentazione del prodotto prestare la massima attenzione al fine di evitare di piegare o deformare le parti componenti e di modificare le distanze di isolamento Peso non distribuito Il peso dell UPS non è uniformemente distribuito Prestare particolare attenzione nel sollev...

Page 1166: ...ll esposizione diretta dei raggi solari e non posizionarlo in prossimità di una fonte di calore Condizioni ambientali particolari L UPS è progettato per sopportare condizioni climatiche ed ambientali di esercizio normali come indicato nella specifica tecnica altitudine temperatura ambiente d esercizio umidità relativa condizioni ambientali di trasporto e stoccaggio Si rende necessarie mettere in a...

Page 1167: ...ica di alimentazione ed al consumo elettrico reale della totalità delle apparecchiature collegate Verificare la conformità alle normative L UPS deve essere installato conformemente alle normative vigenti nel paese di installazione Sistema IT L apparecchiatura è stata progettata anche per essere collegata ad un sistema di distribuzione dell alimentazione IT Tutti i collegamenti elettrici devono ess...

Page 1168: ...parte gli UPS devono seguire tutte le norme vigenti riguardanti la sicurezza equipaggiamenti tecnici e regolamenti antinfortunistici Il dispositivo deve essere avviato manovrato e disconnesso solamente da parte di personale autorizzato Le tarature possono essere modificate solo utilizzando il software di interfaccia originale Pericolo di lesioni a seguito shock elettrico Durante il funzionamento l...

Page 1169: ...ntazione a causa dei condensatori interni che si scaricano lentamente Si consiglia quindi di attendere almeno 5 minuti prima di aprire le porte del dispositivo Pericolo di lesioni a seguito shock elettrico Eventuali interventi devono essere effettuati solamente in assenza di tensione e nel rispetto delle direttive sulla sicurezza Accertarsi di aver aperto il sezionatore della batteria che può esse...

Page 1170: ...one calore condotto o irradiato proveniente da altre fonti funghi insetti nocivi parassiti 2 4TUTELA AMBIENTALE 2 4 1 Certificazione ISO 14001 Legrand è particolarmente sensibile all impatto ambientale dei propri prodotti per questo motivo l UPS è stato realizzato seguendo i più moderni criteri di eco progettazione certificazione ISO 14001 E stata prestata particolare attenzione nell utilizzo di m...

Page 1171: ...costruttore si prega di utilizzare l imballaggio originale Pericolo per le persone a seguito di danni da trasporto Il danneggiamento meccanico dei componenti elettrici costituisce un grave pericolo per persone e cose Qualora si abbia il dubbio di una non completa integrità dell imballo o del prodotto entro ad esso contenuto contattare l azienda produttrice prima di effettuare l installazione e o l...

Page 1172: ...rasportati in posizione eretta Durante le manovre di carico e scarico rispettare sempre le indicazioni relative al baricentro del dispositivo contrassegnato sull imballaggio Per gli spostamenti dell UPS prima del posizionamento finale si consiglia di non rimuoverlo dal pancale in legno sul quale è fissato per evitare eventuali rischi di ribaltamento Prima del posizionamento rimuovere l UPS dal pan...

Page 1173: ...o di installazione in accordo alle normative correnti fare riferimento alla sezione Dimensioni di ingombro distanze minime dalle pareti e ventilazione Condizioni ambientali particolari Si rende necessario mettere in atto misure di protezione specifiche in caso di condizioni ambientali insolite fumi nocivi polveri polvere abrasiva umidità vapore aria salina intemperie o gocciolamento miscela esplos...

Page 1174: ...494 24 24 582 Ø 8 387 387 57 Figura 3 Pianta di base La base di appoggio dell UPS deve essere progettata per sopportare il peso del dispositivo e per garantirne il supporto saldo e sicuro La capacità portante deve essere conforme ai carichi statici indicati nella tabella seguente Potenza kVA 60 80 Peso senza batterie kg 225 250 Carico statico senza batterie kg m2 430 480 Peso con batterie kg 780 8...

Page 1175: ...stallation et démarrage de l ASI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA 159 OMW07096 REV E 3 3 2 Dimensioni di ingombro distanze minime dalle pareti e ventilazione Figura 4 Dimensioni di ingombro Figura 5 Distanze di rispetto ...

Page 1176: ...ondizioni di installazione per quanto riguarda le distanze minime dalle pareti come indicate nella tabella seguente UPS con batterie interne A mm B mm C mm E mm D mm Distanze raccomandate 50 1200 600 600 Distanze minime 0 1200 600 400 E valido solo per UPS con batterie interne UPS con batterie esterne A mm B mm C mm D mm Distanze raccomandate 50 1200 400 600 Distanze minime 0 1200 0 400 La tabella...

Page 1177: ... di origine diversa dalla pioggia NO Formazione di ghiaccio NO Classificazione delle condizioni biologiche EN 60721 3 3 Parametro ambientale Classe 3B1 3B2 3B3 Flora NO Presenza di muffa funghi ecc Presenza di muffa funghi ecc Fauna NO Presenza di roditori e altri animali dannosi ai prodotti escludendo le termiti Presenza di roditori e altri animali dannosi ai prodotti includendo le termiti Classi...

Page 1178: ...amente monitorata e controllata categoria camera pulita X Luoghi con atmosfera continuamente controllata X Luoghi posti in zone rurali e urbane dove sono modeste le attività industriali e il traffico è moderato X Luoghi in zone urbane con attività industriali e o grande traffico X Luoghi posti in prossimità di sorgenti industriali con emissioni chimiche X Luoghi posti all interno di installazioni ...

Page 1179: ... terra Seguire le istruzioni d installazione Per l installazione delle batterie attenersi rigorosamente alle EN62040 1 inoltre dovrà essere seguito il manuale di installazione dell UPS Per ottenere una durata di vita della batteria pari a quella indicata dal costruttore la temperatura di esercizio deve essere compresa fra 0 e 25 C La batteria può comunque operare fino a 40 C con forte riduzione de...

Page 1180: ...a tenendo in considerazione gli aspetti tecnici economici e di sicurezza La scelta e il dimensionamento dei cavi dal punto di vista tecnico è funzione della tensione della corrente assorbita dall UPS dalla rete bypass e dalle batterie della temperatura ambiente e della caduta di tensione infine si deve tenere in particolare considerazione il tipo di posa del cavo Ulteriori chiarimenti sulla scelta...

Page 1181: ... UPS alla rete 4 1COLLEGAMENTO CONDUTTORI DI POTENZA Per il collegamento elettrico dell UPS KEOR HPE 60 80 kVA è necessario allacciare i seguenti conduttori seguendo l ordine sotto elencato Alimentazione AC ingresso raddrizzatore Alimentazione AC ingresso bypass Uscita UPS Alimentazione DC da batteria Pericolo di lesioni a seguito shock elettrico In caso di batteria esterna i cavi provenienti dall...

Page 1182: ...avi sono stati dimensionati in accordo alla norma CEI UNEL35024 1 utilizzando i seguenti dati cavi unipolari in rame con isolamento in PVC e temperatura massima di 70 C temperatura ambiente pari a 40 C massima lunghezza dei cavi pari a 30 m caduta di tensione 0 5 posa dei cavi in cavità di strutture o passerelle non perforate Le sezioni dei cavi non tengono conto dei valori di sovraccarico ammessi...

Page 1183: ...e e collegata all UPS secondo lo schema elettrico riportato in Figura 6 In caso di guasto di backfeed rilevato dall UPS l UPS invierà alla bobina un segnale di 230 Vac impulsivo che farà trippare il MCCB quindi isolerà l UPS al fine di proteggere i circuiti di distribuzione a monte dell UPS L installatore deve applicare la seguente etichetta su tutti i dispositivi che alimentano l UPS La tabella s...

Page 1184: ... KEOR HPE UPS 60 80 kVA Installation et démarrage de l ASI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA 168 OMW07096 REV E Figura 6 Schema unifilare KEOR HPE 60 80kVA con collegamento al dispositivo esterno ...

Page 1185: ...ge de l ASI KEOR HPE 60 80 kVA Installazione e avviamento KEOR HPE UPS 60 80 kVA 169 OMW07096 REV E 4 3MORSETTIERE L UPS KEOR HPE 60 80 kVA è provvisto di morsettiere per l allacciamento dei cavi di potenza e delle connessioni ausiliarie Figura 7 Morsettiera KEOR HPE 60 80 kVA ...

Page 1186: ...a scossa elettrica La probabilità può essere ridotta se i collegamenti di terra vengono interrotti durante l installazione e la manutenzione applicabile ad apparecchiature e ad alimentazioni a batteria poste a distanza prive di circuito di alimentazione messo a terra Installazione batterie Per l installazione delle batterie attenersi rigorosamente alle EN62040 1 paragrafo 7 6 Per ottenere una dura...

Page 1187: ...to è pericoloso per la pelle e per gli occhi Può essere tossico ATTENZIONE non gettare le batterie esauste nell ambiente 4 4 1 Connessione batterie interne Tensione di batteria L installazione della batteria dovrà essere eseguita dopo aver allacciato i seguenti conduttori Alimentazione AC ingresso raddrizzatore Alimentazione AC ingresso bypass Uscita UPS Nel caso in cui si utilizzino cablaggi non ...

Page 1188: ...llazione batterie 7 9 11Ah 12V KEOR HPE 60 80kVA 1 Rimuovere le sei viti per aprire i pannelli laterali destro sinistro e accedere ai vassoi batterie Totale ripiani 6 e ognuno è composto da tre cassetti di batteria Fig 9 10 1a Rimuovere la protezione di cartone sopra tutti i ripiani delle batterie Figura 9 Cassetti batterie 7 9 11Ah 12V vista laterale KEOR HPE 60kVA Figura 10 Cassetti batterie 7 9...

Page 1189: ...portate dal punto 18 al punto 23 di questo capitolo 1 Collegare i 3 cavi B su terminale di batteria con configurazione 180 186 batterie 2A Collegare i 2 cavi B su terminale di batteria con configurazione 120 124 batterie 2 Collegare i 3 cavi N su terminale di neutro batteria con configurazione 180 186 batterie 3A Collegare i 2 cavi N su terminale di neutro batteria con configurazione 120 124 batte...

Page 1190: ...i 1 e 3 i ponticelli cerchiati non siano collegati lasciare scollegati i ponticelli cerchiati 6 Cablare il piano n 1 come indicato nella figura 13 Lasciare scollegati i ponticelli cerchiati Figura 12 Vista dall alto Piano N 1 Figura 13 Vista dall alto Piano N 1 con connessioni batterie LATO POSTERIORE UPS LATO FRONTALE UPS LATO FRONTALE UPS LATO POSTERIORE UPS LATO POSTERIORE UPS Link interconness...

Page 1191: ...ei cassetti 4 e 6 i ponticelli cerchiati non siano collegati lasciare scollegati i ponticelli cerchiati 8 Cablare il piano n 2 come indicato nella figura 15 Lasciare scollegati i ponticelli cerchiati 9 Figura 14 Vista dall alto Piano N 2 Figura 15 Vista dall alto Piano N 2 con connessioni batterie LATO FRONTALE UPS LATO FRONTALE UPS LATO POSTERIORE UPS LATO POSTERIORE UPS Link interconnessione Int...

Page 1192: ...llegati lasciare scollegati i ponticelli cerchiati 10 Cablare il piano come indicato nella figura 17 Lasciare scollegati i ponticelli cerchiati Figura 17 Vista dall alto Piano N 3 con connessioni batterie LATO POSTERIORE UPS LATO POSTERIORE UPS Link interconnessione Link interconnesione tra cassetti 9 e 10 L ink interconnesione L ink interconnesione LATO POSTERIORE UPS Figura 16 Vista dall alto Pi...

