APP -1 APP -1
MELSEC-Q
APPENDIX
APPENDIX
Appendix 1 Dedicated Instruction List and Available Devices
(1) Dedicated instruction list
The following table lists the dedicated instructions that can be used with the A/D
converter modules.
Instruction
Description
Reference
section
OFFGAN
Switches to the offset/gain setting mode.
Switches to the normal mode.
Appendix 1.1
OGLOAD
Reads the offset/gain values of the user range setting to
the CPU.
Appendix 1.2
OGSTOR
Restores the offset/gain values of the user range setting
stored in the CPU to the A/D converter module.
Appendix 1.3
POINT
When the module is mounted to a MELSECNET/H remote station, the dedicated
instructions cannot be used.
(2) Available devices
The following devices are available for the dedicated instructions:
Internal devices
Bit
Word
File register
Constant
X, Y, M, L, F, V, B
T, ST, C, D, W
R, ZR
-
Word device bit designation can be used as bit data.
Word device bit designation is done by designating Word device . Bit No. .
(Designation of bit numbers is done in hexadecimal.)
For example, bit 10 of D0 is designated as D0.A .
However, there can be no bit designation for timers (T), retentive timers (ST) and
counters (C).