Reznor, FSE, Installation Manual, EN 2020-02, D301160 Iss H
CONTROL INTERCONNECTIONS
Power Supply
Controls
SmartCom3
Other Controls
*IMPORTANT* Please remove 'plug-in' jumper
Legend:
Heater Terminals
Controls Terminals
Notes:
1.
230v Single phase supply for FSE40 only.
2.
400v Three phase supply for FSE 60-300 models.
3.
SmartCom sensor & remote 'on' use 6A screened mains cable up to 100 metre run.
4.
Fuse rating must be sufficiently sized to handle heater & motor loadings.
3.
Terminals shown may not be in numerical order. Unused terminals may not be shown at all.
900688 - FSE Control Interconnections
NEUTRAL
LIVE
1-Phase 230v 50Hz
L
N
1-Phase Permanent
Mains Supply
3-Phase 400v 50Hz
L2
N
Mains Fused Isolator - Must be installed within 1 metre of the appliance
3-Phase Permanent
Mains Supply
L1
L3
Optional Room or Return Air Sensor
L
N
E
9
14
15
41
40
E
2N
1L
8
7
6
B1
B0
B2
'ON'
'OFF'
B.M.S. or Remote Switching
D0
D1
Optional
Duct Sensor
S/ R0
S/ R1
L
9
Fan Only Function
240v
Time / Temperature
Control (1st Stage)
14
15
Temperature Control
(2nd Stage)
Please Note: The SmartCom control panel is supplied fitted and wired to all new FSE cabinet heaters