Page 1193: ...e nei cassetti 10 e 12 i ponticelli cerchiati non siano collegati lasciare scollegati i ponticelli cerchiati 12 Cablare il piano come indicato nella figura 19 Lasciare scollegati i ponticelli cerchiati Figura 19 Vista dall alto Piano N 4 con connessioni batterie LATO FRONTALE UPS LATO FRONTALE UPS LATO POSTERIORE UPS LATO POSTERIORE UPS Link interconnessione Interconnessioni tra cassetti 9 e 10 L ...

Page 1194: ...nei cassetti 13 e 15 i ponticelli cerchiati non siano colegati lasciare scollegati i ponticelli cerchiati 14 Cablare il piano come indicato nella figura 21 Lasciare scollegati i ponticelli cerchiati Figura 20 Vista dall alto piano N 5 Figura 21 Vista dall alto Piano N 5 con connessioni batterie LATO FRONTALE UPS LATO FRONTALE UPS LATO POSTERIORE UPS LATO POSTERIORE UPS Link interconnessione Link i...

Page 1195: ...ponticello cerchiato e inserendo i ponticelli come mostrato nella figura 23 NOTE Controllare che nel cassetto 16 il ponticello cerchiato non sia collegato lasciare scollegato il ponticello cerchiato Figura 22 Vista dall alto piano N 6 Figura 23 Vista dall alto piano N 6 cassetti 16 17 LATO FRONTALE UPS LATO FRONTALE UPS LATO POSTERIORE UPS LATO POSTERIORE UPS Link interconnessione Link interconnes...

Page 1196: ...vendo il ponticello cerchiato e inserendo i ponticelli come mostrato nella figura 24 NOTE Controllare che nel cassetto 18 il ponticello cerchiato non sia collegato se collegato rimuovere il ponticello cerchiato Figura 24 Vista dall alto piano N 6 con connesioni batterie LATO FRONTALE UPS LATO POSTERIORE UPS Link interconnessione Interconnessioni tra cassetti 16 e 15 Link interconnesione SOLO PER B...

Page 1197: ... lato destro dell UPS estrarre parzialmente il cassetto n 1 e inserire il ponticello mancante come indicato in figura 25 Figura 25 Vista dall alto piano N 1 con connessioni batterie Tensione di batteria ATTENZIONE TENSIONE PERICOLOSA Dopo la chiusura del ponticello sarà presente una tensione pericolosa sui terminali di batteria rappresentati in figura11 20 Ripetere l operazione per i cassetti n 4 ...

Page 1198: ...e dimostrato in figura 26 utilizzare un multimetro per verificare che non sia presente una tensione CC tra i terminali delle batterie 22 Ripetere l operazione per i cassetti n 6 9 12 15 18 Fig 9 10 23 Verificare la corretta polarità sui morsetti di batteria Figura 27 Terminali batteria Figura 26 Vista dall alto piano N 1 con connessioni batterie LATO FRONTALE UPS LATO POSTERIORE UPS Link interconn...

Page 1199: ...Ah 12V KEOR HPE 60 80kVA 1 Rimuovere le 6 viti per aprire i pannelli laterali destro sinistro e accedere ai vassoi batterie Totale ripiani 6 e ognuno è composto da tre cassetti di batteria Fig 28 29 1a Rimuovere la protezione di cartone sopra tutti i ripiani delle batterie Figura 28 Cassetti batterie 12 14Ah 12V vista laterale KEOR HPE 60kVA Figura 29 Cassetti batterie 12 14Ah 12V vista laterale K...

Page 1200: ...all interno dell UPS A Eseguire le operazioni come indicato nella seguente etichetta installata internamente all UPS Figure 30 Avvertenze per batterie interne B Seguire le istruzioni riportate dal punto 18 al punto 23 di questo capitolo 2 Collegare i 2 cavi B su terminale di batteria 3 Collegare i 2 cavi N su terminale di neutro batteria 4 Collegare i 2 cavi B su terminale di batteria Figura 30A T...

Page 1201: ...ei cassetti 1 e 3 i ponticelli cerchiati non siano collegati lasciare scollegati i ponticelli cerchiati 6 Cablare il piano n 1 come indicato nella figura 32 Lasciare scollegati i ponticelli cerchiati Figura 31 Vista dall alto Piano N 1 Figura 32 Vista dall alto Piano N 1 con connessioni batterie LATO FRONTALE UPS LATO FRONTALE UPS LATO POSTERIORE UPS LATO POSTERIORE UPS Link interconnessione Link ...

Page 1202: ... 6 i ponticelli cerchiati non siano collegati lasciare scollegati i ponticelli cerchiati 8 Cablare il piano n 2 come indicato nella figura 34 Lasciare scollegati i ponticelli cerchiati Figura 33 Vista dall alto Piano N 2 Figura 34 Vista dall alto Piano N 2 con connessioni batterie LATO FRONTALE UPS LATO FRONTALE UPS LATO POSTERIORE UPS LATO POSTERIORE UPS Link interconnessione Interconnessioni tra...

Page 1203: ...5 NOTE Controllare che nei cassetti 7 e 9 i ponticelli cerchiati non siano collegati lasciare scollegati i ponticelli cerchiati 10 Cablare il piano come indicato nella figura 36 Lasciare scollegati i ponticelli cerchiati Figura 35 Vista dall alto Piano N 3 Figura 36 Vista dall alto Piano N 3 con connessioni batterie LATO FRONTALE UPS LATO FRONTALE UPS LATO POSTERIORE UPS LATO POSTERIORE UPS Link i...

Page 1204: ...nei cassetti 10 e 12 i ponticelli cerchiati non siano collegati lasciare scollegati i ponticelli cerchiati 12 Cablare il piano come indicato nella figura 38 Lasciare scollegati i ponticelli cerchiati Figura 37 Vista dall alto Piano N 4 Figura 38 Vista dall alto Piano N 4 con connessioni batterie LATO FRONTALE UPS LATO POSTERIORE UPS LATO POSTERIORE UPS LATO FRONTALE UPS Link interconnessione Link ...

Page 1205: ...o collegati lasciare scollegati i ponticelli cerchiati 14 Cablare il piano come indicato nella figura 40 Lasciare scollegati i ponticelli cerchiati Figura 39 Vista dall alto Piano N 5 Figura 40 Vista dall alto Piano N 5 con connessioni batterie LATO FRONTALE UPS LATO FRONTALE UPS LATO POSTERIORE UPS LATO POSTERIORE UPS Link interconnessione Interconnessioni tra cassetti 12 e 13 L ink interconnesio...

Page 1206: ...Figura 41 Vista dall alto piano N 6 16 Inserire il cassetto n 16 rimuovendo il ponticello cerchiato e inserendo i ponticelli come mostrato nella figura 42 NOTE Controllare che nel cassetto 16 il ponticello cerchiato non sia collegato lasciare scollegato il ponticello cerchiato Figura 42 Vista dall alto piano N 6 cassetti 16 17 LATO FRONTALE UPS LATO FRONTALE UPS LATO POSTERIORE UPS LATO POSTERIORE...

Page 1207: ...o n 18 rimuovendo il ponticello cerchiato e inserendo i ponticelli come mostrato nella figura 43 NOTE Controllare che nel cassetto 16 il ponticello cerchiato non sia collegato lasciare scollegato il ponticello cerchiato Figura 43 Vista dall alto piano N 6 con connesioni batterie LATO FRONTALE UPS LATO POSTERIORE UPS Link interconnessione Interconnessioni tra cassetti 15 e 16 Link interconnesione ...

Page 1208: ...lato destro dell UPS estrarre parzialmente il cassetto n 1 e inserire il ponticello mancante come indicato in figura 44 Figura 44 Vista dall alto piano N 1 con connessioni batterie Tensione di batteria ATTENZIONE TENSIONE PERICOLOSA Dopo la chiusura del ponticello sarà presente una tensione pericolosa sui terminali di batteria rappresentati in figura 30 20 Ripetere l operazione per i cassetti n 4 ...

Page 1209: ...ome dimostrato in figura 45 utilizzare un multimetro per verificare che non sia presente una tensione CC tra i terminali di batteria 22 Ripetere l operazione per i cassetti n 6 9 12 15 18 Fig 28 29 23 Verificare la corretta polarità sui morsetti di batteria Figura 46 Terminali batteria Figura 45 Vista dall alto piano N 1 con connessioni batterie LATO FRONTALE UPS LATO POSTERIORE UPS Link interconn...

Page 1210: ...ssa elettrica La probabilità può essere ridotta se i collegamenti di terra vengono interrotti durante l installazione e la manutenzione applicabile ad apparecchiature e ad alimentazioni a batteria poste a distanza prive di circuito di alimentazione messo a terra Installazione batterie Per l installazione delle batterie attenersi rigorosamente alle EN62040 1 paragrafo 7 6 Per ottenere una durata di...

Page 1211: ...rgenti di calore La batteria potrebbe esplodere ATTENZIONE non aprire il contenitore delle batterie L elettrolito rilasciato è pericoloso per la pelle e per gli occhi Può essere tossico ATTENZIONE non gettare le batterie esauste nell ambiente 4 6 1 Connessione batterie esterne Tensione di batteria L installazione della batteria dovrà essere eseguita dopo aver allacciato i seguenti conduttori Alime...

Page 1212: ...ica e la presenza di appropriate protezioni tra armadio batterie e KEOR HPE 60 80kVA 111 Leggere attentamente la sezione Schema di collegamento Armadio batterie esterno della sezione installazione batterie Per evitare il rischio di interferenze elettromagnetiche separare i cavi della batteria dai cavi di ingresso e uscita111 1 ELEVATA TENSIONE nominale di 720 VDC è presente quando sosno state coll...

Page 1213: ...terminale di batteria Fig 46 4 Collegare il contatto ausiliario del sezionatore BCB ESTERNO sull apposito ingresso disponibile all interno dell UPS vedi foto sotto Figura 49 Cablaggio opzione Battery Internal External 5 Dopo aver verificato il collegamento e il cablaggio dell armadio batteria esterno chiudere BCB dell armadio batteria esterno e verificare che la tensione e la polarità siano corret...

Page 1214: ...60 80 kVA 4 7 1 Contatto ausiliario sezionatore di batteria Contatto ausiliario del sezionatore di Batteria morsetti X10 1 2 Contatto ausiliario necessario per l indicazione della posizione del sezionatore aperto chiuso 4 7 2 Contatto ausiliario Generatore Diesel Contatto ausiliario proveniente da gruppo elettrogeno morsetti X10 3 4 Deve essere utilizzato un contatto normalmente aperto il contatto...

Page 1215: ...zata per il collegamento con software proprietario di programmazione e controllo SRC 2 scheda relè utilizzata per la ripetizione a distanza di stati di funzionamento e allarmi EXT INP utilizzata per la connessione dei contatti esterni PARALLELO OPZIONALE utilizzata per la comunicazione tra UPS in configurazione parallelo MODBUS OPZIONALE utilizzata per la trasmissione dei dati all esterno per mezz...

Page 1216: ...in Stato in funzionamento normale Nome Stato in funzionamento normale RL1 Allarme A30 ALLARME GENERALE Non energ se allarme presente 2 3 Chiuso DL1 On 1 2 Aperto RL2 Allarme A1 MANCANZA RETE Non energ se allarme presente 5 6 Chiuso DL2 On 4 5 Aperto RL3 Allarme A9 FINE AUT BATTERIA Non energ se allarme presente 8 9 Chiuso DL3 On 7 8 Aperto RL4 Allarme A13 INV FUORI TOL Non energ se allarme present...

Page 1217: ...PE UPS 60 80 kVA 201 OMW07096 REV E 5 11 COLLEGAMENTO SCHEDA EXT INP L UPS KEOR HPE 60 80 kVA nella sua configurazione completa è provvisto di una scheda relè per la connesione dei contatti esterni Il collegamento elettrico è realizzato direttamente sui morsetti sul fronte dello slot di interfaccia EXT INP Figura 53 Morsetti scheda EXT INP ...

