7 - 19 7 - 19
MELSEC-Q
7 ONLINE MODULE CHANGE
7.3.4 When user range setting is used and initial setting was made with GX Configurator-AD
(other system is unavailable)
(1) Conversion disable
(a)
On the Operating condition setting screen of GX Configurator-AD, set
"Disable" in the Setting value field of CH A/D conversion enable/disable
setting, and click the [Execute test] button.
(b)
After making sure that the indication in the Current value field of CH A/D
conversion enable/disable setting is "Disable", change the Setting value
field of Operating condition setting request to "Setting request", and click
the [Execute test] button to stop conversion.
Monitor the A/D conversion completion flag (buffer memory address 10:
Un\G10) and confirm that conversion has stopped.
Summary of Contents for GX Configurator-AD
Page 2: ......
Page 23: ...2 6 2 6 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Page 120: ...5 31 5 31 MELSEC Q 5 UTILITY PACKAGE GX Configurator AD MEMO ...
Page 145: ...6 25 6 25 MELSEC Q 6 PROGRAMMING MEMO ...
Page 207: ......