Reznor, FSE, Installation Manual, EN 2020-02, D301160 Iss H
Information requirements for warm air heaters Commission Regulation (EU) 2018
B1 warm air heater:
[NO]
C2 warm air heater:
[NO]
C4 warm air heater:
[NO]
Type of fuel:
Heating Oil
Model:
FSE
FSE40
O
FSE60
O
FSE75
O
FSE100
O
FSE145
O
FSE175
O
FSE225
O
FSE300
O
Item:
Symbol
Units
Capacity:
Rated heating capacity:
Prated,h
[kW]
40.0
55.5
69.9
96.4
144.9
175.1
218.9
304.3
Minimum capacity:
Pmin
[kW]
33.2
45.5
53.5
84.3
113.8
133.3
158.6
222.5
Electric power consumption:
At rated heating capacity:
elmax
[kW]
0.278
0.184
0.192
0.405
0.405
0.43
0.53
0.53
At minimal capacity:
elmin
[kW]
0.247
0.175
0.176
0.396
0.396
0.375
0.53
0.53
In standby mode:
elsb
[kW]
0.003
0.003
0.003
0.003
0.003
0.003
0.003
0.003
Useful efficiency:
Useful efficiency at rated
heating capacity:
ƞ
nom
[%]
87%
87%
87%
85%
86%
87%
87%
87%
Useful efficiency at minimum
capacity:
ƞ
pl
[%]
89%
89%
88%
87%
88%
89%
90%
89%
Other items:
Envelope loss factor:
Fenv
[%]
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Flame consumption:
Pign
[kW]
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Emissions of nitrogen oxides
[input energy (GCV)]:
NOx
[mg/
kWh]
130
133
151
145
129
127
127
113
Emission efficiency:
ƞ
s,flow
[%]
90%
90%
91%
89%
89%
90%
91%
90%
ErP seasonal space heating
energy efficiency:
ƞ
s
[%]
74%
75%
76%
72%
74%
75%
77%
76%
Thermal efficiency at rated
heating capacity [NCV]:
ƞ
[%]
93%
92%
93%
91%
92%
92%
93%
93%
ErP Data chart oil