Page 1218: ...che seguono fanno riferimento al dispositivo di interruzione BCB BCB INTERNO con configurazione batterie interne BCB INTERNO e ESTERNO con configurazione batterie esterne e i suoi contatti ausiliari opportunamente cablati agli appositi morsetti nell UPS 5 1 VERIFICHE PRELIMINARI Prima di iniziare la procedura di avvio verificare che tutti i lavori di installazione e allacciamento elettrico siano s...

Page 1219: ...i bypass manuale uscita e batteria che vanno collegati agli appositi morsetti sull UPS In questo modo la logica di controllo acquisisce lo stato degli interruttori per guidare l operatore durante le procedure di avvio e bypass manuale No DISPLAY LCD AZIONE CONTROLLI OPERATIVI 1 SPENTO Chiudere RCB Alla chiusura del sezionatore RCB inizia la fase di precarica del banco capacitivo con l avvio della ...

Page 1220: ...chiusura statico SSI 9 AVVIO BYPASS CHIUDI SBCB Chiudere SBCB 10 AVVIO BYPASS ATTENDERE PREGO La logica di controllo verifica che tutti i parametri di bypass tensione senso ciclico frequenza siano corretti LED 2 acceso verde presenza tensione Bypass 11 AVVIO BATTERIA CHIUDI BCB Chiudere BCB 12 AVVIO BATTERIA ATTENDERE PREGO La logica di controllo verifica la chiusura dell interruttore per passare ...

Page 1221: ...erno dell UPS 2 Dopo lo step 1 l UPS blocca la sequenza d avvio e mostra uno o più messaggi di allarme Verificare gli allarmi che sono indicati a display e risolverne le cause Chiudere RCB e provare a riavviare l UPS 3 Dopo lo step 2 l UPS mostra l allarme A15 Byp non disp Verificare di aver chiuso il sezionatore SBCB Controllare I fusibili di protezione static switch Bypass sono installati all in...

Page 1222: ...TROLLI OPERATIVI 1 Aprire OCB A30 ALLARME GENERALE L alimentazione al carico viene interrotta LED 7 spento 2 Aprire BCB A30 ALLARME GENERALE La batteria viene disconnessa dal raddrizzatore LED 4 rosso lampeggiante 3 Aprire SBCB A30 ALLARME GENERALE L alimentazione di bypass viene disconnessa LED 2 spento 4 Aprire RCB A30 ALLARME GENERALE Arresto del Raddrizzatore e dell Inverter 5 SPENTO Fine dell...

Page 1223: ...ne sui carichi No AZIONE DISPLAY LCD CONTROLLI OPERATIVI 1 Muovere il selettore Bypass_SW su BYPASS A30 ALLARME GENERALE Il carico viene trasferito sulla linea di bypass LED 5 spento LED 6 acceso arancio 2 Chiudere MBCB A30 ALLARME GENERALE L inverter viene spento Il carico viene alimentato dalla rete d ingresso tramite l interruttore di bypass manuale L interruttore statico di bypass è ancora chi...

Page 1224: ...nello frontale sono accesi Il microprocessore controlla che tutte le condizioni di avvio siano buone per il riavvio LED 1 accesi verdi LED 8 acceso arancio 5 AVVIO RADDRIZZATORE ATTENDERE PREGO Il ponte Raddrizzatore ad IGBT inizia a modulare la tensione VDC viene portata al valore nominale accensione del LED 3 acceso verde presenza tensione DC 6 AVVIO DA MBCB CHIUDERE SBCB Chiudere SBCB 7 AVVIO B...

Page 1225: ...te inverter e la tensione AC viene portata al valore nominale Il microprocessore controlla la sincronizzazione con la linea di by pass 12 AVVIO DA MBCB MUOVERE BYP SWITCH Muovere il selettore NORMAL BYPASS su NORMAL Il carico è trasferito sotto inverter LED 5 acceso verde 13 AVVIO TERMINATO ATTENDERE PREGO Il microprocessore controlla che tutti i parametri di uscita tensione corrente frequenza sia...

Page 1226: ...EL DE L UTILISATEUR DE L ASI UTILIZZO DELL UPS Index Indice ENGLISH LANGUAGE 9 SCOPE 11 SAFETY RULES AND WARNINGS 12 GENERAL UPS DESCRIPTION 13 TYPOLOGY 13 SYSTEM DESCRIPTION 13 3 2 1 Rectifier 13 3 2 2 Inverter 14 3 2 3 Battery and battery charger 14 3 2 4 Static bypass 14 3 2 5 Manual bypass 14 OPERATING STATUS 15 3 3 1 Normal operation 15 3 3 2 Green Conversion 15 3 3 3 Bypass operation 16 3 3 ...

Page 1227: ...story 29 5 3 2 Alarms and operating status 30 SETTINGS AND ADVANCED OPERATIONS 32 SETTING DATE AND TIME 34 DISPLAY LANGUAGE SETTING 34 NEW BATTERY INSTALLATION 34 BATTERY CONFIGURATION 34 SETTING THE MODBUS PARAMETERS 36 UPS TEST 36 BATTERY TEST 37 SYSTEM RESET 37 ALARMS HISTORY RESET 38 SYSTEM INFORMATION 39 PARALLEL OPERATION INFORMATION 40 7 1 1 UPS position 40 7 1 2 Master Slave priority 40 7 ...

Page 1228: ...ME 63 3 2 1 Redresseur 63 3 2 2 Onduleur 63 3 2 3 Batterie et chargeur de batterie 64 3 2 4 By pass statique 64 3 2 5 Bypass manuel 64 3 3 ÉTAT DE FONCTIONNEMENT 65 3 3 1 Fonctionnement normal 65 3 3 2 Conversion Green 65 3 3 3 Fonctionnement en by pass 66 3 3 4 Fonctionnement sur batterie 67 3 3 5 Bypass manuel 67 3 4 DISPOSITIFS DE CONTROLE ET DE FONCTIONNEMENT 69 3 4 1 Sectionneurs d isolation ...

Page 1229: ... BATTERIE 87 6 8 RÉINITIALISATION DU SYSTÈME 87 6 9 REMISE A ZERO DE L HISTORIQUE DES ALARMES 89 7 INFORMATIONS SYSTÈME 90 7 1 INFORMATIONS SUR LE FONCTIONNEMENT EN PARALLELE 91 7 1 1 Position de l ASI 91 7 1 2 Hiérarchie maitre esclave 91 7 1 3 Surveillance du bus de communication 92 7 1 4 Type de système parallèle 92 7 1 5 Statistiques relatives aux messages 92 7 2 INFORMATIONS SUR LE FONCTIONNE...

Page 1230: ...to da bypass 118 3 3 4 Funzionamento da batteria 118 3 3 5 Bypass manuale 119 3 4 COMANDI E ORGANI DI MANOVRA 121 3 4 1 Sezionatori 121 3 4 2 Comando di arresto di emergenza EPO 122 3 4 3 Selettore Normale Bypass 122 3 4 4 Pannello di comando LCD 122 4 PANNELLO FRONTALE 123 4 1 TASTI FUNZIONE 124 4 2 LED DEL SINOTTICO 125 4 3 BARRA LED 126 5 GESTIONE DEL PANNELLO LCD 127 5 1 MENU PRINCIPALI 127 5 ...

Page 1231: ...MENTO IN PARALLELO 142 7 1 1 Posizione dell UPS 142 7 1 2 Priorità Master Slave 142 7 1 3 Controllo bus di comunicazione 143 7 1 4 Tipo di parallelo 143 7 1 5 Statistiche messaggi 144 7 2 INFORMAZIONI SUL FUNZIONAMENTO IN PARALLELO RADDRIZZATORE 144 7 2 1 Posizione dell UPS 144 7 2 2 Priorità Master Slave 144 7 2 3 Controllo bus di comunicazione 145 7 2 4 Tipo di parallelo 145 7 2 5 Statistiche me...

Page 1232: ...39 Illustration 1 Schéma bloc 63 Illustration 2 Fonctionnement normal 65 Illustration 3 Green Conversion 65 Illustration 4 Charge alimentée par bypass 66 Illustration 5 Fonctionnement sur batterie 67 Illustration 6 Bypass manuel pour vérification fonctionnelle 67 Illustration 7 By pass manuel pour réparations ou maintenance 68 Illustration 8 Panneau avant de l ASI 71 Illustration 9 Tableau à schém...

Page 1233: ...ura 7 By pass manuale per manutenzione o riparazione 120 Figura 8 Pannello frontale UPS 123 Figura 9 Sinottico UPS 125 Figura 10 Barra LED 126 Figura 11 Struttura menu MISURE 1 di 2 128 Figura 12 Struttura menu MISURE 2 di 2 129 Figura 13 Struttura menu allarmi 130 Figura 14 Struttura menu SPECIALE 134 Figura 15 Struttura menu INFO 141 ...

Page 1234: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMW07104 REV A 9 ENGLISH LANGUAGE ...

Page 1235: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 10 OMW07104 REV A ...

Page 1236: ...6 KEOR HPE 80 kVA Storing documentation This manual and any other supporting technical documentation relating to the product must be stored and made accessible to personnel in the immediate vicinity of the UPS Further information In the event that the information provided in this manual is not sufficiently exhaustive please contact the manufacturer of the device whose details are available in the ...

Page 1237: ...ed in the manuals must be strictly followed Injury hazard due to device failure Potentially hazardous situations may arise in case of UPS failure Do not use the device if visibly damaged Maintain the device regularly to identify possible failure Possible device damage Whenever work is carried out on the device make sure all actions are taken in order to avoid electrostatic discharges which might d...

Page 1238: ...line or the plugs supplied by the UPS making the User aware of this fact Picture 1 Block diagram The UPS uses IGBT technology with a high switching frequency in order to allow a low distortion of the current re injected into the supply line as well as high quality and stability of output voltage The components used assure high reliability very high efficiency and maintenance easiness SYSTEM DESCRI...

Page 1239: ...ic is completely integrated in the rectifier s control electronics The battery is charged according to the DIN 41773 Standard every time it has been partially or completely discharged When its full capacity is restored it is disconnected from the DC bus by means of a static switch in order to save energy reduce the stress due to the AC ripple thus increasing the lifetime This operating mode is cal...

Page 1240: ...e inverter and compensates mains voltage as well as load variations keeping the DC voltage constant At the same time it provides to charge the battery The inverter converts the DC voltage into an AC sine wave with stabilized voltage and frequency and also supplies the load via its static switch SSI Picture 2 Normal operation 3 3 2 Green Conversion During the operation in Green Conversion mode the ...

Page 1241: ...st capacity 20 Additional charge for 96 hours Such values complies with the recommendations of the main battery manufacturers Set the right battery capacity The UPS front panel allows the setting of the battery parameters including the rated capacity Considering the importance that such value assumes for the correct execution of the charge control algorithm it is highly recommended to verify the c...

Page 1242: ...restart from the black out condition can be customized based on the requirements of the plant in three different modes Bypass loads are supplied as soon as the bypass line is available factory configuration Inverter loads are supplied by the inverter even if the bypass line is available when the battery voltage has reached a programmed threshold after the rectifier restart Man Inverter the output ...

Page 1243: ...auxiliary contacts Carry out a proper electrical installation by wiring the auxiliary contacts of the manual bypass and output isolators to the dedicated terminals on board the UPS This will allow the control logic to acquire the status of the switches and guide the operator during the start up and manual bypass procedures For further information refer to the section Installation and start up Duri...

Page 1244: ...ol devices of the UPS is intended for authorized personnel only We recommend to check the training of the personnel responsible for the use and maintenance of the system 3 4 1 Isolators The isolators provided on the UPS are used to isolate the power components of the device from the AC supply line from the storage battery and from the load Voltage present on terminals The isolators do not isolate ...

