144
Command Specifications
Section B-4
•
Network parameter
•
Slave Unit parameter
Command
START_IOCYCLE
Purpose
Start the I/O communications.
Code
0x1001
Argument
None
Set 0x0000.
Response code
Normal end: 0x0000
At an error:
Status change not allowed: 0x8101
Remarks
•
This command is used to start the I/O communications, when the I/O
communications manual startup function is enabled or after the I/O
communications is explicitly stopped.
•
These are the possible causes of having a situation in which no status
change is allowed.
•
The I/O communications has already started.
•
The communications cycles have stopped.
Command
STOP_IOCYCLE
Purpose
Stop the I/O communications.
Code
0x1002
Argument
None
Set 0x0000.
Response code
Normal end: 0x0000
At an error:
Status change not allowed: 0x8101
Remarks
•
These are the possible causes of having a situation in which no status
change is allowed.
•
The I/O communications has already stopped.
•
The communications cycles have stopped.