3 - 14 3 - 14
MELSEC-Q
3 SPECIFICATIONS
(5) This function is executed at every sampling processing.
(6) Perform the following procedure to use this function.
1) Set the input signal error detection setting value for the corresponding channel.
2) Enable the A/D conversion of the corresponding channel.
3) Enable the input signal error detection of the corresponding channel.
4) Turn ON the operating condition setting request (Y9).
3.2.4 Warning output function
(1) Process alarm
(a) If the detected digital output value rose to or above the process alarm upper
upper limit value or fell to or below the process alarm lower lower limit value
and entered the warning output range zone, the warning output flag (buffer
memory address 48: Un\G48) and warning output signal (X8) turn ON and
the ALM LED is lit to indicate the warning.
(b) If, after the output of the warning, the detected digital output value fell below
the process alarm upper lower limit value or rose above the process alarm
lower upper limit value and returned to within the setting range, "0" is stored
into the bit position corresponding to the channel number of the warning
output flag (buffer memory address 48: Un\G48).
The warning output signal (X8) turns OFF only when all channels return to
within the setting range.
Digital output value
Upper upper
limit value
Upper lower
limit value
CH1 digital output
value
Lower upper
limit value
CH2 digital
output value
Lower lower
limit value
Warning
occurrence
Warning
occurrence
Warning output range zone
Warning output range outside zone
Included
Warning cancel
Warning
occurrence
Warning cancel
Warning cancel
CH1 process alarm upper limit value
(Buffer memory address 48, b0)
CH1 process alarm lower limit value
(Buffer memory address 48, b1)
CH2 process alarm upper limit value
(Buffer memory address 48, b2)
Time
Warning output signal (X8)
(c) When time or count averaging is specified, this function is executed at
intervals of the preset averaging time or averaging count.
When any other A/D conversion system (sampling processing, move
averaging, primary delay filter) is specified, this function is executed at
intervals of the sampling time.