Page 1245: ...d you are sure that there is no hazard to persons and things 3 4 3 Normal Bypass selector It is used during the manual bypass procedure when it is necessary to isolate the UPS for maintenance or repair Follow the procedures contained in the manual The Normal Bypass selector shall only be operated in accordance with the procedures specified in the installation and start up section The manufacturer ...

Page 1246: ...S OMW07104 REV A 21 FRONT PANEL The front panel of the UPS consisting of four rows alphanumeric display plus 5 function keys allows the complete monitoring of the UPS status The mimic flow helps to understand the operating status of the UPS Picture 8 UPS front panel ...

Page 1247: ... 5 buttons whose functions are indicated in the following table Button Assigned functions Scrolls up the menus Increases the values by one unit Selects a value Scrolls down the menus Decreases the values by one unit Selects a value Selects a menu Confirms changes Silences the buzzer activated due to an alarm or a failure Returns to the previous menu ...

Page 1248: ...EEN Battery discharging or under TEST ORANGE Circuit breaker BCB open RED Battery fault following a battery test OFF Battery not available LED 5 GREEN Inverter voltage within tolerance and static switch closed GREEN Inverter overload or short circuit OFF Inverter off or voltage out of tolerance LED 6 ORANGE Re transfer blocked ORANGE Static bypass switch closed OFF Static bypass switch open LED 7 ...

Page 1249: ...harging ORANGE Battery discharging or under TEST fast blinking ORANGE Circuit breaker BCB open slow blinking RED End of battery autonomy Battery fault LED 13 GREEN Inverter voltage within tolerance and static switch closed ORANGE Inverter overload or short circuit RED Inverter critical alarm OFF Inverter off LED 14 GREEN AC bypass line within tolerance RED Wrong phase rotation fast blinking RED AC...

Page 1250: ...S NAME Main screen nominal power of the UPS xxx kVA UPS NAME UPS measures regarding basic parameters voltage current etc MEASURES UPS NAME UPS operating status possible alarms present and alarms history ALARMS UPS NAME Setting of parameters and special functions SPECIAL UPS NAME General information regarding the UPS INFO ...

Page 1251: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 26 OMW07104 REV A MEASURE DISPLAY The MEASURES menu is structured as follows Picture 11 Structure of MEASURES menu 1 of 2 ...

Page 1252: ...ent 3 1 A Frequency 0 1 Hz Active power 1 kW Apparent power 1 kVA Load percentage 1 BYPASS Voltage 1 2 1 V Frequency 0 1 Hz INVERTER Voltage 1 2 1 V Frequency 0 1 Hz AC DC Rectifier output voltage 1 V BATTERY Voltage and current 1 V 1 A Nominal capacity 1 Ah Residual autonomy 1 min 1 1 The voltage measures are always referred to the phase to neutral value 2 The three voltages are displayed in one ...

Page 1253: ... ALARMS menu automatically whenever an alarm occurs The audible indicator if enabled is activated to show the occurred failure The audible alarm is silenced pressing the key BUZZER UPS STATUS Display of the first alarm present if no alarm is present the operating status is displayed alarm status no 1 UPS STATUS Press the key to browse the menu and to go to the next alarm status in alphabetical ord...

Page 1254: ...g the oldest event The quantity of stored events is displayed on the first line xxx yyy which contains the data currently displayed position in the list and the total number of stored data maximum number equal to 500 respectively An asterisk indicates the automatic reset of the alarm HISTORY 001 015 Latest event stored in order of time E g automatic reset of alarm A3 BOOSTER STOPPED A3 26 10 10 20...

Page 1255: ...RATION A14 BYPASS WR SEQ A46 PAR LOST REDUND A15 BYPASS FAULT A47 SEND PARAM ERROR A16 BYPASS LOAD A48 RCV PARAM ERROR A17 RETRANSFER BLOCK A49 TEST MODE ERROR A18 MBCB CLOSED A51 BATT TEMPERATURE A19 OCB OPEN A52 UNDER VOLTAGE LOCKOUT A20 OVERLOAD A53 FIRMWARE ERROR A21 THERMAL IMAGE A54 CAN ERROR A22 BYPASS SWITCH A55 PAR CABLE DISC A23 EPO PRESSED A56 MAINS UNBALANCE A24 HIGH TEMPERATURE A59 BA...

Page 1256: ... ALARMS STATUSES menu is entered The alarms are shown when they are present and must be silenced with the buzzer The alarms remain displayed whilst they are present and they are automatically stored in the event log with date and time Description of alarms and statuses For a more detailed description of the alarms and statuses see the Faults and alarms section of the present manual ...

Page 1257: ...l utilisateur de l ASI Utilizzo dell UPS 32 OMW07104 REV A SETTINGS AND ADVANCED OPERATIONS Some operating parameters of the UPS can be set via the SPECIAL menu which is structured as follows Picture 14 Structure of SPECIAL menu ...

Page 1258: ...s a battery test NEW BATTERY INSTALL Sets autonomy to 100 RESET HISTORY Event log reset MODBUS MODBUS address of device RESET RUNNING HOURS Reset the hour counter related to the UPS running time Password protected access The SETTINGS menu is protected by a password set by the factory in order to prevent access to unauthorized personnel We recommend minimum disclosure of the access password Changes...

Page 1259: ... parameters are changed via the arrow buttons to increase the digits and the button is used to confirm the entry NEW BATTERY INSTALLATION The NEW BATTERY INSTALLATION menu is used in case battery circuit breaker BCB is not closed when requested in the start up phase In this case the system will start considering the battery completely discharged and activating the alarm A10 BATTERY FAULT To set th...

Page 1260: ...reen of the parameter set YES BAT RECHAR CURR SET The single digits can be modified via the arrow keys and confirmed by pressing ENTER 18 CONFIRM RECHAR CURR Confirmation screen of the parameter set YES AUTONOMY BAT SETTING The single digits can be modified via the arrow keys and confirmed by pressing ENTER 0020 CONFIRM AUTON BATT Confirmation screen of the parameter set YES SAVE BATT SETTINGS Con...

Page 1261: ...e modified via the arrow keys and confirmed by pressing ENTER 202 Parameter Standard Range MODBUS ADDRESS 1 1 247 UPS TEST The UPS TEST menu allows to carry out a switching test of the inverter The inverter is switched off and the load is transferred to the bypass supply The inverter supply is automatically restored after a few seconds UPS TEST The value on the second line is ready to be changed N...

Page 1262: ...ssible loss of supply This test can affect the continuity of supply to the loads if the battery is not fully charged SYSTEM RESET The UPS is equipped with internal protections which block the system or some of its sections The alarm can be cleared and normal operation can be resumed via the RESET menu In case the failure persists the UPS will return to the previous failure condition In some cases ...

Page 1263: ...trol loop error alarm A43 Static switch blocked alarm A50 Booster shutdown due to the operation of the load symmetry sensor alarm A33 Activation of the battery fault alarm alarm A10 Scheduled maintenance request alarm A29 For a description of the UPS status in each of the failure conditions listed above please refer to the Faults and alarms section ALARMS HISTORY RESET Access the RESET HISTORY men...

Page 1264: ...ormation regarding the UPS based on the structure indicated below Picture 15 Structure of INFO menu All data shown in the various sections are set by the factory via a special interface software and cannot be altered except by personnel authorized by the manufacturer The only adjustable parameters are the MODBUS settings see SPECIAL menu ...

Page 1265: ...ding technical service RUNNING HOURS Dates related to hours number of UPS running time 1 the menu is only active if the UPS belongs to a Parallel or Load Sync system 2 the menu is only active if the UPS belongs to a common battery system PARALLEL OPERATION INFORMATION The PARALLEL menu is only active if the UPS belongs to a parallel or load sync system 7 1 1 UPS position PARALLEL 2 6 The first num...

Page 1266: ...PS units UPS2 is currently the MASTER UPS we are checking the data communication on UPS3 UPS4 is not communicating The menu will be as shown below PARALLEL 1 S 2 M 3 S 4 In case there are more than four paralleled devices the menu will be as follows PARALLEL 1 S 2 M 3 S The dots indicate the presence of a further menu which shows the status of the other UPS units in the system 7 1 4 Parallel type ...

Page 1267: ... the number will only increase on the SLAVE UPS units CAN STATISTICS INV MSG RX 9277 99 9 Number of messages received and percentage of reception accuracy regarding the status of the system The messages are exchanged between all the UPS units therefore the number will increase on all of them PARALLEL RECTIFIER OPERATION INFORMATION The PARALLEL menu is only active if the UPS belongs to a parallel ...

Page 1268: ... by number X For example in a system composed of 2 UPS units REDUNDANT 1 means that only one of the UPS units is sufficient to feed the load 7 2 5 Message statistics The statistics section regarding the messages exchanged on the communication buses consists of two different menus CAN STATISTICS RAD SYNC RX 15849 100 0 Number of messages received and percentage of reception accuracy regarding the s...

Page 1269: ...YPASS FAULT 1x UPS STATUS The other alarms present are displayed by scrolling the menu A30 COMMON ALARM UPS STATUS After the last alarm present the operating statuses are displayed S1 BOOSTER OK Injury hazard due to electric shock Before carrying out any operation on the UPS make sure that all the safety precautions are adhered to Any work on the unit must be carried out by qualified personnel Int...

Page 1270: ...n The inverter is ready to feed the load Status S4 INVERTER LOAD Description The inverter feeds the load Operating condition The load is fed via the static inverter switch Status S5 INV BYPASS SYNC Description The inverter is synchronized with the bypass Operating condition The synchronization between the inverter and the bypass is locked and the static switch can change over from one source to th...

Page 1271: ... is in standby mode Operating condition The inverter is off and ready to be started in case of anomaly of the bypass mains Status S12 BATT STANDBY NOT AVAILABLE Description The battery is in standby mode Operating condition The battery static switch is open and the battery is disconnected from the DC bus Status S14 BATT CHARGE I Description The battery is charging Operating condition The battery s...

Page 1272: ...the phase rotation If the alarm persists contact our Technical Support Service Alarm A3 BOOSTER STOPPED Description The rectifier has been temporarily disconnected and the inverter is fed by the battery Possible causes Instability of the AC line voltage or frequency Possible fault in the rectifier control circuit Solutions Check the parameters of the AC line voltage Restart the device If the alarm...

Page 1273: ...e of the battery Possible causes A battery test has been started automatically if set or manually by the user Solutions Wait for the test to end and check possible battery faults Alarm A7 BCB OPEN Description The battery isolator is open Possible causes Battery isolator open Solutions Check the status of the battery isolator Check the functionality of the auxiliary contact of the isolator Check th...

Page 1274: ...cted a short circuit at the output Possible causes Load problem Measuring circuit failure Solutions Check the loads connected to the UPS output If the alarm persists contact our Technical Support Service Alarm A12 STOP TIMEOUT SC Description Inverter shutdown due to an extended short circuit during a power failure or due to an overcurrent on the inverter bridge input Possible causes Short circuit ...

Page 1275: ...D Description The load is fed by the bypass line Possible causes Temporary changeover due to inverter failure Solutions Verify the inverter status and check whether other alarms are present If the alarm persists contact our Technical Support Service Alarm A17 RETRANSFER BLOCK Description The load is blocked on the bypass line Possible causes Very frequent changeovers due to load in rush currents S...

Page 1276: ...l image protection has been activated after an extended inverter overload The inverter is shut down for 30 minutes and then restarted Possible causes Output overload Measuring circuit failure Solutions 1 Check the loads connected to the UPS output 2 Should you need to restore the inverter supply immediately reset the system 3 If the alarm persists contact our Technical Support Service Alarm A22 BY...

Page 1277: ...scription The inverter is blocked due an operation failure Possible causes Various Solutions Reset the system If the alarm persists contact our Technical Support Service Alarm A26 COMMUNIC ERROR Description Internal error Possible causes Microcontroller communication problems Solutions If the alarm persists contact our Technical Support Service Alarm A27 EEPROM ERROR Description The controller has...

