384
FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
14 Handy Instruction – FNC 60 to FNC 69
14.5 FNC 64 – TTMR / Teaching Timer
Cautions
1. When the command contact turns OFF
The current value [
+1] of the pressing and holding time is reset, and the teaching time
will not
change any more.
2. Number of occupied devices
Two devices are occupied from a device specified as the teaching time
.
Make sure that these devices are not used in other controls for the machine.
•
: Teaching time
•
+1: Current value of the pressing and holding time
Program example
1. Writing the teaching time to 10 types of data registers
Suppose that the set value is written in advance to D400 to D409.
D
1
D
D
1
D
D
1
D
D
1
D
D
1
D
M8000
RUN
monitor
T 0
D 400
T 1
D 401
T 9
D 409
X010
Teaching
button
M 0
X010
FNC 19
BIN
K1X000
Z
FNC 64
TTMR
D300
K 0
PLF
M 0
FNC 12
MOV
D300
D400Z
10 timers to be set
Because the timers T0 to T9 are the 100 ms type, the actual
operating time (sec) is 1/10 of the teaching data.
Selecting a timer by a digital switch
An input to the 1-digit digital switch connected to X000 to
X003 is converted into the binary format, and transferred to Z.
Measuring the teaching time
The time (sec) in which X010 is pressed and held is stored to
D300.
Recovery of the teaching time is detected.
Writing the set value of a timer
The teaching time (D300) is transferred to the register D400Z
for setting a timer selected by the digital switch.
…