3 - 20 3 - 20
MELSEC-Q
3 SPECIFICATIONS
Table 3.5 List of I/O signal (Q62AD-DGH)
Signal direction CPU Module Q62AD-DGH
Signal direction CPU Module
Q62AD-DGH
Device No. (Input)
Signal name
Device No. (Output)
Signal name
X0
Module ready
Y0
X1
Y1
X2
Y2
X3
Y3
X4
Y4
X5
Y5
X6
Y6
X7
Use prohibited
1
Y7
X8
Warning output signal
Y8
Use prohibited
1
X9
Operating condition setting completed flag
Y9
Operating condition setting request
XA
Offset/gain setting mode flag
YA
User range writing request
XB
Channel change completed flag
YB
Channel change request
Input signal error detection signal
XC
Offset/gain change completed flag
YC
Offset/gain change request
XD
Maximum value/minimum value reset
completed flag
YD
Maximum value/minimum value reset
request
XE
A/D conversion completed flag
YE
Use prohibited
1
XF
Error flag
YF
Error clear request
POINT
1 These signals cannot be used by the user since they are for system use only.
If these are turned ON/OFF by the sequence program, the functioning of the
A/D converter module cannot be guaranteed.
Summary of Contents for GX Configurator-AD
Page 2: ......
Page 23: ...2 6 2 6 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Page 120: ...5 31 5 31 MELSEC Q 5 UTILITY PACKAGE GX Configurator AD MEMO ...
Page 145: ...6 25 6 25 MELSEC Q 6 PROGRAMMING MEMO ...
Page 207: ......