TA600032-EN0/0
- 48 -
5.2.3.1
RADD (00h) Device setting register
"Device number" and "Port attribute" of "G9006" can be set.
This register cannot be written while "MSTS.SBSY = 1" is set.
Write the "CDVOF" (11h) operation command and check that "MSTS.SBSY = 0" has been set.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
RSV
PMD
MONI
0
DN
Bit
Symbol
Description
5:0
DN
Set the "Device Number" of "Local LSI".
The "Device Number" can be set from "0" to "63".
For details, see "6.3.1 Device number".
6
0
Fixed to "0".
7
MONI
Set the "Operation mode".
0: Local operation mode (message communication) is selected.
1: Monitor operation mode (local information monitor) is selected.
For details, see "6.2 Operation mode".
12:8
PMD
Set the "Port attribute" of "I/O communication".
The "Port attribute" can be set from "00000b" to "11111b".
For details, see "5.2.3.1.1 Port attribute".
15:13
RSV
Set the "Virtual local LSI additional count".
The "Virtual local LSI additional count" can be set from "0" to "7".
For details, see "6.3.2 Virtual local LSI additional count".
5.2.3.1.1
Port attribute
The "Port attribute" of "I/O communication" is selected by "RADD.PMD".
The combination of "Port attribute" is 32 patterns in "Table 5.2-1 Port attribute".
The settings of "Device number" and "Port attribute" that are not in "G9006" and "Virtual local LSI" are ignored.
For example, if "RADD.DN = 00001b" is set, "1" will be set to "Device number" of "G9006".
When "RADD.RSV = 011b" is additionally set, "2", "3", and "4" are set in "Device number" of "Virtual local LSI".
In this case, the settings of "5" to "8" of "Port attribute" of "Device number" are ignored.
That is, when "RADD.PMD" is set to any value from "10000b" to "11111b", the result is the same as "RADD.PMD = 01111b".
All ports cannot be set to "Output attributes" only.
When sending data of 32 bytes or more to the "Local CPU", use two or more "G9006".
For the connection method, see "4.5.2 Multi-steps connection circuit" and "4.6.2 Multiple connection circuit".