3 - 2 3 - 2
MELSEC-Q
3 SPECIFICATIONS
Table 3.2 Performance Specifications of Q62AD-DGH
Model name
Item
Q62AD-DGH
Number of
analog input
points
2 points (2 channels)
Input
specification
Analog input
4 to 20mADC 4(Input resistance 250 )
Supply voltage
26±2VDC
Maximum
supply current
24mADC
Supply
power
specification Short-circuit
protection
Available
Limit current: 25 to 35mA
Connecting
with 2-wire
transmitter
Check terminals
Available
Digital output
16-bit signed binary (-768 to 32767)
32-bit signed binary (-1536 to 65535)
Maximum resolution
Analog input range
32-bit
16-bit
Digital output value
(32-bit)
Digital output value
(16-bit)
4 to 20mA
250.0nA
500.0nA
Users range setting
151.6nA
303.2nA
0 to 64000
0 to 32000
I/O characteristics, Maximum resolution
Reference accuracy 1
±0.05%
Digital output value (32-bit): ±32digit 2
Digital output value (16-bit): ±16digit 2
Accuracy
(Accuracy
relative to
digital output
value)
Temperature coefficient 3
±71.4ppm/°C (0.00714 %/°C)
Conversion speed
10ms/2 channels
Specific isolated area
Isolation method
Dielectric withstand
voltage
Insulation
resistance
Between I/O terminal and
PLC power supply
Photocoupler
isolation
Between analog input
channels
Transformer
isolation
Between external supply
power and analog input
Transformer
isolation
1780VAC rms/3 cycles
(elevation 2000m)
500VDC
10M or more
Isolation specifications
Maximum number of writes for
E
2
PROM
100,000
Number of I/O occupied points
16 points
Connected terminal
18 points terminal block
Applicable wire size
0.3 to 0.75mm
2
Applicable solderless terminals
R1.25-3 (Solderless terminals with sleeves are not applicable)
24VDC +20%, -15%
Ripple, spike within 500mV
P-P
Inrush current : 5.5A, within 200µs
External supply power
0.19A
Internal current consumption (5VDC)
0.33A
Weight
0.19kg
1: Accuracy of offset/gain setting at ambient temperature
Q62AD-DGH needs to be powered on 30 minutes prior to operation for compliance to the specification
(accuracy).
2: "digit" indicates a digital output value.
3: Accuracy per temperature change of 1°C
Example) Accuracy when temperature changes from 25 to 30°C
0.05% (reference accuracy) + 0.00714 %/°C (temperature coefficient) 5°C (temperature
change difference) = 0.0857%
4: User range setting is 2 to 24mA.
3