PAGE 12 Reznor, FSE, Installation Manual, EN 2020-02, D301160 Iss H
Kerosene
Model
FSE
40
FSE
60
FSE
75
FSE
100
FSE
145
FSE
175
FSE
225
FSE
300
Flue type
Class
B23 / B53
Heat output (28 sec)
kW
40.0
57.3
69.8
102.1
138.4
182.0
210.4
305.4
Heat input nett (28 sec)
kW
43.0
61.0
75.2
110.0
150.0
195.0
225.0
328.0
Efficiency nett
%
93
94
93
93
92
93
93
93
Gross flue gas temperature (1)
°C
180
170
190
205
210
185
200
195
Heat output low fire
kW
35.8
45.3
62.8
88.5
124.4
153.0
129.2
251.2
Heat input nett low fire
kW
38.0
48.0
67.0
95.0
134.0
161.0
135.0
265.0
Efficiency low nett
%
95
95
94
94
93
96
96
95
Gross flue gas temperature (1)
°C
155
155
170
185
195
145
145
155
Kerosene (28 sec) consumption
kg/h
3.6
4.8
6.2
8.9
12.4
16.0
18.7
26.1
Model
FSE
40
FSE
60
FSE
75
FSE
100
FSE
145
FSE
175
FSE
225
FSE
300
Fan thermostat calibration
°C
+35
Limit thermostat calibration
°C
+100
Range of use
°C
-15/+40
External static pressure
Pa
80
150
150
150
150
150
150
150
Supply air fan quantity
No.
1
Fan size
Type
10-10
280
280
355
355
355
355
400
Sound level (2)
dB(A)
74.0
76.9
81.6
79.8
85.5
76.6
82.7
82.9
Nominal temperature rise
°C
33
35
33
35
39
37
35
36
Nominal airflow rate
m³/h
3500
4800
6300
8300
10900 14000 19000 25000
Nozzle quantity (nozzle version
only)
No.
2
2
3
3
3
4
4
4
Combustion chamber pressure
mbar
0.2
1.1
1.2
1.4
2.0
1.4
1.5
2.9
(1) Referred to combustion air tempe15°C
(2) Sound power at inlet of fan
Table 2 – Technical specifications