152019 – Global Timing out of Range
Yellow alarm. Initiated by IC922.
Cause
Corrective action
Specified global ignition timing is
beyond the valid range.
u
Adjust value.
152020 – Unknown Timing or Energy Level
Red alarm. Initiated by IC922.
Cause
Corrective action
No global ignition timing and
power level received, CAN bus
connection is faulty.
u
Check cabling and setting.
152021 – Individual Timing out of Range
Yellow alarm. Initiated by IC922.
Cause
Corrective action
Specified individual ignition
timing is beyond the valid range.
u
Adjust value.
152023 – Selftest Shutdown
Cause
Corrective action
Self-test is active with the engine
rotating.
u
Restart ignition system.
152024 – Open Primary Rate Exceeded
Red alarm. Initiated by IC922.
Cause
Corrective action
Admissible summation of
discharge faults is reached.
1. Check associated cabling.
2. Check ignition coils.
152026 – Open Primary, Channel 1
Yellow alarm. Initiated by IC922.
Cause
Corrective action
Ignition energy was not
discharged.
1. Check cabling to ignition coil.
2. Check ignition coil.
152027 – Open Primary, Channel 2
Yellow alarm. Initiated by IC922.
Cause
Corrective action
Ignition energy was not
discharged.
1. Check cabling to ignition coil.
2. Check ignition coil.
MS150059/01E 2012-07 | Troubleshooting | 79
TIM-ID: 0000017543 - 001