Page 1278: ...the status of the manual bypass isolator Check the functionality of the auxiliary contact of the isolator If the alarm persists contact our Technical Support Service Alarm A32 EPO BUS CLOSED Description The system is blocked due to the activation of the emergency power off button Possible causes Activation of the local or remote emergency power off button Solutions Release the emergency power off ...

Page 1279: ...escription Inverter shutdown due to the operation of the protection sensor as a result of sudden DC voltage variations Possible causes Battery fault Solutions Check the battery Reset the system If the alarm persists contact our Technical Support Service Alarm A38 INV LOAD Description The load is fed by the inverter This alarm is active for UPS systems in ECO mode where the preferential supply is f...

Page 1280: ...the system If the alarm persists contact our Technical Support Service Alarm A44 DESATURATION NOT AVAILABLE Description The inverter is blocked due to the operation of the desaturation sensor of the IGBT drivers Possible causes Inverter bridge fault Solutions 1 Reset the system 2 If the alarm persists contact our Technical Support Service Alarm A46 PAR LOST REDUND Description This alarm is only ac...

Page 1281: ...us temperature in the battery cabinet Possible failure on the measuring circuit Solutions Check the temperature on the batteries and remove the cause of the alarm if any If the alarm persists contact our Technical Support Service Alarm A52 UNDER VOLTAGE LOCKOUT Description The inverter is blocked because of an anomaly on the control power supply Possible causes Internal error Solutions 1 Contact o...

Page 1282: ...ssible causes Problems on the bypass static switch Solutions Check the static switch thyristors Contact our Technical Support Service Alarm A61 MAX VDC Description The alarm is activated when the DC voltage exceeds 910 V 455 V for each capacitors bank The alarm must be manually reset by display Possible causes Rectifier shuts down alarm A3 Inverter shuts down alarms A13 and A25 and remains blocked...

Page 1283: ...e internal fault Solutions Make sure the position of the control devices isolators selectors is as specified in the procedures see Installation and start up section If the alarm persists contact our Technical Support Service Alarm A64 MAINS UNDERVOLTAGE Description Sudden drop of the AC input voltage fast sensor Possible causes Voltage drop on the AC mains brown out Possible internal fault Solutio...

Page 1284: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMW07104 REV A 59 LANGUE FRANÇAIS ...

Page 1285: ...46 KEOR HPE 80 kVA Ce manuel ainsi que les autres documentations techniques relatives à ce produit doivent êtres stockés et mis à disposition du personnel à proximité immédiate de l ASI Si les informations fournies dans le présent manuel ne sont pas suffisamment complètes veuillez contacter le fabricant de l appareil dont les coordonnées sont indiquées dans la section Contacts Autres informations ...

Page 1286: ......

Page 1287: ...ions potentiellement dangereuses peuvent découler d une défaillance de l ASI N utilisez pas l appareil s il est visiblement endommagé Entretenez régulièrement l appareil afin d identifier les éventuellesdéfaillances Lorsqu une intervention est réalisée sur l appareil assurez vous que toutes les mesures nécessaires sont prises afin d éviter des décharges électrostatiques susceptibles d endommager l...

Page 1288: ... à l utilisateur Illustration 1 Schéma bloc L ASI utilise la technologie IGBT à haute fréquence d inversion afin de permettre une faible distorsion du courant réinjecté dans la ligne d alimentation ainsi qu une qualité et une stabilité élevées de la tension en sortie Les composants utilisés assurent une haute fiabilité une très haute efficacité et une facilité de maintenance 3 2 DESCRIPTION DU SYS...

Page 1289: ...lectronique de contrôle du redresseur La batterie est chargée conformément à la norme DIN 41773 chaque fois qu elle a été partiellement ou complètement déchargée Lorsque sa pleine capacité est restaurée elle est maintenue en charge flottante afin de compenser l autodécharge réduire les contraintes dues à l ondulation résiduelle du courant alternatif et ainsi augmenter sa durée de vie Ce mode de fo...

Page 1290: ...mente l onduleur et compense les variations du secteur et de la charge assurant une tension CC constante Dans le même temps il maintient la batterie chargée chargement flottant ou boost en fonction du type de batterie L onduleur convertit la tension CC en onde sinusoïdale CA avec tension et fréquence stabilisées tout en alimentant la charge via son commutateur statique SSI Illustration 2 Fonctionn...

Page 1291: ...e du DC bus Capacité perdue 10 Charge additionnelle pour 12 heures Capacité perdue entre 10 et 20 Charge additionnelle pour 48 heures Capacité perdue 20 Charge additionnelle pour 96 heures Ces valeurs sont conformes aux recommandations des principaux fabricants de batteries Le panneau avant de l onduleur permet de régler les paramètres de la batterie y compris la capacité nominale Compte tenu de l...

Page 1292: ...e le redresseur recharge la batterie Dans la configuration standard les charges sont réalimentées via le commutateur statique SSB lorsque le secteur est à nouveau opérationnel L onduleur est redémarré une fois que la capacité de la batterie a été partiellement restaurée Les conditions de redémarrage du système après une panne totale peuvent être personnalisées en fonction des exigences du site dan...

Page 1293: ...de l interrupteur de sortie sur le bornier de l ASI dédié à cet effet Cela permettra à la logique de commande d accéder à l état des interrupteurs et de guider l opérateur lors de la mise en route des procédures de démarrage et de bypass manuel Pour de plus amples renseignements veuillez consulter la section Installation et démarrage En cas de by pass manuel pour une intervention de réparation ou ...

Page 1294: ... de l ASI est réservée au personnel autorisé uniquement Nous vous recommandons de vérifier la formation du personnel en charge de l utilisation et de la maintenance du système 3 4 1 Sectionneurs d isolation Les sectionneurs d isolation qui équipent l ASI sont utilisés afin d isoler les composants de puissance de l appareil de la ligne d alimentation CA de la batterie de stockage et des charges Les...

Page 1295: ... Il est utilisé lors de la procédure de by pass manuel lorsqu il est nécessaire d isoler l ASI pour une intervention de maintenance ou de réparation Le sélecteur normal by pass doit être utilisé conformément aux procédures indiquées dans la section relative à l installation et au démarrage Le fabricant ne pourra être tenu responsable des dommages liés à une utilisation incorrecte 3 4 4 Panneau de ...

Page 1296: ...PANNEAU AVANT Le panneau avant de l ASI composé d un affichage alphanumérique à deux lignes et de 5 touches de fonction permet la surveillance complète de l état del ASI Le tableau à schéma permet de mieux comprendre l état de fonctionnement de l ASI Illustration 8 Panneau avant de l ASI ...

Page 1297: ...indiquées dans le tableau suivant Touches Fonctions affectées Défilement des menus vers le haut Augmentation de la valeur d une unité Sélection d une valeur Défilement des menus vers le bas Diminution de la valeur d une unité Sélection d une valeur Sélection d un menu Confirmation des modifications Arrêt du buzzer activé lors d une alarme oudéfaillance Retour au menu précédent ...

Page 1298: ...erie en décharge ou en TEST ORANGE Disjoncteur BCB ouvert ROUGE Défaut de la batterie suite à un test de batterie ETEINTE Batterie indisponible LED 5 VERTE Tension de l onduleur dans les tolérances et commutateur statique fermé VERTE Surcharge ou court circuit de l onduleur ETEINTE Onduleur arrêté ou tension hors tolérances LED 6 ORANGE Re transfert bloqué ORANGE Commutateur de by pass statique fe...

Page 1299: ...e déchargée ou en TEST clignotement rapide ORANGE Disjoncteur BCB ouvert clignotement lent ROUGE Fin de l autonomie de la batterie Défault de la batterie LED 13 VERTE Tension de l onduleur dans les tolérances et commutateur statique fermé ORANGE Surcharge ou court circuit de l onduleur ROUGE Alarme critique de l onduleur ETEINTE Onduleur arrêté LED 14 VERTE Ligne de by pass CA dans les tolérances ...

Page 1300: ...issance nominale de l ASI Mesures de l ASI pour les paramètres de base tension courant etc État de fonctionnement de l ASI éventuelles alarmes présentes et historique des alarmes Configuration des paramètres et des fonctions spéciales Informations générales concernant l ASI UPS NAME xxx kVA UPS NAME MEASURES UPS NAME ALARMS UPS NAME SPECIAL UPS NAME INFO ...

Page 1301: ...anual Manuel de l utilisateur de l ASI Utilizzo dell UPS 76 OMW07104 REV A 5 2 AFFICHAGE DES MESURES Le menu MEASURES MESURES possède la structure suivante Illustration 11 Structure du menu MEASURES mesures 1 à 2 ...

Page 1302: ...nce 0 1 Hz Puissance active 1 kW Puissance apparente 1 kVA Pourcentage de charge 1 BYPASS Tension 1 2 1 V Fréquence 0 1 Hz INVERTER ONDULEUR Tension 1 2 1 V Fréquence 0 1 Hz AC DC CA CC Tension en sortie du redresseur 1 V BATTERY BATTERIE Tension et courant 1 V 1 A Capacité nominale 1 Ah Autonomie résiduelle 1 min 1 1 Les mesures de tension font toujours référence à la valeurphase neutre 2 Les tro...

Page 1303: ... ALARMES automatiquement dès qu une alarme se déclenche L indicateur sonore s il est sélectionné est activé afin d indiquer la survenance d une défaillance L alarme sonore peut être arrêtée en appuyant sur la touche BUZZER Affichage de la première alarme présente si aucune alarme n est présente l état de fonctionnement est affiché Appuyez sur la touche pour parcourir le menu et accéder à l alarme ...

Page 1304: ...s est affiché sur la première ligne xxx yyy qui indique respectivement l événement actuellement affiché position dans la liste et le nombre total d événements enregistrés au maximum égal à 500 Une astérisque indique la réinitialisation automatique de l alarme Dernier événement enregistré dans l ordre chronologique Par ex réinitialisation automatique de l alarme A3 BOOSTER STOPPED A3 Arrêt du boost...

Page 1305: ... PARALLÈLE A15 DÉFAUT DE BY PASS A47 ERREUR D ENVOI DES PARAMÈTRES A16 BY PASS CHARGE A48 ERREUR DE RÉCEPTION DES PARAMÈTRES A17 BLOCAGE DE RETRANSFERT A49 ERREUR DU MODE DE TEST A18 MBCB FERMÉ A51 TEMPÉRATURE DE LA BATTERIE A19 OCB OUVERT A52 VERROUILLAGE DE SOUS TENSION A20 SURCHARGE A53 ERREUR DU LOGICIEL DE L APPAREIL A21 IMAGE THERMIQUE A54 ERREUR CAN A22 COMMUTATEUR DE BY PASS A55 CÂBLE PARA...

Page 1306: ...ssent et leur indicateur sonore doit être désactivé à l aide de la touche buzzer Les alarmes restent affichées tant qu elles sont présentes Elles sont automatiquement enregistrées dans le journal d événements avec la date et l heure de leur survenance Pour une description plus détaillée des alarmes et des états voir la section Défauts et alarmes du présent manuel Mode d affichage et d enregistreme...

Page 1307: ...de l ASI Utilizzo dell UPS 82 OMW07104 REV A 6 REGLAGES ET OPERATIONS AVANCEES Certains paramètres de fonctionnement de l ASI peuvent être réglés via le menu SPECIAL dont la structure est la suivante Illustration 14 Structure du menu SPECIAL ...

Page 1308: ... BATTERY INSTALL Installation d une nouvelle batterie Règle l autonomie à 100 RESET HISTORY Remise à zéro de l historique Remise à zéro du journal des événements MODBUS Adresse MODBUS de l appareil RESET RUNNING HOURS Remise à zéro des heures de fonctionnement Remise à zéro du compteur d heures de fonctionnement de l ASI Le menu SETTINGS Réglages est protégé par un mot de passe défini en usine afi...

