3 - 22 3 - 22
MELSEC-Q
3 SPECIFICATIONS
Device No.
Signal Name
Description
X9
Operating
condition setting
completed flag
(1) This signal is used as an interlock condition to turn ON/OFF the Operating condition
setting request (Y9) when any of the following settings has been changed.
• A/D conversion enable/disable setting (buffer memory address 0: Un\G0)
• CH Average time/Average number of times/Move average/Time constant settings
(buffer memory addresses 1 to 4: Un\G1 to Un\G4)
• CH A/D conversion starting time setting (buffer memory addresses 5, 6: Un\G5,
Un\G6)
• Averaging process specification (buffer memory address 9: Un\G9)
• Input signal error detection/warning output settings (buffer memory address 47:
Un\G47)
• CH process alarm upper/lower limit value (buffer memory addresses 86 to 117:
Un\G86 to Un\G117)
• CH rate alarm warning detection period (buffer memory addresses 118 to 121:
Un\G118 to Un\G121)
• CH rate alarm upper/lower limit value (buffer memory addresses 122 to 137:
Un\G122 to Un\G137)
• CH input signal error detection setting value (buffer memory addresses 138 to 141:
Un\G138 to Un\G141)
(2) When the operating condition setting completed flag (X9) is OFF, A/D conversion
processing is not performed. Under the following conditions, the operating condition
setting completed flag (X9) turns OFF.
• When operating condition setting request (Y9) is ON
Performed by the A/D converter module
Performed by the sequence program
A/D conversion
completed flag (XE)
Module ready (X0)
Operating condition
setting completed flag (X9)
Operating condition
change request (Y9)