146
Command Specifications
Section B-4
Command
REQUEST_RESETSTATUS
Purpose
Issue a request to clear the Detailed status group.
Code
0x2002
Argument
Clearing status
1-WORD data,
items
Set the bits to clear to 1 (ON) and the bits not to clear to 0
(OFF).
Response code
Normal end: 0x0000
Remarks
•
It is cleared at the time a normal end is the response.
•
When the Master status is set to be cleared, the Maximum communication
cycle time, the Cumulative CRC reception error and the Cumulative code
reception error in the Master status are cleared.
Command
SET_PC_WDT
Purpose
Set the PC Watchdog Timer.
Code
0x3001
Argument
Timer value
1-WORD data,
Unit: 10 ms
Range: 0x0000, 0x0001 to 0xFFFF (1 to 655350 ms)
(Setting 0x0000 will disable the PC WDT function.)
Response code
Normal end: 0x0000
Remarks
•
When the PC WDT is enabled, be sure to refresh it before it times out.
•
See Section 5-5 for the usage of PC WDT.
Bit
Flag name
0 to 4
Reserved area, Set 0 (OFF).
5
Master status
6
Error counter
7 to 10
Reserved area, Set 0 (OFF).
11
Error log
12 to 15
Reserved area, Set 0 (OFF).