164
CompoNet Network Specifications
Section E-1
*3 Branch lines support T-branch connections.
In Data Rate of 93.75
kbps
* This is the maximum number of Slave and Repeater Units that can be
connected to a branch line through the use of multidrop connections or T-
branch connections. The purpose of T-branching here is to have a sub-
branch line.
E-1-4
Types of CompoNet Network Addresses
The types of node address that are set on a CompoNet network are given in
the following table.
IN Slave Unit Node
Addresses Are Used
for Mixed Slave Units
• For Word Mixed Slave Units, use the same node address type as for a
Word Input Slave Unit.
• For Bit Mixed Slave Units, use the same node address type as for a Bit
Input Slave Unit.
• If you connect a Word Input Expansion Unit (such as the XWT-ID16 or
XWT-ID08) to a Word Output Slave Unit, the result is treated as a Mixed
Slave Unit. Therefore, the node address type is a Word MIX Slave Unit
instead of a Word OUT Slave Unit.
Item
Round cable I
Round cable II Flat
Cable I or II
Length of a trunk line or a sub-
trunk line (Maximum length when
two Repeater Units are used)
500 m (1500 m)
Unrestricted wiring can
be done for a total
length of 200 m per
segment
Length of a branch line
6 m
Total length of branch lines
120 m
Branching restriction
3 branches / m
Number of connectable Units per
branch line *
1
Maximum length of a sub-branch
line
−
Total length of sub-branch lines
−
Number of connectable Slave
Units and Repeater Units
altogether per trunk line or sub-
trunk line
32
32
Type of node address
Address range
Applicable Slave Units
Word IN Slave Unit
Word MIX Slave Unit
0 to 63
Input Slave Unit or I/O Slave
Unit that is allocated memory
in increments of 16 bits
Word OUT Slave Unit
0 to 63
Output Slave Unit that is
allocated memory in
increments of 16 bits
Bit IN Slave Unit
Bit MIX Slave Unit
0 to 127
Input Slave Unit or I/O Slave
Unit that is allocated memory
in increments of 2 bits
Bit OUT Slave Unit
0 to 127
Output Slave Unit that is
allocated memory in
increments of 2 bits
Repeater Unit
0 to 63
Repeater Unit
Summary of Contents for 3G8F7-CRM21
Page 4: ...iv...
Page 10: ...x TABLE OF CONTENTS...
Page 46: ...26 Connecting the Communications Power Supply Cables Section 2 4...
Page 74: ...54 Board Hardware Error Notification Section 4 8...
Page 173: ...153 APPENDIX D Sample Program D 1 Sample Program 154...
Page 230: ...210 Wiring for Power Supply Section E 5...
Page 234: ...214 Index...
Page 236: ...216 Revision History...
Page 237: ......