Operation
4-22
P/N 7105144G
2008 Nordson Corporation
VersaBlue_NW
Undertemperature Interlock
The undertemperature interlock prevents the melter motors from being
switched on as long as the material is too cold and thus too thick. This could
damage the pumps.
The undertemperature interlock is active during every
Heatup phase
(status
display) and after every standby. Also refer to section
Troubleshooting,
Undertemperature Fault Triggered.
If the system ready delay time is
activated, this time must also have expired before the interlock is disabled.
Motor Startup Protection
The motor startup protection prevents the motors from starting up on their
own after heatup or after a fault. The melter goes to startup protection if the
condition for
Motor running
:
All motors ON
AND
Enable motor
is fulfilled.
When the system is ready again (status display), the motors can be
switched on again via the control panel or the interface
Standard I/O
.
Acknowledge Startup Protection
On the Control Panel
Press the key
Switch on/off all motors (collective enable)
; startup protection
is acknowledged and all enabled motors run again.
Via Interface Standard I/O
Switch
All motors ON/OFF
from OFF to ON. All enabled motors run again.
Via Field Bus
Set
Switch ON/OFF All Motors (Collective Enable)
(Rising edge; refer to
Melter control
: If bit 1 = 0, then set to 1. If bit 1 = 1, set to 0 then back to 1).
All enabled motors are running again.
or
Switch off all motors with the keys
Switch motor on/off (individual enable)
on
the control panel; the startup protection is acknowledged. If the key(s) is/are
touched again: The respective motor starts up again:
The same applies to acknowledgement via standard I/O or field bus with the
signal
Enable motor
for the individual motor.
Summary of Contents for VersaBlue VB Series
Page 40: ...Introduction 2 14 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...
Page 66: ...Installation 3 26 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...
Page 150: ...Operation 4 84 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...
Page 174: ...Maintenance 5 24 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...
Page 236: ...Parts 8 2 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...
Page 250: ...Options 10 6 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...
Page 254: ...Password A 4 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...
Page 280: ...Glossary D 16 P N 7105144G 2008 Nordson Corporation VersaBlue_NW...