139
Shared Memory Area Specifications
Section B-3
Detailed format
Name
Access
Description
Function setting
Read/Write
Sets the Registration table function.
Registered Slave
participation time
Read/Write
This is the time in which to monitor the participation
of registered Slave Units. The value can be set in
units of 10 ms.
Settable range: 1 to 65535
Setting it to 0 will select the default of 1000
(10000ms).
Checking items
for the
Registration Table
Read/Write
Sets the items to check in the Registration table.
I/O size
information
Read/Write
Sets the I/O size information.
See the I/O size information format in the following
page for the set content.
Vendor Code
Read/Write
Sets these flags when the relevant flag of the
Registration table is set to check.
The values to be set are the ones in the Slave Unit
Identity object information.
Device Type
Read/Write
Product Code
Read/Write
Major Revision
Read/Write
Bit
Flag
Description
0
Registration
table enabled
flag
Set it to 1 (ON) when
the Registration tables
are used.
1
All Registered
Slave
Participation
Standby flag
0 (OFF): Disabled
1 (ON): Enabled
2 to 7 Reserved
area
Set 0 (OFF).
8
Communications
cycle optimization
flag
0 (OFF): Disabled
1 (ON): Enabled
9 to 15 Reserved area
Set 0 (OFF).
Bit
Flag
Description
0
VendorCode
0 (OFF) : Not checked.
1 (ON) : Checked.
1
DeviceType
2
ProductCode
3
MajorRevision
4 to 5 Reserved area
Summary of Contents for 3G8F7-CRM21
Page 4: ...iv...
Page 10: ...x TABLE OF CONTENTS...
Page 46: ...26 Connecting the Communications Power Supply Cables Section 2 4...
Page 74: ...54 Board Hardware Error Notification Section 4 8...
Page 173: ...153 APPENDIX D Sample Program D 1 Sample Program 154...
Page 230: ...210 Wiring for Power Supply Section E 5...
Page 234: ...214 Index...
Page 236: ...216 Revision History...
Page 237: ......