PAGE 32 Reznor, FSE, Installation Manual, EN 2020-02, D301160 Iss H
Control panel
Figure 19. Control panel
The control panel is located in the lower
left of the front panel, refer to instructions
provided with the control panel.
Limit safety thermostat
The appliance is equipped with a MANUAL
RESET LIMIT safety thermostat with the
element positioned on the air supply.
It functions to stop the burner if the air
becomes too hot. It can be restored by
pushing the restore button, after removing
the causes that have triggered it.
Fan thermostat
The appliance is equipped with a fan
thermostat with the element positioned on
the air supply.
Activating the fan max. 60 seconds after
the burner has started and it stops it
approx. 4 minutes after it has stopped.
Thus, preventing cold air from being
released when the heater is activated.
The thermal energy accumulated by the
heat exchanger will be disposed of before
the fan stops.
TR safety thermostat
The appliance is equipped with an
automatic reset TR safety thermostat with
the element positioned on the air supply.
It has the function of stopping the burner
if the air becomes overheated. Restoring is
automatic.
Controls
For its operation and programming, refer
to the dedicated instructions, which are
supplied together with the appliance.
LIMIT thermostat reset button:
Located on the LIMIT thermostat’s interface,
the button will reset the operation of the
burner after it has stopped due to over-
heating. Before resetting the device please
verify that the issues have been resolved
before continuing operation. If confused,
please contact manufacturer for further
clarification.
Ventilation/Heating
Operating cycle in fan only mode:
• Power the appliance
• Turn on the unit in fan only mode
At this point, the fan unit will operate and
air at ambient temperature will be released.
Operating cycle in heating mode:
• Power the appliance
• Set the room thermostat to desired
temperature
• Turn on the unit on “heating” mode.
COMMISSIONING