129
Installation
GB
SUPREMATouch
Turn-on Behavior and Failure Behavior MAO Module
After turn-on, at the analog outputs a 0 mA signal is issued for 10 - 15sec.
If the settings for FREEA / FREEB are done locally on the MGO or MAO modules (position INT),
or if no such modules are installed in the rack, then the switches FREEA / FREEB on the MIB have
to be set to the ON position.
Configuration MAT Module
Two solder bridges are provided for each input on the bottom of the circuit board for 3 or 5 wire
operation of the sensors:
CAUTION!
The solder bridges for 3 wire operation must only be closed when passive detectors (MPI module)
are connected. For 5 wire operation with active transmitters (MCI module), the solder bridges must
be open!
MAO Module, Configuration of turn-on behavior and failure behavior
CAN
FREE
Baud
Rack
A
B
A
B
4
2
1
4
2
1
Turn-on behavior
Behavior at CAN bus
failure
1
2
3
4
5
6
7
8
9
10
In case of alternative assembly
10
9
8
7
6
5
4
3
2
1
All analogue
outputs at 2 mA.
All analogue outputs at
2 mA after 2 min.
OFF OFF
All analogue
outputs at 2 mA.
Last status is kept.
OFF ON
All analogue
outputs at 0 mA.
All analogue outputs at
0 mA after 2 min.
ON
OFF
All analogue
outputs are 0 mA.
Last status is kept.
ON
ON
= Any switch
Solder bridge OPEN
= 5 wire operation
Solder bridge CLOSED
= 3 wire operation
Assignment:
BR1, BR2
input 1
BR3, BR4
input 2
BR5, BR6
input 3
BR7, BR8
input 4
BR9, BR10
input 5
BR11, BR12
input 6
BR13, BR14
input 7
BR15, BR16
input 8
Summary of Contents for SUPREMATouch MCP 20
Page 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Page 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Page 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Page 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Page 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Page 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Page 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...