Page 1309: ...rs et la touche pour valider 6 3 INSTALLATION D UNE NOUVELLE BATTERIE Le menu NEW BATTERY INSTALL Installation d une nouvelle batterie est utilisé lorsque le disjoncteur de batterie BCB n est pas fermé lorsque demandé dans la phase de démarrage Dans ce cas le système démarre en considérant que la batterie est complètement déchargée et active l alarme A10 BATTERY FAULT A10 Défaut de labatterie Pour...

Page 1310: ...tre modifié à l aide des flèches et validé à l aide de la touche Entrée Écran de confirmation du réglage de paramètre Chaque chiffre peut être modifié à l aide des flèches et validé à l aide de la touche Entrée Écran de confirmation du réglage de paramètre Écran de confirmation de la configuration BAT CAPACITY SETTING 0120 CONFIRM BATT CAP YES BAT RECHAR CURR SET 18 CONFIRM RECHAR CURR YES AUTONOM...

Page 1311: ...che Entrée Paramètre Standard Valeurs possibles Adresse MODBUS 1 1 247 6 6 TEST DE L ASI Le menu UPS TEST Test de l ASI permet de réaliser un test de commutation de l onduleur L onduleur est arrêté et la charge est transférée sur l alimentation de by pass L alimentation de l onduleur est automatiquement restaurée après quelques secondes La valeur de la seconde ligne est prête à être modifiée Le pa...

Page 1312: ... pas complètement chargée 6 8 RÉINITIALISATION DU SYSTÈME L ASI est équipé de protections internes qui bloquent tout ou partie du système L alarme peut être effacée et le fonctionnement normal rétabli via le menu RESET Réinitialiser Si la défaillance persiste l ASI reviendra dans la condition de défaillanceprécédente Dans certains cas le menu RESET Réinitialiser est nécessaire pour la simple réini...

Page 1313: ...l activation du capteur de déconnexion rapide alarme A36 Arrêt de l onduleur du fait d une erreur de la boucle de contrôle de la tension alarme A39 Arrêt du booster du fait d une erreur de la boucle de contrôle de la tension alarme A41 Arrêt du booster du fait d une erreur de la boucle de contrôle du courant alarmeA43 Commutateur statique bloqué alarme A50 Arrêt du booster du fait de l activation ...

Page 1314: ...paramètre est modifié La modification est confirmée en appuyant sur Entrée Le système effectue une réinitialisation de l historique des alarmes puis revient à l écran précédent L historique des alarmes contient des données importantes pour la surveillance du comportement de l appareil dans le temps Nous vous recommandons d enregistrer les données avant toute remise à zéro Perte de données RESET HI...

Page 1315: ...SI selon la structure de base suivante Illustration 15 Structure du menu INFO Toutes les données affichées dans les diverses sections sont définies en usine via un logiciel d interface spécial Elles ne peuvent pas être modifiées sauf par un personnel autorisé par le fabricant Les seuls paramètres pouvant être modifiés sont les réglages MODBUS voir le menu SPECIAL ...

Page 1316: ...relatives à l entretien technique RUNNING HOUR Heures de fonctionnement Dates relatives au nombre d heures de fonctionnement de l ASI 1 Ce menu n est actif que si l ASI fait partie d un système parallèle ou de synchronisation de charge 2 Ce menu n est actif que si l ASI fait partie d un système common battery 7 1 INFORMATIONS SUR LE FONCTIONNEMENT EN PARALLELE Le menu PARALLEL Parallèle n est acti...

Page 1317: ...rifie la communication des données sur l ASI 3 l ASI 4 ne communique pas Le menu affichera les informations suivantes S il y a plus de quatre appareils en parallèle le menu affichera les informations suivantes Les points indiquent la présence d une autre ligne de menu indiquant l état des autres ASI du système 7 1 4 Type de système parallèle La seconde ligne peut indiquer l une des deux valeurs su...

Page 1318: ...essages sont échangés entre tous les ASI par conséquent cette valeur augmentera sur chacun 7 2 INFORMATIONS SUR LE FONCTIONNEMENT EN PARALLELE REDRESSEUR Le menu PARALLEL Parallèle n est actif que si l ASI fait partie d un système parallèle ou de synchronisation de charge 7 2 1 Position de l ASI Le premier chiffre de la seconde ligne identifie la position de cet ASI spécifique au sein du système p...

Page 1319: ...T 1 signifie qu un seul ASI est nécessaire pour alimenter la charge 7 2 5 Statistiques relatives aux messages Les statistiques de la section pour les messages échangés sur le bus de communication se compose deux menus différents Nombre de messages reçus et pourcentage de précision de la réception concernant les signaux de synchronisme Les messages sont envoyés par l ASI maître Par conséquent la va...

Page 1320: ...affichées en faisant défiler le menu Après la dernière alarme présente les états de fonctionnement sont affichés Avant toute intervention sur l ASI assurez vous que toutes les précautions de sécurité sont respectées toute intervention sur l unité doit être réalisée par un personnel qualifié les composants internes ne peuvent être manipulés qu après déconnexion de l appareil de ses sources d alimen...

Page 1321: ... à alimenter la charge État S4 INVERTER LOAD Onduleur charge Description L onduleur alimente la charge Condition de fonctionnement La charge est alimentée par le commutateur d onduleur statique État S5 INV BYPASS SINCRO Description L onduleur est synchronisé avec le by pass Condition de fonctionnement La synchronisation entre l onduleur et le by pass est verrouillée Le commutateur statique peut ba...

Page 1322: ...R STAND BY Description The inverter is in standby mode Condition de fonctionnement L onduleur est éteint et prêt à être démarré en cas d anomalie du réseau de base État S12 BATT STANDBY Description La batterie est en mode standby Condition de fonctionnement L interrupteur statique de la batterie est ouvert et la batterie est déconnectée du bus CC État S14 BATT CHARGING I Description La batterie es...

Page 1323: ...ifiez la rotation des phases 2 Si l alarme persiste contactez notre service de supporttechnique Alarme A3 ARRÊT DU BOOSTER Description Le redresseur a été alimenté par la batterie temporairement déconnecté et l onduleur est Causes possibles Instabilité de la tension ou de la fréquence de la ligne CA Défaut possible du circuit de contrôle du redresseur Solutions 1 Vérifiez les paramètres de tension...

Page 1324: ... lancé automatiquement si ce paramètre a été défini ou manuellement par l utilisateur Solutions 1 Attendez la fin du test et vérifiez les éventuels défauts de batterie Alarme A7 BCB OUVERT Description Le sectionneur d isolation de la batterie est ouvert Causes possibles Sectionneur d isolation de la batterie ouvert Solutions 1 Vérifiez l état du sectionneur d isolation de la batterie 2 Vérifiez la...

Page 1325: ...i l alarme persiste contactez notre service de supporttechnique Alarme A11 COURT CIRCUIT Description Le capteur de courant a détecté un court circuit à la sortie Causes possibles Problème de charge Défaillance du circuit de mesure Solutions 1 Vérifiez les charges raccordées à la sortie de l ASI 2 Si l alarme persiste contactez notre service de supporttechnique Alarme A12 ARRÊT DÉLAIDE COURT CIRCUI...

Page 1326: ...on Solutions 1 Vérifiez la rotation des phases 2 Si l alarme persiste contactez notre service de supporttechnique Alarme A15 DÉFAUT DE BY PASS Description La tension ou la fréquence de la ligne de by pass est hors tolérances Causes possibles Instabilité ou défaillance de la ligne de by pass Mauvaise rotation des phases Solutions 1 Vérifiez les raccordements au secteur 2 Vérifiez la stabilité de la...

Page 1327: ... 2 Vérifiez la fonctionnalité du contact auxiliaire du sectionneur d isolation 3 Si l alarme persiste contactez notre service de supporttechnique Alarme A19 OCB OUVERT Description Le sectionneur d isolation de la sortie est ouvert Causes possibles Sectionneur d isolation de la sortie ouvert Solutions 1 Vérifiez l état du sectionneur d isolation de la sortie 2 Vérifiez la fonctionnalité du contact ...

Page 1328: ... 2 Si l alarme persiste contactez notre service de supporttechnique Alarme A23 ARRÊT D URGENCEDÉCLENCHÉ Description Le système d urgence est bloqué du fait de l activation du bouton d arrêt Causes possibles Activation du bouton d arrêt d urgence local ou distant Solutions 1 Relâchez le bouton d arrêt d urgence et réinitialisez l alarme 2 Si l alarme persiste contactez notre service de supporttechn...

Page 1329: ... contrôleur a détecté une erreur dans les paramètres enregistrés dans l E2 PROM Causes possibles Mauvais paramètres saisis lors de la programmation Solutions 1 Contactez notre service de support technique Alarme A28 DÉFAUT CRITIQUE Description Une alarme a été déclenchée entraînant l arrêt d une partie de l ASI redresseur onduleur commutateur statique Causes possibles Défaillance du système Soluti...

Page 1330: ...S EPO FERMÉ Description Le système d urgence est bloqué du fait de l activation du bouton d arrêt Causes possibles Activation du bouton d arrêt d urgence local ou distant Solutions 1 Relâchez le bouton d arrêt d urgence et réinitialisez l alarme 2 Si l alarme persiste contactez notre service de supporttechnique Alarme A33 CHARGE ASYMÉTRIQUE Description Les tensions positives et négatives mesurées ...

Page 1331: ...erie Solutions 1 Vérifiez la batterie 2 Réinitialisez le système 3 Si l alarme persiste contactez notre service de supporttechnique Alarme A38 ONDULEUR CHARGE Description La charge est alimentée par l onduleur Cette alarme est active pour les systèmes ASI en mode ECO lorsque l alimentation préférée est celle issue de la ligne de by pass Causes possibles Basculement temporaire du fait d une défaill...

Page 1332: ...te contactez notre service d assistance technique Alarme A44 DÉSATURATION DE L ONDULEUR IGBT Description L onduleur est bloqué en raison du fonctionnement du capteur de désaturation des drivers IGBT Causes possibles Fault Panne du pont de l onduleur Solutions 1 Réinitialisez le système 2 Si l alarme persiste contactez notre service d assistance technique Alarme A46 PERTE DE REDONDANCE PARALLÈLE De...

Page 1333: ...ive que lorsqu une sonde de température est installée et activée au niveau de la batterie Causes possibles Température anormale dans l armoire de batterie Possible défaillance du circuit de mesure Solutions 1 Vérifiez la température au niveau des batteries et supprimez la cause de l alarme le cas échéant 2 Si l alarme persiste contactez notre service de supporttechnique Alarme A52 VERROUILLAGE DE ...

Page 1334: ... tension d entrée 2 Contactez notre service de support technique Alarm A61 DC SUR LA PROTECTION Description L alarme est activée lorsque la tension continue dépasse 910 V 455 V pour chaque batterie de condensateurs L alarme doit être réinitialisée manuellement par affichage Possible causes Le redresseur s arrête alarm A3 L onduleur s arrête alarms A13 and A25 et reste bloqué La charge est transfér...

Page 1335: ...ns 1 Assurez vous que les dispositifs de commande sectionneurs d isolation sélecteurs sont dans la bonne position telle qu indiquée dans les procédures voir la section Installation et démarrage 2 Si l alarme persiste contactez notre service de supporttechnique Alarm A64 SOUS TENSION DU RÉSEAU Description Chute soudaine de la tension d entrée AC capteur rapide Possible causes Chute de tension sur l...

Page 1336: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS OMW07104 REV A 111 LINGUA ITALIANA ...

Page 1337: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 112 OMW07104 REV A ...

Page 1338: ...kVA Conservazione della documentazione Questo manuale e tutta la restante documentazione tecnica di supporto al prodotto devono essere conservati e possibilmente resi accessibili al personale nelle immediate vicinanze dell UPS Informazioni aggiuntive Nel caso le informazioni riportate nel presente manuale non fossero abbastanza esaurienti si prega di contattare il costruttore del dispositivo i cui...

