Reznor, FSE, Installation Manual, EN 2020-02, D301160 Iss H
ErP Data chart natural gas
Information requirements for warm air heaters Commission Regulation (EU) 2018
B1 warm air heater:
[NO]
C2 warm air heater:
[NO]
C4 warm air heater:
[NO]
Type of fuel:
Natural Gas
Model:
FSE
FSE40
G
FSE60
G
FSE75
G
FSE100
G
FSE145
G
FSE175
G
FSE225
G
FSE300
G
Item:
Symbol
Units
Capacity:
Rated heating capacity:
P rated,h
[kW]
39.0
56.8
68.5
99.2
143.5
175.9
223.4
300.1
Minimum capacity:
Pmin
[kW]
28.1
38.2
53.2
67.3
100.4
124.0
153.6
230.6
Electric power consumption:
At rated heating capacity:
elmax
[kW]
0.183
0.195
0.197
0.403
0.408
0.43
0.53
0.598
At minimal capacity:
elmin
[kW]
0.156
0.164
0.17
0.371
0.38
0.375
0.53
0.565
In standby mode:
elsb
[kW]
0.003
0.003
0.003
0.003
0.003
0.003
0.003
0.003
Useful efficiency:
Useful efficiency at rated
heating capacity:
ƞ
nom
[%]
82%
81%
82%
81%
82%
81%
81%
82%
Useful efficiency at minimum
capacity:
ƞ
pl
[%]
84%
84%
84%
84%
85%
85%
84%
85%
Other items:
Envelope loss factor:
Fenv
[%]
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Flame consumption:
Pign
[kW]
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Emissions of nitrogen oxides
[input energy (GCV)]:
NOx
[mg/
kWh]
59
66
70
54
64
59
81
97
Emission efficiency:
ƞ
s,flow
[%]
91%
91%
91%
91%
90%
91%
90%
90%
ErP seasonal space heating
energy efficiency:
ƞ
s
[%]
72%
72%
72%
72%
72%
72%
72%
72%
Thermal efficiency at rated
heating capacity [NCV]:
ƞ
[%]
91%
90%
91%
90%
91%
90%
90%
91%
Summary of Contents for Reznor FSE 100