ASTRONOMICAL ONE-CHANNEL
TIME PROGRAMMER ZCM-31, ZCM-31P/U
INSTRUCTION MANUAL
ZAMEL
Sp. z o.o.
ul. Zielona 27, 43-200 Pszczyna, Poland
Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04
www.zamel.com
, e-mail: [email protected]
plik: zcm-31_31_pu_bateria_inst_ext_gb | modyfikacja: 25.10.2019
DESCRIPTION
MAIN MENU
APPEARANCE**
CHANGE OF MODE OF WORK (AUTOMATIC, MANUAL)
STORAGE MODE / BATTERY REPLACEMENT
● ZCM series programmers have a default setting, the so called storage mode in order to protect the battery during storage.
● In case of battery backup operation the storage mode is switched off during the first use of the programmer. It is done by means of a short pressing of the
push-button and subsequent date and time adjustment.
● In case of a nominal power supply the storage mode is switched off during the first use of the programmer by means of date and time adjustment.
● Adjusting the programmer into the storage mode is realised by means of a reset - in order to carry it out press at the same time the and push-buttons
in the main window.
● ZCM series programmers have the option to replace the clock maintenance battery. Before replacing the battery, disconnect the programmer from the
external power supply. Please pay the attention to correct battery polarity when replacing.
Do not dispose of this device with other
waste! In order to avoid harmful effects
on the environment and human health,
the used device should be stored in
designated areas. For this purpose, you
can dispose of household waste free of
charge and in any quantity to a collection
point set up, as well as to the shop when
you buy new equipment.
Description of elements and messages displayed
Buttons descriptions
• In the main window - entry to automatic mode or change of the transmitter status, if the clock is already in the automatic mode;
• In other windows - one level up exit without saving the introduced data;
• In the main window - entry to manual mode or change of transmitter status if the clock is already in the manual mode;
• In other windows- one level up exit without saving the introduced data;
• In the main window - entry to main menu;
• In other windows - entry to sub- menu or confirmation of the parameter being set;
• Shifting windows /menu options or increasing/ decreasing of the parameter being set;
• Right cursor ( ) in the main window- displaying a time of sunrise and sunset.
We enter menu from the main window by
choosing OK; we move inside menu using cur-
sors . Return to the main window is possible
after pressing button
or
.
You can enter the windows of displaying cal-
culated sunrise/sunset time from the main
window by using cursor . Return is automat-
ical after 10 s.
Function Description
NIGHT BREAK SETTING
CORRECTION OF TIME SETTING (SUNRISE/ SUNSET TIME)
CURRENT TIME SETTING
CURRENT DATE SETTING
TIME SETTING (SUMMER/WINTER SEASON)
GEOGRAPHICAL POSITION AND TIME ZONE SETTING
EXTERNAL INPUT SETTING
EXTERNAL MEMORY ADJUSTMENT**
CALCULATED SUNRISE TIME
CALCULATED SUNSET TIME
FEATURES
TECHNICAL DATA
DESCRIPTION
ZCM-31
Power supply clamps: A1, A2
Rated voltage: ZCM-31: 230 V AC
~
(-15 ÷ +10 %)
ZCM-31/U: 24 ÷ 250 VAC, 30 ÷ 300 V DC
Rated frequency: 50 / 60 Hz
Rated power consumption: 2 W / 14 VA
Number of channels: 1
Programme: astronomical
Mode of work: manual, automatic
Change of season summer/ winter: automatic, manual
Colour of LCD panel lighting: amber
Input: yes
Accuracy of time measurement: max. ±1 s / 24 h at temp. 25 °C
Time of clock maintenance: 3 years
Time of programme maintenance: 5 years
Clamps of release system: IN, IN, IN, IN
Clamps of receiver power supply: 11, 12, 14
Parameters of transmitter contacts: 1NO/NC-16 A/250 V AC1 4000 VA
Number of terminating clamps: 12
Intersection of terminating conductors: 0,2 ÷ 2,50 mm
2
Temperature of work: -20 ÷ +60
o
C
Position of work: any
Fixing of casing: TH 35 rail (PN-EN 60715)
Level of protection of casing: IP20 (PN-EN 60529)
Protectivity class: II
Overvoltage category: II
Level of pollution: 2
Measurements: two-module (35 mm) 90x35x66 mm
Weight: 0,17 kg
Compatibility with norms: PN-EN 60730-1; PN-EN 60730-2-7
PN-EN 61000-4-2,3,4,5,6,11
● Steering dependant on a current hour in
an astronomical cycle,
● two-module casing with a protective flap
valve,
● steering input IN,
● lighting the LCD display.
