151021 – Warning Hold Position
Yellow alarm. Initiated by TecJet.
Cause
Corrective action
Hold position is activated.
u
Deactivate setting or interrupt serial communication.
151022 – Zero Pressure Detected
Yellow alarm. Initiated by TecJet.
Cause
Corrective action
No gas pressure/gas flow
detected.
u
Check gas pressure.
151023 – Zero Flow Detected
Yellow alarm. Initiated by TecJet.
Cause
Corrective action
No gas pressure/gas flow
detected.
u
Check gas pressure.
151024 – Flow Not Reached
Red alarm. Initiated by TecJet.
Cause
Corrective action
No gas flow detected.
1. Check inlet and outlet.
2. Check gas pressure, gas quality, gas filter, gas line for
obstruction.
3. Check engine for overloading.
151025 – Valve Position Error
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart TecJet.
151026 – High Elec Temp
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart TecJet.
151028 – Elec Temp Fail High
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart TecJet.
MS150059/01E 2012-07 | Troubleshooting | 73
TIM-ID: 0000017543 - 001