21 Real Time Clock Control – FNC160 to FNC169
21.7 FNC166 – TRD / Read RTC data
21.7
FNC166 – TRD / Read RTC data
Outline
This instruction reads the clock data of the real time clock built in a PLC.
1. Instruction format
2. Set data
3. Applicable devices
Explanation of function and operation
1. 16-bit operation (TRD)
The clock data stored in D8013 to D8019 of the real time clock built in a PLC is read in the following format,
and stored to
to
+6.
This instruction reads the real time clock data in a PLC, and transfers it to
seven data registers.
Caution
1. Number of occupied devices
Seven devices are occupied by
.
Make sure that these devices are not used in other controls for the machine.
Operand type
Description
Data type
Specifies the head device number storing the clock data.
(Seven devices are occupied.)
16-bit binary
Oper-
and
Type
Bit Devices
Word Devices
Others
System User
Digit Specification
System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
X Y M T C S D
.b KnX KnY KnM KnS
T
C
D
R U
\G
V
Z Modify K
H
E
"
"
P
3 3 3 3
3
3
Device
Item
Clock data
Device
Item
Sp
eci
al d
a
ta
r
e
gis
ter
D8018
Year
0 to 99
(lower two digits)
→
D 0
Year
D8017
Month
1 to 12
→
D 1
Month
D8016
Day
1 to 31
→
D 2
Day
D8015
Hour
0 to 23
→
D 3
Hour
D8014
Minute
0 to 59
→
D 4
Minute
D8013
Second
0 to 59
→
D 5
Second
D8019
Day of week
0 (Sunday) to
6 (Saturday)
→
D 6
Day of week
P
FNC 166
TRD
−
Mnemonic
Operation Condition
16-bit Instruction
3 steps
TRD
TRDP
Mnemonic
Operation Condition
Continuous
Operation
Pulse (Single)
Operation
32-bit Instruction
D
S
2
D
D
D
Command
input
FNC166
TRD
D
D