36
Entering System Parameters
GB
SUPREMATouch
Field
Field Type
Function
Relay
Selection
Contains a list of all available relay outputs. After an output
number is selected, the rest of the window is filled, if
settings have already been entered for that output.
If an output number is selected that has not been configured
before, the settings from the last displayed output remain
and are used as the preliminary settings for the new output.
This makes it easy to copy the settings from one output to
another. If an output is displayed that has not yet been
configured, default values are used as the preliminary
settings.
This input field can be accessed without a key switch or
password if an output has been selected for which parame-
ters have already been set. If a number is entered that has
not been used before, authorization with a password or key
switch is required.
When first opened, the field contains the relay output that
was last selected in the Measuring Point window.
Tag
text, 10 charac-
ters; empty by
default
Enter a customer-specific designation for the selected relay
output.
Normal run
Selection,
default is closed-
circuit
Set the operating mode for the selected relay output:
• Closed circuit (normally energized):
The relay coil is energized in the no alarm status and is
de-energized in the alarm status.
• Open circuit (normally de-energized):
The relay coil is de-energized in the no alarm status and
is energized in the alarm status.
blinking
Checkbox, not
set by default
If enabled, the relay flashes at a frequency of approx.
0.5 Hz when activated until the alarm is acknowledged. This
function doesn't work combined with the inhibit condition.
New Alarm
Checkbox, not
set by default
If enabled, the relay output selected can be set to the status
defined by the input field Normal Run by acknowledging the
selected conditions, even if the conditions are still pending.
Point based
voting
Checkbox, not
set by default
If enabled, the counting for the voting is done by counting
the effected measuring points instead of the effected condi-
tions.
Summary of Contents for SUPREMATouch MCP 20
Page 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Page 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Page 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Page 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Page 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Page 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Page 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...