Digital steering clocks ZCM-31 are intended
for realization of time functions in the sys-
tems of automatics and steering. Switching
on/off the appliance is connected with sun-
rise and sunset (dawn an dusk). The infor-
mation about geographic coordinates, the
place of the clock’s installation, current date
and a shift in relation to the universal time-
all these factors are used in order to cal-
culate the time of sunrise and sunset. The
system calculates the end of civil dusk, that
is the phase, during which the centre of the
Sun’s face is located on the 6 degrees angu-
lar below the horizon- the Sun’s face is not
noticeable but sky is lit with dispersed sun-
light. The system additionally has a function
of a programmed night break and an ability
of shifting the calculated time of sunrise and
sunset within a range of +/- 120 min. The
construction of a casing makes it possible to
install the system on a rail TH 35 and pos-
sible sealing the appliance with lead.
The
construction of the system guarantees
supporting of all the settings with battery
energy when the electric power supply is
off.
In order to protect the battery during stor-
age, the ZCM series programmers have
a default setting, the so-called storage
mode in which the battery power con-
sumption is limited to a minimum.
The device should be connected
to a singlephase system accord-
ing to current standards. The
device connections will be de-
scribed in this manual. Only qual-
ified electricians are allowed to mount, connect
and adjust the device. It is necessary to read
this manual and know the unit functions be-
fore the device mounting. Do not disassembly
the device casing or you will lose any warranty
rights and expose yourself to the electric shock
hazard. Before mounting operation make sure
of disconnecting the connection wires from the
electric network. Use a cross-head screwdriver
of 3.5 mm diameter to mount the device. The
relay should be carried, stored and used in an
appropriate way. Do not mount the device in
case of any device parts lack, damage or defor-
mation. In case of malfunction please notify the
manufacturer.
CAUTION
* does not apply to the product ZCM-31
** apply to the product ZCM-31P/U
* does not apply to the product ZCM-31
** apply to the product ZCM-31P/U
**
- days of week
- relay status
- automatic mode
- manual mode
/ - winter time / summer time
- external input
/
- day / night
- day
- year
- night break setting
- time correction setting
- current time setting and summer/winter time shift
- current date setting
- geographical position setting
- external input setting
- external memory operation**
- external memory record**
- external memory reading**
- external memory busy**
- reading / record error**
/
- sunrise time / sunset time
/
- latitude/ longitude
- automatic,
- user’s
- switched on / switched off
CHANGE OF MODE INTO MANUAL - if the system is situated in the main window and it is in the
automatic mode, pressing the button will cause a shift of the system from the manual mode with
simultaneous change of transmitter status;
Subsequent pressing of button will cause switching transmitter to the opposite status without
change of work mode;
CHANGE OF MODE INTO AUTOMATIC - if the system is placed in the main menu and it is in the
manual mode, pressing button will cause automatic shift to the automatic mode, with simultaneous
updating transmitter status.
Winter time
Summer time
Manual mode
Automatic mode
Week’s day
Relay state
Info field / data
Current time
(gg:mm:ss)
Power terminals
(A1, A2)
LCD display
External memory**
Replaceable battery
Control buttons
Relay output terminals
(12, 12, 11, 11, 14, 14)
Trigger terminals
(IN, IN, IN, IN)
Day/night time