Digital Message Priority
The highest priority messages [with “1” being of highest priority] are displayed first. Messages with
a lower priority are displayed in addition if these use other indicating ranges for message display.
6.7
LED and Sounder Test
An LED and sounder test is provided for the MDO which enables a visual functional test of the
front panel LEDs and an acoustical test of the sounder. This test can be carried out independently
from the active operating state of the SUPREMATouch and does not affect the mode of operation
of the SUPREMATouch. To carry out this test, press the button shown in the illustration. The front
panel LEDs should now be illuminated (System–power, fail, inhibit and Signal–1st to 4th alarm,
fail). If there is an LED that is not illuminated when the switch is pressed, it is possible that the
MDO module needs to be replaced.
Fig. 53 MDO Module, Switch for LED Test
Message
Priority Display [List]
LEDs/Relays
Alarm 1
9
Measuring points status 1st Alarm Signal AL 1 on
Alarm 2
8
Measuring points status 2nd Alarm Signal AL 2 on
Alarm 3
7
Measuring points status 3rd Alarm Signal AL 3 on
Alarm 4
6
Measuring points status 4th Alarm Signal AL 4 on
System error
1
System Fail on
Signal error
3
Meas. point status Signal fail
Signal Fail on
Module error
1
Module fail on
CAN bus failure
1
Free
1
Measuring point status free
Measuring
10
Measuring point status measuring
Inhibit
2
Measuring point status inhibited
Inhibit on
DO [Disable Output]
2
Measuring point status
Inhibit flashing
Calibration
6
Measuring point status calibration Inhibit on
Sensor warm-up
4
Measuring point status suppressed Inhibit on
Measuring range overflow
5
Measuring point status overflow
Signal Fail on
New value
1
Signal flashing
LED and sounder test
Summary of Contents for SUPREMATouch MCP 20
Page 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Page 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Page 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Page 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Page 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Page 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Page 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...