112
Shared Memory Area Specifications
Section B-3
StateStatus
Data format
Offset address: 0x00B2
Detailed format
Offset
(Word)
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
+0
StateStatus
Bit
Name
Access
Description
00
Communications
error occurred on
a Slave Unit
Read
0 (OFF): Normal
1 (ON): An error occurred.
The bit will be 1 (or “on”) even if one of the
participating Slave Units has a communications
error.
01
Registration Table
comparison error
occurred
Read
0 (OFF): Normal
1 (ON): An error occurred.
The flag can be on only when the Registration
table function is enabled.
The flag will be on if any one of the Slave Units
(i.e. a node address and model combination of
a Slave Unit) that participated in the network
while the power is on does not conform to the
Registration table (i.e., a table that registered
the node addresses and the models of the
Slave Units) or if a non-registered Slave Unit is
found to have participated.
02
Communications
stop due to
communications
error occurred
Read
0 (OFF): Normal
1 (ON): An error occurred.
This flag can be on only when the
Communications stop due to communications
error function is enabled. The bit will be 1 (or
“on”) even if one of the participating Slave Units
has a communications error.
03
Slave duplication
error occurred
Read
0 (OFF): Normal
1 (ON): An error occurred.
The bit will be 1 (or “on”) if the Slave duplication
error occurs or if a Slave Unit has an error due
to unstable communications.
04
Communications
error occurred on
a Repeater Unit
Read
0 (OFF): Normal
1 (ON): An error occurred.
The bit will be 1 (or “on”) even one of the
participating Slave Units has a communications
error.
05
Repeater
duplication error
occurred
Read
0 (OFF): Normal
1 (ON): An error occurred.
The bit will be 1 (or “on”) if the Repeater
duplication error occurs or if a Repeater Unit
has an error due to unstable communications.
06
All registered
Slave Units
participating
Read
0 (OFF): Not all of the registered Slave Units
have participated,
1 (ON): All of the registered Slave Units have
participated.
This bit will be on only when the Registration
table function is enabled.
07
I/O
communications
started
Read
0 (OFF): I/O communications stops
1 (ON): I/O communications is running
Summary of Contents for 3G8F7-CRM21
Page 4: ...iv...
Page 10: ...x TABLE OF CONTENTS...
Page 46: ...26 Connecting the Communications Power Supply Cables Section 2 4...
Page 74: ...54 Board Hardware Error Notification Section 4 8...
Page 173: ...153 APPENDIX D Sample Program D 1 Sample Program 154...
Page 230: ...210 Wiring for Power Supply Section E 5...
Page 234: ...214 Index...
Page 236: ...216 Revision History...
Page 237: ......