3 - 8 3 - 8
MELSEC-Q
3 SPECIFICATIONS
(2) Input characteristic of Q62AD-DGH
Fig. 3.3 shows a graph of the Q62AD-DGH input characteristic.
1)
65535(32767)
64000(32000)
0
-1536(-768)
-10
0
10
20
30
4
24
Analog input practical range
Di
g
it
a
l out
p
u
t va
lu
e
Analog input current (mA)
The value within parentheses indicates the digital output value (16 bits).
Maximum resolution
Number
Analog input
range setting
Offset
value
Gain
value
Digital output value
(32 bits) 2
Digital output value
(16 bits) 2
32 bits
16 bits
1)
4 to 20mA
4mA
20mA
250.0nA
500.0nA
—
User range setting
1
1
0 to 64000
0 to 32000
151.6nA
303.2nA
Fig. 3.3 Input characteristic of Q62AD-DGH
POINT
(1) Set within the analog input range and digital output range for each input range.
If these ranges are exceeded, the maximum resolution and accuracy may not
fall within the performance specifications. (Avoid use in the dotted area of Fig.
3.3.)
(2) Set the offset/gain values for the user setting range 1 within a range in which
the following conditions are satisfied.
(a) Gain value 24mA, offset value 2mA
(b) { (gain value) - (offset value) } > 9.70mA
(3) When an analog value that exceeds the range of the digital output value 2 is
entered, the digital output value will be fixed at the maximum or minimum
value.
Digital output value (32 bits)
Digital output value (16 bits)
Analog input
range setting
Minimum
Maximum
Minimum
Maximum
4 to 20mA
User range setting
-1536
65535
-768
32767