308
FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
12 Data Operation – FNC 40 to FNC 49
12.7 FNC 46 – ANS / Timed Annunciator Set
12.7
FNC 46 – ANS / Timed Annunciator Set
Outline
This instruction sets a state relay for annuciator (S900 to S999).
1. Instruction format
2. Set data
3. Applicable devices
S
1 : T0 to T199
S
2 : S900 to S999
Explanation of function and operation
1. 16-bit operation
When the command input remains ON for not less than the evaluation time [m
×
100 ms, timer
],
is set.
When the command input remains ON for less than the evaluation time [m
×
100 ms] and then turns OFF, the
current value of the timer for evaluation
is reset and
is not set.
When the command input turns OFF, the timer for evaluation is reset.
Related devices
Operand type
Description
Data type
Timer number for evaluation time
16-bit binary
m
Evaluation time data [m = 1 to 32767 (unit: 100 ms)]
16-bit binary
Annunciator device to be set
16-bit binary
Oper-
and
Type
Bit Devices
Word Devices
Others
System User
Digit Specification
System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
X Y M T C S D
.b KnX KnY KnM KnS
T
C
D
R U
\G
V
Z Modify K
H
E
"
"
P
S
1
3
m
3 3
3 3
S
2
3
Device
Name
Description
M8049
Enable annunciator
When M8049 is set to ON, M8048 and D8049 are valid.
M8048
Annunciator ON
When M8049 is ON and either one among the state relays S900 to S999 is ON, M8048
turns ON.
D8049
Smallest state relay
number in ON status
Among S900 to S999, the smallest state relay number in the ON status is stored.
FNC 46
ANS
−
Mnemonic
Operation Condition
16-bit Instruction
7 steps
ANS
Mnemonic
Operation Condition
Continuous
Operation
32-bit Instruction
S
1
S
D
S
1
S
D
D
1
S
D
1
D
D
1
S
D
1
D
Command
input
FNC 46
ANS
S
D
m
Command input
D
Less than
evaluation time
(m
×
100 ms)
Equivalent to or
more than
evaluation time
(m
×
100 ms)