Reznor, FSE, Installation Manual, EN 2020-02, D301160 Iss H
Gas
Model
FSE
40
FSE
60
FSE
75
FSE
100
FSE
145
FSE
175
FSE
225
FSE
300
Flue type
Class
B23 / B53
Heat output (G20)
kW
39.0
56.8
68.5
99.2
143.5
175.9
223.4
300.0
Heat input nett (G20)
kW
43.0
63.0
75.2
110.0
158.0
195.0
248.0
328.0
Efficiency nett
%
91
91
91
91
91
91
91
92
Gross flue gas temperature (1)
°C
210
220
205
215
210
215
220
200
Heat output low fire
kW
28.0
38.2
52.9
67.1
99.9
124.0
153.6
230.6
Heat input nett low fire
kW
30.0
41.0
56.7
72.0
106.0
131.2
165.0
244.0
Efficiency low nett
%
94
93
94
93
95
95
93
94
Gross flue gas temperature (1)
°C
155
155
155
155
140
140
155
140
Nominal inlet pressure G20
natural gas
mbar
20
Natural gas G20 consumption
m³/h
4.6
6.7
8.0
11.6
16.7
20.6
26.2
34.7
Nominal inlet pressure G31
LPG gas
mbar
37
Nominal inlet pressure G31
(NL) LPG gas
mbar
30
LPG gas G31 consumption
litres
6.8
9.8
11.3
17.2
24.4
30.9
39.2
50.2
Heating Oil
Model
FSE
40
FSE
60
FSE
75
FSE
100
FSE
145
FSE
175
FSE
225
FSE
300
Flue type
Class
B23 / B53
Heat output (35 sec)
kW
40.0
55.5
69.9
96.4
144.9
175.1
218.9
304.3
Heat input nett (35 sec)
kW
43.0
60.0
75.2
106.0
158.0
189.3
235.0
328.0
Efficiency nett
%
93
92
93
91
92
92
93
93
Gross flue gas temperature (1)
°C
195
200
195
240
230
205
190
200
Heat output low fire
kW
33.2
44.4
53.5
84.3
113.8
133.3
158.6
222.5
Heat input nett low fire
kW
35.0
48.0
56.7
90.6
120.9
141.1
165.0
235.0
Efficiency low nett
%
95
93
94
93
94
94
96
94
Gross flue gas temperature (1)
°C
150
170
165
200
170
165
120
150
Heating oil (35 sec)
consumption
kg/h
3.6
5.0
6.3
8.9
13.3
16.0
19.8
27.6