188
Redundant Systems
GB
SUPREMATouch
15
Redundant Systems
15.1 Application/Function Safety
For the safety functions of gas warning measuring instruments, the European standards
EN 60 079-29-1, EN 50 104, EN 50 271 and EN 50 402 apply for the monitoring of combustible
gas and vapors as well as oxygen.
Additionally, if systems are using microcomputers, EN 61 508 must be considered regarding func-
tional safety in a measuring and control application.
This standard divides the application types into Safety Integrity Levels SIL 1–4. The system must
be designed to meet the safety level required.
For Safety Integrity Level SIL 3 according to EN 61 508, the SUPREMATouch must be provided
with a redundant power supply. The redundant power supply for the system as well as for the MRC
TS module must have a failure rate of less than 6.73 * 10-6 1/h.
For Safety Integrity Level SIL 4, additional conditions must be met which are not achievable with
the SUPREMATouch.
By adding the MCP module, a second CAN bus and the necessary double modules for data acqui-
sition and setting alarms, the non-redundant system can be converted into a redundant system.
There must be sufficient spare slots in the rack for the additional MGO modules and sufficient
additional space in the cabinet for additional relay modules (MRO).
The following module types are needed for retrofitting:
15.2 Function of Redundant Systems
The block diagram (Fig. 127) of the redundant system shows its design and function:
The signal from the sensors connected to the MAT modules is amplified by 2 separate A/D
converters (on MAI + MAR), the measuring signal is digitised and transferred to the two CAN bus
systems (channels). The signal processing and evaluation of one channel is carried out inde-
pendently from the other. The table “Rack Modules” in chapter 15.3 "Design of the Redundant
System" shows the different components of the rack for a non-redundant and a redundant system.
For module functions, see chapter 11 "Modules".
MCP Module
Central Processing
MAI30 Module
Analogue Input
MAR Module
analogue Redundant
MGO Module
General Output
MRO8 Module
Relay Output (8 Relay)
MRO16 Module
Relay Output (2 x 8 Relay, redundant)
Summary of Contents for SUPREMATouch MCP 20
Page 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Page 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Page 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Page 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Page 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Page 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Page 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...