140
Shared Memory Area Specifications
Section B-3
I/O size information format
Network Parameter
This is the network setting for the CompoNet Master Board.
Normally, no setting is required. It is set when the network parameter is
enabled. The command is used to make the setting.
Data format
Offset address: 0x4692
Bit
Flag
Description
0 to 4
Number of IN
channels (points)
Set the number of IN channels of Slave Units.
Set the Bits 0 to 5 to 0 (OFF), when the number of IN
channels is zero.
=00000: 2 points, =00001: 4 points,
=00010: 8 points, =00011: 16 points,
=00100: 32 points, =00101: 48 points,
=00110: 64 points, =00111: 80 points,
=01000: 96 points, =01001: 112 points,
=01010: 128 points, =01011: 144 points,
=01100: 160 points, =01101: 176 points,
=01110: 192 points, =01111: 208 points,
=10000: 224 points, =10001: 240 points,
=10010: 256 points, others: prohibited
5
IN-setting enabled
flag
0: Disabled IN number setting
1: Enabled IN number setting
6 to 7
Reserved area
Set 0 (OFF).
8 to 12
Number of OUT
channels
Set the number of OUT channels for Slave Units.
Set the Bits 8 to 13 to 0 (OFF), when the number of
OUT channels is zero.
=00000: 2 points, =00001: 4 points,
=00010: 8 points, =00011: 16 points,
=00100: 32 points, =00101: 48 points,
=00110: 64 points, =00111: 80 points,
=01000: 96 points, =01001: 112 points,
=01010: 128 points, =01011: 144 points,
=01100: 160 points, =01101: 176 points,
=01110: 192 points, =01111: 208 points,
=10000: 224 points, =10001: 240 points,
=10010: 256 points, others: prohibited
13
Out-setting enabled
flag
0: Disabled OUT number setting
1: Enabled OUT number setting
14
Reserved area
Don't care
15
Slave Unit Enabled
flag
Enable the relevant flag when a Slave Unit is
registered.
0: The “All” setting is invalid. (No Slave Unit is
registered.)
1: The “All” setting is valid. (The Slave is registered.)
Offset
(Word)
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
+0
Event function enabling
+1
Monitoring time of event addressed to Slave Units
+2 to +4
Reserved
Summary of Contents for 3G8F7-CRM21
Page 4: ...iv...
Page 10: ...x TABLE OF CONTENTS...
Page 46: ...26 Connecting the Communications Power Supply Cables Section 2 4...
Page 74: ...54 Board Hardware Error Notification Section 4 8...
Page 173: ...153 APPENDIX D Sample Program D 1 Sample Program 154...
Page 230: ...210 Wiring for Power Supply Section E 5...
Page 234: ...214 Index...
Page 236: ...216 Revision History...
Page 237: ......