A Programming Tool Applicability and Version Upgrade History
A-1 Programming Tool Applicability
Appendix A-1-4 Cautions on using transparent (2-port) function of
GOT-F900 Series
When monitoring circuits, device registration, etc. in an FX
3U
or FX
3UC
PLC from GX Developer Ver. 8.13P or
later using the transparent (2-port) function in the GOT-F900 Series, make sure to execute the following
setting.
If the following setting is not provided, monitoring cannot be executed normally.
*1.
GX Developer Ver.8.13P or later supports the FX
3UC
Series.
Setting in GX Developer (Ver.8.13P or later)
1. Select [Online]
→
[Transfer setup...] to open "Transfer Setup" dialog box.
2. Double-click [PLC module] in [PLC side I/F] to open [PLC side I/F Detailed setting of PLC
module] dialog box.
3. Put a check mark to the check box [via GOT-F900 transparent mode] as shown below.
4. Click [OK] button to finish the setting.
GX Developer
Ver.8.12N or earlier
*1
GX Developer
Ver.8.13P or later
GX Developer Ver.8.22Y or later
When using
transparent function in
GOT-F900 Series
Setting shown below is
not required.
Setting shown below is
required.
Select "RS-232C" on "PC side I/F Serial
setting" dialog box, and execute setting
shown below.
When directly
connecting GX
Developer to PLC
Set "COM port" and "Transmission speed" on "PC
side I/F Serial setting" dialog box.
Select "RS-232C" on "PC side I/F Serial
setting" dialog box, and set "COM port" and
"Transmission speed".
Double-click it.
Put a check mark to the
check box "via GOT-F900
transparent mode".