564
FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
22 External Device – FNC170 to FNC179
22.4 FNC177 – WR3A / Write to Dedicated Analog Block
22.4
FNC177 – WR3A / Write to Dedicated Analog Block
Outline
This instruction writes a digital value to the analog block FX
0N
-3A or FX
2N
-2DA.
1. Instruction format
2. Set data
3. Applicable devices
Explanation of function and operation
1. 16-bit operation (WR3A)
m1
: Special block number
FX
3U
PLC : K0 to K7
FX
3UC
PLC: K1 to K7 (K0 indicates the built-in CC-Link/LT master.)
m2
: Analog input channel number
FX
0N-
3A
: K1 (ch 1)
FX
2N
-2DA : K21 (ch 1) or K22 (ch 2)
: Data to be written
Specify a value output to the analog block.
FX
0N
-3A
: 0 to 255 (8 bits)
FX
2N
-2DA : 0 to 4095 (12 bits)
Operand Type
Description
Data Type
m1
Special block number
- FX
3U
PLC : K0 to K7
- FX
3UC
PLC : K1 to K7
16- or 32-bit binary
m2
Analog output channel number
16- or 32-bit binary
Data to be written or word device storing data to be written
16- or 32-bit binary
Oper-
and
Type
Bit Devices
Word Devices
Others
System User
Digit Specification
System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
X Y M T C S D
.b KnX KnY KnM KnS
T
C
D
R U
\G
V
Z Modify K
H
E
"
"
P
m1
3
3
3
3
3 3 3 3
3 3
3
3 3
m2
3
3
3
3
3 3 3 3
3 3
3
3 3
3
3
3
3 3 3 3
3 3
3
P
FNC 177
WR3A
Mnemonic
Operation Condition
16-bit Instruction
7 steps
WR3A
WR3AP
Mnemonic
Operation Condition
Continuous
Operation
Pulse (Single)
Operation
32-bit Instruction
−
S
S
FNC177
WR3A
m1
m2
Command
input
S
S