Reznor, FSE, Installation Manual, EN 2020-02, D301160 Iss H
The return line should terminate within the
oil tank at the same level as the suction
line; in this case a non return valve is not
required. Should, however, the return line
terminate over the fuel level, a non return
valve is essential. This solution, however, is
less safe than the previous one, due to the
possibility of leakage in the valve.
Priming the pump: start the burner and
await priming. Should lock-out prior to
arrival of the fuel, wait at least 20 seconds
before repeating the operation
Figure 17. Burner oil pump details 40 -
175 suction feed
H(m)
L metres
8mm I.D
10mm I.D
0.0
35.0
100.0
1.0
30.0
100.0
1.0
25.0
100.0
1.5
20.0
90.0
2.0
15.0
70.0
3.0
8.0
30.0
3.5
6.0
20.0
Table 8 – Dimensions burner 40-175
suction feed
The dimension P should not exceed 4
metres to avoid damage to the pump seals
Figure 18. Burner oil pump details 225-
300 gravity feed from bottom of tank
H(m)
L metres
8mm I.D
10mm I.D
0.5
5.0
10.0
1.0
10.0
20.0
1.5
15.0
30.0
2.0
20.0
40.0
Table 9 – Dimensions burner 225-300
Burner technical details
The data and any pre-calibration at the
factory are non-binding. It is always
mandatory to check and adjust the
burner at start-up and in the actual
conditions of use.
Natural Gas
Model
FSE 40
FSE 60
FSE 75
FSE100
MIN
MAX
MIN
MAX
MIN
MA
MIN
MAX
Riello burner
BS1D
BS2D
BS2D
BS3D
Head pressure
mbar
2.9
5.5
2.7
6.1
4.6
7.6
2.6
6.0
Burner head position
No
4.0
1.0
5.0
2.0
Air damper position
No
1.5
4.0
1.3
2.9
2.2
6.0
0.6
2.0
Measured CO2
%
9.4
8.9
9.1
9.3
9.5
9.0
9.4
Measured CO
ppm
1
14
3
3
2
32
30
Gas connections
inch
Rp 1/2
Rp 3/4
Rp 3/4
Rp 3/4
NOTE: Head pressure is the differential pressure between the burner outlet gas pressure and the combustion chamber pressure.
Table 10a Burner technical details NATURAL GAS FSE 40-100
Natural Gas
Model
FSE 145
FSE 175
FSE 225
FSE 300
MIN
MAX
MIN
MAX
MIN
MAX
MIN
MAX
MIN
MAX
Riello burner
BS3D
BS4D
RS34 MZ
RS44 MZ
RS35/MBLU
Head pressure
mbar
4.2
8.6
4.1
9.3
3.7
8.5
5.5
10.0
1.5
5.7
Burner head position
No
5.0
6.5
3.0
2.0
3.0
Air damper position
No
1.5
5.0
1.5
5.0
40.0
80.0
45.0
70.0
20.0
43.0
Measured CO2
%
9.2
9.4
9.1
9.3
9.1
9.3
9.2
9.58
9.52
Measured CO
ppm
23
5
7
18
1
1
1
113
Gas connections
inch
Rp 3/4
Rp 1 ¼
Rp 1 ½
Rp 2
Rp 1 ½
NOTE: Head pressure is the differential pressure between the burner outlet gas pressure and the combustion chamber pressure.
Table 10b Burner technical details NATURAL GAS FSE 145-300
Summary of Contents for Reznor FSE 100
Page 2: ......
Page 46: ...PAGE 42 Reznor FSE Installation Manual EN 2020 02 D301160 Iss H...
Page 51: ......
Page 52: ......