Entering System Parameters
GB
SUPREMATouch
Relay connections subwindow
Fig. 23 Relay connections subwindow
Groups Window
Parameters for groups of measuring points can be viewed and changed here.The Groups window
is divided into two subwindows:
• Information
• Measuring Points
The following paragraphs describe the functions of the individual window fields and buttons.
The following fields described are identical in both subwindows:
Maximum three relays can be connected in series.The acknowledgment status will be
handed over from the child relay to the parent relay. The blinking and new alarm config-
uration of the child relay are not relevant here.
Relays are treated as one event in voting, regardless of the settings in point based
voting.
Field
Field Type
Function
Channel
Checkbox, not
set by default
If this condition is set, the selected relay output is activated
when the switching condition occurs for the relay shown in
the channel column in the specific line.
Field
Field Type
Function
Group No.
Selection Field
List of all available groups.
After a group number is selected, the available space of the
window is filled with data.
OK
Button
Press this button to accept the settings entered in both subwin-
dows for the selected group. After tapping the button, the param-
eters are immediately checked to see if they are valid. If the
parameters are valid, they become part of the system's param-
eter set. If they are not valid, a warning appears.
Cancel
Button
Press this button to discard the settings entered in both subwin-
dows for the selected group.
Clear
Button
Press this button to delete all parameters for the selected group.
The group will then return to the status it had before being set up
the first time.
Summary of Contents for SUPREMATouch MCP 20
Page 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Page 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Page 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Page 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Page 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Page 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Page 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...