217
Sensor Data
GB
SUPREMATouch
Simulation of normal operation / Alarm / RESET / Open or short-circuit fault indication:
Simulation
Effect
Normal operation
External power supply 23–32 V connected
according to circuit diagram
END OF LINE resistor 2K2 connected according
to circuit diagram
Connect resistor 10 K 0.5 W between terminal 1
and 2
Normal operation
Voltage of terminal 1–2 shall be <0.1 V
Alarm
External power supply 23–32 V connected
according to circuit diagram
END OF LINE resistor 2K2 connected according
to circuit diagram
Connect resistor 1.0 K 1% 0.5 W between
terminal 3 and 4
Alarm message
RESET
Connect wire jumper between terminals 3 and 4
Normal operation
After max. 45 s failure message appears.
Open-circuit of line
External power supply 23–32 Vconnected
according to circuit diagramEND OF LINE
resistor 2K2 not connected
Failure message
Line short-circuit
External power supply 23–32 Vconnected
according to circuit diagramEND OF LINE
resistor short-circuited
Failure message
Interruption of the supply voltage
External power supply 23–32 Vnot connected
END OF LINE resistor 2K2connected according
to circuit diagram
Failure message after max. 45 s
Leakage current
External power supply 23–32 V connected
according to circuit diagramEND OF LINE
resistor 2K2 connected according to circuit
diagramConnect resistor 10 K 0.5 W between
terminal 1 and 2Connect resistor 18 K between
terminals 4 and 5, or connect resistor 330R
between terminals 3 and 5.
Failure message
Voltage terminals 1-2 must be 23–32 V
Summary of Contents for SUPREMATouch MCP 20
Page 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Page 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Page 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Page 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Page 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Page 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Page 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...