85
Service
GB
SUPREMATouch
6.8
System Configuration
Configuration during initial installation
If there is no configuration saved in the SUPREMATouch during transfer of the configuration and
the first MCP is not plugged into Slot1 of the rack, the PC program "SUPREMA Manager" displays
an error message "transmission failed". This can be ignored.
Varying or manual selection of a configuration
If there are different configurations in the SUPREMATouch modules, e.g. because of replacement
of an MCP, a system configuration message appears when the system is switched on for the first
time after the modification. The module from which the [effective] configuration is to be taken must
be specified.
(1) If the configuration is to be taken manually from a particular module, press the RESET button
for approx. 1 second directly after switch-on.
The system configuration message appears after the system starts so that the configuration of a
module can be selected.
Fig. 54 System Configuration Message
Selecting a Configuration
(2) Touch the desired configuration to select it.
(3) Press OK to copy the selected configuration to other MDO and/or MCP modules.
Loading a Configuration from SDcard
If an SDcard is inserted the Load button is activated. Press this button loads the stored configu-
ration from SDcard and continues the start-up with this configuration.
If a configuration is transferred to the SUPREMATouch with the "SUPREMA Manager",
this configuration is always saved in the MDO. If it is not certain that the configuration
was distributed to the system, choose
MDO
as the system configuration.
Summary of Contents for SUPREMATouch MCP 20
Page 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Page 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Page 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Page 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Page 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Page 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Page 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...