Page 1339: ...riportate nei manuali Pericolo di lesioni a seguito di guasti al dispositivo In caso di guasto dell UPS si possono creare situazioni potenzialmente pericolose Non utilizzare il dispositivo se presenta danni visibili Effettuare regolarmente interventi di manutenzione al fine di rilevare possibili anomalie Possibile danneggiamento del dispositivo Prima di qualsiasi intervento sul dispositivo aver cu...

Page 1340: ...ancanza della rete per cui in accordo alle prescrizioni della CEI EN62040 1 l installatore dovrà identificare la linea o le prese alimentate dall UPS richiamando l attenzione dell utente Figura 1 Schema a blocchi L UPS è realizzato con tecnologia ad IGBT ad elevata frequenza di commutazione per consentire una bassa distorsione della corrente re iniettata nella rete di alimentazione e un alta quali...

Page 1341: ...A Per KEOR HPE 100 125 160kVA la batteria è installata all esterno dell UPS E generalmente ubicata all interno di un armadio La logica del carica batteria è integrata all interno dell elettronica di controllo del raddrizzatore La batteria viene sottoposta ad un ciclo di carica in accordo alle DIN41773 ogni volta che avviene una scarica parziale o totale Al ripristino della completa capacità viene ...

Page 1342: ... compensa le variazione della tensione di rete così come quelle di carico mantenendo la tensione DC costante Allo stesso tempo provvede a caricare la batteria L inverter converte la tensione DC in una sinusoide AC stabilizzata in tensione e frequenza e provvede ad alimentare il carico tramite il suo static switch SSI Figura 2 Funzionamento normale 3 3 2 Green Conversion Durante il funzionamento in...

Page 1343: ...pacità persa è 10 Carica mantenimento per 12 ore Capacità persa è compresa tra il 10 e il 20 Carica mantenimento per 48 ore Capacità persa è 20 Carica mantenimento per 96 ore Tali valori sono conformi alle raccomandazioni dei principali produttori di batterie Impostare il corretto valore di capacità Il pannello frontale dell UPS permette l impostazione dei parametri di batteria inclusa la capacità...

Page 1344: ...vvio dell inverter avviene quando la batteria ha ripristinato parte della sua capacità La ripartenza del sistema dalla condizione di black out può essere personalizzata sulla base delle esigenze dell impianto in tre modalità differenti Bypass i carichi vengono alimentati appena la rete di bypass è disponibile configurazione di fabbrica Inverter i carichi vengono alimentati dall inverter anche se l...

Page 1345: ...lazione elettrica prestare cura al cablaggio dei contatti ausiliari degli isolatori di bypass manuale uscita e batteria che vanno collegati agli appositi morsetti sull UPS In questo modo la logica di controllo acquisisce lo stato degli interruttori per guidare l operatore durante le procedure di avvio e bypass manuale Per maggiori informazioni fare riferimento alla sezione Installazione e avviamen...

Page 1346: ...ando dell UPS è destinato a personale autorizzato Si consiglia di verificare l addestramento del personale addetto all utilizzo e alla manutenzione del sistema 3 4 1 Sezionatori I sezionatori previsti sull UPS servono per isolare la parte di potenza del dispositivo dalla rete AC di alimentazione dalla batteria di accumulatori e dai carichi Presenza di tensione sui terminali I sezionatori non isola...

Page 1347: ...ll arresto di emergenza sono state eliminate e si è certi che non ci siano pericoli per le persone o le cose 3 4 3 Selettore Normale Bypass Viene utilizzato durante la procedura di bypass manuale quando è necessario isolare l UPS per manutenzione o riparazione Seguire le procedure riportate nel manuale Il selettore Normale Bypass deve essere manovrato solamente in accordo alle procedure riportate ...

Page 1348: ...23 4 PANNELLO FRONTALE Il pannello frontale dell UPS è composto da un display alfanumerico a 4 righe più 5 tasti funzione e consente il completo monitoraggio dello stato dell UPS Il sinottico di flusso agevola la comprensione dello stato di funzionamento Figura 8 Pannello frontale UPS ...

Page 1349: ...ui funzioni sono indicate nella tabella seguente Tasto Funzioni assegnate Scorre i menu verso l alto Incrementa i valori di una unità Seleziona un valore Scorre i menu verso il basso Decrementa i valori di una unità Seleziona un valore Seleziona un menu Conferma le modifiche Silenzia il buzzer attivato a seguito di un allarme o anomalia Torna al menu precedente ...

Page 1350: ...IO Interruttore BCB aperto ROSSO Batteria guasta a seguito test di batteria OFF Batteria non presente LED 5 VERDE Tensione inverter in tolleranza e static switch chiuso VERDE Sovraccarico inverter o corto circuito OFF Inverter spento o tensione fuori tolleranza LED 6 ARANCIO Ritrasferimento bloccato ARANCIO Static switch bypass chiuso OFF Static switch bypass aperto LED 7 VERDE Interruttore di usc...

Page 1351: ...ARANCIO Batteria in scarica o in TEST lampeggio veloce ARANCIO Interruttore BCB aperto lampeggio lento ROSSO Fine autonomia batteria Batteria guasta LED 13 VERDE Tensione inverter in tolleranza e static switch chiuso ARANCIO Sovraccarico inverter o corto circuito ROSSO Allarme critico inverter OFF Inverter spento LED 14 VERDE Rete AC bypass in tolleranza ROSSO Senso ciclico errato lampeggio veloce...

Page 1352: ...ta principale dove è visualizzata la potenza nominale dell UPS xxx kVA NOME UPS Misure dei parametri fondamentali dell UPS tensione corrente ecc MISURE NOME UPS Stato di funzionamento dell UPS eventuali allarmi presenti e storico allarmi ALLARMI NOME UPS Impostazione parametri e funzioni speciali SPECIALE NOME UPS Informazioni generali sull UPS INFO ...

Page 1353: ...UPS user manual Manuel de l utilisateur de l ASI Utilizzo dell UPS 128 OMW07104 REV A 5 2 VISUALIZZAZIONE DELLE MISURE Il menu MISURE è strutturato come segue Figura 11 Struttura menu MISURE 1 di 2 ...

Page 1354: ...Frequenza 0 1 Hz Potenza attiva 1 kW Potenza apparente 1 kVA Percentuale di carico 1 BYPASS Tensione 1 2 1 V Frequenza 0 1 Hz INVERTER Tensione 1 2 1 V Frequenza 0 1 Hz AC DC Tensione uscita raddrizzatore 1 V BATTERIA Tensione e corrente 1 V 1 A Capacità nominale 1 Ah Autonomia residua 1 min 1 1 Le misure di tensione sono sempre riferite tra fase e neutro 2 Le tre tensioni sono visualizzate in una...

Page 1355: ...LARMI ogni volta che si verifica un allarme il segnalatore acustico se abilitato viene attivato per indicare l avvenuta anomalia La tacitazione viene effettuata premendo il pulsante BUZZER STATO UPS Visualizzazione del primo allarme presente se non presenti allarmi visualizzazione dello stato di funzionamento Allarme stato no 1 STATO UPS Premendo il tasto si scorre il menu e si passa all allarme s...

Page 1356: ...più vecchio La quantità di eventi memorizzati è visualizzata sulla prima riga xxx yyy dove sono riportati rispettivamente il dato visualizzato al momento posizione nella lista e il numero totale di dati memorizzati numero massimo pari a 500 Un asterisco indica il reset automatico dell allarme STORICO 001 015 Ultimo evento memorizzato in ordine di tempo Es reset automatico allarme A3 RADD SPENTO A3...

Page 1357: ...URAZIONE A14 ER SENSO CIC BYP A46 PERDITA RIDOND A15 BYPASS NON DISP A47 ERR INVIO PARAM A16 BYP CARICO A48 ERR RIC PARAM EE A17 RITRASF BLOC A49 DISCOR TEST MODE A18 MBCB CHIUSO A51 TEMPERATURA BATT A19 OCB APERTO A52 INVERTER BLOCCATO UVL A20 SOVRACCARICO A53 ER COMP FIRMWARE A21 IMMAGINE TERMICA A54 ERRORE CAN A22 BYPASS SWITCH A55 CAVO PAR DISC A23 EPO CHIUSO A56 TERNA SBILANCIATA A24 ALTA TEM...

Page 1358: ...ati sempre in ordine crescente Gli allarmi vengono mostrati quando si presentano e devono essere tacitati con il buzzer Gli allarmi restano visibili finché sono presenti e vengono registrati automaticamente nello storico eventi con data e ora Descrizione degli allarmi e degli stati Per una descrizione più approfondita degli allarmi e degli stati vedere la sezione del presente manuale Guasti e alla...

Page 1359: ...ateur de l ASI Utilizzo dell UPS 134 OMW07104 REV A 6 IMPOSTAZIONI E OPERAZIONI AVANZATE L impostazione di alcuni parametri operativi dell UPS è possibile dal menu SPECIALE che è strutturato come segue Figura 14 Struttura menu SPECIALE ...

Page 1360: ...della batteria INSTALL NUOVA BATT Imposta l autonomia al 100 RESET STORICO Reset dello storico eventi MODBUS Indirizzo MODBUS del dispositivo AZZERA CONTAORE Azzeramento del contaore di funzionamento della macchina Accesso protetto da password Il menu IMPOSTAZIONI è protetto da una password impostata in fabbrica per impedire l accesso a personale non autorizzato Si raccomanda la minima divulgazion...

Page 1361: ...ametri si effettua utilizzando i tasti freccia per incrementare le cifre e il tasto per confermare l inserimento 6 3 INSTALLAZIONE NUOVA BATTERIA Il menù INSTALLAZIONE NUOVA BATTERIA serve nel caso in cui durante la fase di avvio non viene chiuso l interruttore di batteria BCB quando richiesto In tal caso il sistema si avvia considerando la batteria completamente scarica e attivando l allarme A10 ...

Page 1362: ... parametro impostato SI CONFIG COR RICAR BAT Le singole cifre si modificano con i tasti freccia e si confermano con il tasto ENTER 18 CONF CORR RICARICA Schermata di conferma del parametro impostato SI CONFIG AUTONOMIA BAT Le singole cifre si modificano con i tasti freccia e si confermano con il tasto ENTER 0020 CONF AUTONOMIA BATT Schermata di conferma del parametro impostato SI SALVARE CONFIG BA...

Page 1363: ...icano con i tasti freccia e si confermano con il tasto ENTER 202 Parametro Standard Range INDIRIZZO MODBUS 1 1 247 6 6 TEST DELL UPS Il menù TEST UPS permette di effettuare una prova di commutazione dell inverter L inverter viene spento e il carico trasferito all alimentazione di bypass L alimentazione da inverter viene ripristinata automaticamente dopo pochi secondi TEST UPS Il valore sulla secon...

Page 1364: ... Questo test può essere rischioso per la continuità sui carichi se la batteria non è pienamente carica 6 8 RESET DEL SISTEMA L UPS è provvisto di protezioni interne che provvedono al blocco del sistema o di alcune sue sezioni Tramite il menu RESET è possibile sbloccare l allarme e ripristinare il funzionamento normale Nel caso l anomalia persista l UPS si riporta nella condizione di blocco precede...

Page 1365: ...e statico allarme A50 Arresto booster per intervento del sensore di simmetria del carico allarme A33 Intervento allarme di avaria batteria allarme A10 Richiesta manutenzione programmata allarme A29 Per la descrizione dello stato dell UPS in ciascuna delle condizioni di blocco elencata in precedenza fare riferimento alla sezione Guasti e allarmi 6 9 RESET STORICO ALLARMI Accedere al menu RESET STOR...

Page 1366: ... secondo la struttura mostrata di seguito Figura 15 Struttura menu INFO Tutti i dati mostrati all interno delle varie sezioni sono impostati in fabbrica tramite apposito software di interfaccia e non possono essere modificati tranne che da parte di personale autorizzato dal costruttore Gli unici parametri modificabili sono le impostazioni MODBUS vedi menu SPECIALE ...

