29 Data Table Operation – FNC250 to FNC269
29.7 FNC269 – SCL2 / Scaling 2 (Coordinate by X/Y Data)
29.7
FNC269 – SCL2 / Scaling 2 (Coordinate by X/Y Data)
Outline
This instruction executes scaling of the input value using a specified data table, and outputs the result.
There is SCL (FNC259) instruction whose data table configuration is different.
SCL2 instruction is supported in the FX
3UC
Series Ver. 1.30 or later.
→
For SCL (FNC259) instruction, refer to Section 29.4.
1. Instruction format
2. Set data
3. Applicable devices
Operand Type
Description
Data Type
Input value used in scaling or device number storing the input value
16- or 32-bit binary
Head device number storing the conversion table used in scaling
Device number storing the output value controlled by scaling
Oper-
and
Type
Bit Devices
Word Devices
Others
System User
Digit Specification
System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
X Y M T C S D
.b KnX KnY KnM KnS
T
C
D
R U
\G
V
Z Modify K
H
E
"
"
P
3
3
3
3
3 3 3 3
3
3
3 3
3 3
3
3
3
3
3 3 3 3
3
3
P
FNC 269
SCL2
D
Mnemonic
Operation Condition
16-bit Instruction
7 steps
SCL2
SCL2P
Mnemonic
Operation Condition
Continuous
Operation
Pulse (Single)
Operation
32-bit Instruction
13 steps
DSCL2
DSCL2P
Continuous
Operation
Pulse (Single)
Operation
S
1
S
2
D
S
1
S
2
D