Reznor, FSE, Installation Manual, EN 2020-02, D301160 Iss H
Kerosene
Model
FSE 40
FSE 60
FSE 75
FSE100
MIN
MAX
MIN
MAX
MIN
MAX
MIN
MAX
Riello burner
RG1RKD
RG2D
RG2D
RG3D
Nozzle danfos 60°S
GPH
1.00
1.35
1.75
2.5
Pump pressure
bar
8.0
10.0
7.0
11.0
8.0
10.0
8.0
10.0
Burner head position
No
4.0
0.0
0.0
5.0
Air damper position
No
0.5
2.0
0.5
2.0
0.6
1.9
1.1
2.0
Measured CO2
%
11.76
11.69
11.88
12.23
12.00
12.01
11.65
12.44
Measured CO
ppm
1
2
4
2
1
1
1
1
Pump connection
inch
3/8
3/8
3/8
3/8
Smoke number
No
1
1
0
0
1
1
1
1
Table 13a Burner technical details KEROSENE FSE 40-145
Kerosene
Model
FSE 145
FSE 175
FSE 225
FSE 300
MIN
MAX
MIN
MAX
MIN
MAX
MIN
MAX
Riello burner
RG3D
RG4D
RG5D
RL32 BLU
Nozzle danfos 60°S
GPH
3.5
4.5
3.0
2.0
7.0
Pump pressure
bar
8.0
10.0
7.0
10.0
11.0
11.0
7.0
11.0
Burner head position
No
5.0
5
4.0
1.0
Air damper position
No
0.7
2.0
0.8
3.0
0.5
6.0
40.0
70.0
Measured CO2
%
12.04
12.08
12.55
12.54
12.49
12.63
12.70
12.70
Measured CO
ppm
1
1
1
1
0
1
1
1
Pump connection
inch
3/8
3/8
3/8
3/8
Smoke number
No
1
1
0
0
0
0
0
0
Table 13b Burner technical details KEROSENE FSE 175-300
Heating Oil
Model
FSE 145
FSE 175
FSE 225
FSE 300
MIN
MAX
MIN
MAX
MIN
MAX
MIN
MAX
Riello burner
RG3D
RG4D
RG5D
RL32 BLU
Nozzle danfos 60° S
GPH
3.00
3.50
3.50
1.50
5.50
Pump pressure
bar
8.0
13.7
8.0
14.4
10.9
10.9
9.0
17.5
Burner head position
No
5.0
2.5
6.0
1.0
Air damper position
No
0.6
3.9
0.7
2.3
0.5
3
41.0
129
Measured CO2
%
12.47
12.63
12.69
12.44
12.69
12.52
12.48
12.50
Measured CO
ppm
2
4
1
1
2
2
1
1
Pump connection
inch
3/8
3/8
3/8
3/8
Smoke number
No
0
0
0
0
0
0
0
0
Table 12b Burner technical details OIL FSE 145-300
Summary of Contents for Reznor FSE 100
Page 2: ......
Page 46: ...PAGE 42 Reznor FSE Installation Manual EN 2020 02 D301160 Iss H...
Page 51: ......
Page 52: ......