Page 1367: ... all assistenza tecnica CONTATORE Dati relativi al numero di ore di funzionamento della macchina 1 Il menù è attivo solamente se l UPS fa parte di un sistema Parallelo oppure Load Sync 2 Il menù è attivo solamente se l UPS fa parte di un sistema con batteria unica 7 1 INFORMAZIONI SUL FUNZIONAMENTO IN PARALLELO Il menù PARALLELO è attivo solamente se l UPS fa parte di un sistema parallelo oppure l...

Page 1368: ...UPS2 stiamo verificando la comunicazione dati sull UPS3 l UPS4 non comunica Il menù si presenterà come mostrato di seguito PARALLELO 1 S 2 M 3 S 4 Nel caso che i dispositivi in parallelo siano più di quattro il menù si presenta come segue PARALLELO 1 S 2 M 3 S I punti indicano la presenza di un ulteriore menù che mostra lo stato degli altri UPS del sistema 7 1 4 Tipo di parallelo PARALLELO RIDONDA...

Page 1369: ...mero incrementa solo sugli UPS SLAVE STATIST CAN INV MSG RX 9277 99 9 Numero di messaggi ricevuti e percentuale di accuratezza della ricezione relativamente agli stati del sistema I messaggi vengono scambiati fra tutti gli UPS quindi il numero incrementa su tutti 7 2 INFORMAZIONI SUL FUNZIONAMENTO IN PARALLELO RADDRIZZATORE Il menù PARALLELO è attivo solamente se l UPS fa parte di un sistema paral...

Page 1370: ...ato dal numero X Per esempio in un sistema composto da 2 UPS RIDONDANTE 1 significa che uno solo degli UPS è sufficiente per alimentare il carico 7 2 5 Statistiche messaggi La sezione statistiche relative ai messaggi scambiati sui bus di comunicazione si compone di due diversi menù STATIST CAN RADR SYNC RX 15849 100 0 Numero di messaggi ricevuti e percentuale di accuratezza della ricezione relativ...

Page 1371: ...ATO UPS Scorrendo il menu dove vengono visualizzati gli altri allarmi presenti A30 ALLARME GENERALE STATO UPS Dopo l ultimo allarme presente si passa alla visualizzazione degli stati operativi S1 BOOSTER OK Pericolo di lesioni a seguito shock elettrico Prima di effettuare qualsiasi intervento sull UPS aver cura di rispettare tutte le indicazioni relative alla sicurezza tutti i lavori sull apparato...

Page 1372: ... pronto per erogare alimentare il carico Stato S4 INV CARICO Descrizione L inverter alimenta il carico Condizione operativa Il carico è alimentato attraverso l interruttore statico di inverter Stato S5 INV BYPASS SINCRO Descrizione L inverter è sincronizzato con il bypass Condizione operativa Il sincronismo fra inverter e bypass è agganciato e l interruttore statico può effettuare commutazioni fra...

Page 1373: ...in modalità standby Condizione operativa L inverter è spento e pronto ad essere avviato in caso di anomalia della rete di bypass Stato S12 BATTERIA STANDBY NON DISPONIBILE Descrizione La batteria è in modalità standby Condizione operativa L interruttore statico di batteria è aperto e la batteria è disconnessa dal bus DC Stato S14 BATT IN CARICA I Descrizione La batteria è in carica Condizione oper...

Page 1374: ...oni Verificare il senso ciclico delle fasi Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A3 RADD SPENTO Descrizione Il raddrizzatore è stato momentaneamente arrestato e l inverter viene alimentato dalla batteria Possibili cause Instabilità della tensione o della frequenza della rete AC Possibile guasto del circuito di controllo del raddrizzatore Soluzioni Verificare i ...

Page 1375: ... batteria Possibili cause E stato avviato un test di batteria automaticamente se impostato oppure manualmente dall operatore Soluzioni Attendere la fine del test e verificare eventuali anomalie della batteria Allarme A7 BCB APERTO Descrizione Il sezionatore di batteria è aperto Possibili cause Sezionatore di batteria aperto Soluzioni Verificare lo stato del sezionatore di batteria Verificare la fu...

Page 1376: ...tteria Resettare il sistema Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A11 CORTO CIRCUITO Descrizione Il sensore di corrente ha rilevato un corto circuito in uscita Possibili cause Problema sui carichi Guasto del circuito di misura Soluzioni Verificare i carichi connessi all uscita dell UPS Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A...

Page 1377: ...are il senso ciclico delle fasi Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A15 BYPASS NON DISP Descrizione La tensione o la frequenza della rete di bypass sono fuori dal range di tolleranza Possibili cause Instabilità o mancanza della rete di bypass Errato senso ciclico delle fasi Soluzioni Controllare i collegamenti di connessione alla rete Verificare la stabilità ...

Page 1378: ...ass manuale Verificare la funzionalità del contatto ausiliario del sezionatore Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A19 OCB APERTO Descrizione Il sezionatore di uscita è aperto Possibili cause Sezionatore di uscita aperto Soluzioni Verificare lo stato del sezionatore di uscita Verificare la funzionalità del contatto ausiliario del sezionatore Se l allarme pers...

Page 1379: ...Assistenza Tecnica Allarme A23 EPO CHIUSO Descrizione Il sistema è bloccato in seguito all azionamento del pulsante di arresto di emergenza Possibili cause Azionamento del pulsante di arresto di emergenza locale o remoto Soluzioni Sbloccare l arresto di emergenza e resettare l allarme Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A24 ALTA TEMPERATURA Descrizione Alta t...

Page 1380: ...ollore ha rilevato un errore nei parametri memorizzati in EEPROM Possibili cause Inserimento di parametri errati durante la programmazione Soluzioni Contattare il servizio di Assistenza Tecnica Allarme A28 GUASTO CRITICO Descrizione E presente un allarme che causa l arresto di una parte dell UPS raddrizzatore inverter interruttore statico Possibili cause Guasto del sistema Soluzioni Verificare qua...

Page 1381: ...e Il sistema è bloccato in seguito all azionamento del pulsante di arresto di emergenza Possibili cause Azionamento del pulsante di arresto di emergenza locale o remoto Soluzioni Sbloccare l arresto di emergenza e resettare l allarme Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A33 CARICO ASIMMETR Descrizione Le tensioni misurate sui condensatori DC positiva e negativ...

Page 1382: ... Possibili cause Anomalia batteria Soluzioni Verificare la batteria Resettare il sistema Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A38 INV CARICO Descrizione Il carico è alimentato dall inverter Allarme attivo per UPS in modalità ECO dove l alimentazione privilegiata è dalla rete di bypass Possibili cause Trasferimento momentaneo per mancanza rete di bypass Soluzio...

Page 1383: ...e persiste contattare il servizio di Assistenza Tecnica Allarme A44 DESATURAZIONE Descrizione L inverter è bloccato in seguito all intervento del sensore di desaturazione dei driver IGBT Possibili cause Anomalia del ponte inverter Soluzioni Resettare il sistema Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A46 PERDITA RIDOND Possibili cause Il carico totale è superiore...

Page 1384: ...larme A51 TEMPERATURA BATT Descrizione La temperatura della batteria è fuori dai limiti di tolleranza Allarme attivo solo se è installata e abilitata la sonda di temperatura sulla batteria Possibili cause Temperatura anomala all interno dell armadio batterie Possibile guasto del circuito di misura Soluzioni Verificare la temperatura sulle batterie ed eventualmente rimuovere la causa di allarme Se ...

Page 1385: ...tattare il servizio di Assistenza Tecnica Allarme A54 ERRORE CAN Descrizione Errore interno Possibili cause Problemi di comunicazione del microcontrollore Soluzioni Contattare il servizio di Assistenza Tecnica Allarme A55 CAVO PAR DISC Descrizione Mancata comunicazione del cavo parallelo Possibili cause Cavo di parallelo disconnesso o danneggiato Soluzioni Controllare la connessione del cavo Conta...

Page 1386: ...e il corretto funzionamento sezione statico Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A62 MAINS OVERVOLTAGE Descrizione Rilevazione di un picco di tensione sull ingresso AC Possibili cause Picco di tensione sulla rete AC Possibile guasto interno Soluzioni Controllare la rete AC Se l allarme persiste contattare il servizio di Assistenza Tecnica Allarme A63 SEQ AVVIO...

Page 1387: ...THREE PHASE UPS From 60 to 500 kW Keor HPE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES ...

Page 1388: ...00 125 160 200 300 400 500 kVA and can be connected in parallel and have N X redundancy up to a maximum of 6 units Keor HPE is the ideal solution for medium and large power critical applications tertiary hospital industry transport where continuity of service high quality power supply and reduced consumption are required THREE PHASE UPS Keor HPE 2 ...

Page 1389: ...reen displays and the hexagonal motif also reflected in the ventilation grids enrich the product combining technology and design Smart Display The new Keor HPE are equipped with smart interactive simple and intuitive displays thanks to which it is possible to view the operating parameters of the UPS selecting the preferred language The displays are supplied in 2 different versions 7 inch LCD for 6...

Page 1390: ...guarantee low operating costs Transformer free technology and configurations with internal batteries facilitate installation and optimise space in technical rooms Greater power density The 60 and 80 kW models have optimised dimensions in a volume of 0 78 m3 Power factor The modern power circuit architecture allows for load supply with maximum active power ...

Page 1391: ... HPE UPS was designed to be installed and maintained from the front All the protection switches and communication ports are located on the front of the UPS A practical internal door also allows you to reach the parts installed on the bottom of the UPS in order to have maximum access to all the components The simplicity of access to all parts subject to maintenance significantly reduces MTTR that i...

Page 1392: ... family as optional external accessories Keor HPE includes advanced battery charging and management functions which guarantee the best performance and maximum operating life Intermittent charging with adjustable cycle 27 3 standard to extend the effective life and obtain maximum energy savings Automatic current charging regulation with load power priority to quickly charge batteries for long auton...

Page 1393: ...ons and environment For battery cabinet solutions please refer to the dedicated catalogue to create two synchronous but independent power lines typical in Tier III IV systems Model UPS Apparent power kVA Active power kW Autonomy min Dimensions H x W x D mm Net weight kg 3 110 87 60 60 0 1500 x 560 x 940 225 3 110 88 60 60 5 1500 x 560 x 940 525 3 110 89 60 60 10 1500 x 560 x 940 675 3 110 90 80 80...

Page 1394: ...s at 150 0 1 seconds 150 10 minutes at 110 5 minutes at 125 30 seconds at 150 0 1seconds 150 Efficiency in Eco Mode 98 Bypass Automatic and maintenance bypass Batteries Internal battery yes yes Autonomy expansion Yes with additional battery cabinets Battery series type VRLA AGM Lead acid sealed maintenance free Battery test Automatic or manual Battery charger IU DIN41773 Communication and manageme...

Page 1395: ...ming up with solutions for lower energy consumption but also integrating product design into the overall development process With around 200 000 catalogue items the Group also provides all products required for electrical and digital building installations particularly as integrated systems finding solutions to fit everyone s needs Tailor made Legrand offers a complete range of specific solutions ...

Page 1396: ... parts when needed Our Service Contracts include cleaning IR thermography measurements functional tests event log and power quality analysis battery health check hardware and software upgrades and technical reports A Preventive Maintenance Plan is one of the most cost effective actions that can preserve your initial investment and ensure your business continuity CORRECTIVE MAINTENANCE EMERGENCY CA...

Page 1397: ...11 WWW UPS LEGRAND COM UPS CONVENTIONAL UPS ...

Page 1398: ...AD EXLGUPS KE20B GB 06 2020 FOLLOW US ALSO ON www ups legrand com World Headquarters and International Department 87045 Limoges Cedex France 33 0 5 55 06 87 87 Fax 33 0 5 55 06 74 55 ...

Reviews: