Chapter 9
207
Logic programming – Function blocks
The general safety regulations and protective measures have to be observed!
If you use muting, be sure to observe the following information about the correct use of
muting:
Access to the hazardous area has to be detected reliably by the ESPE or be
excluded through other measures. It has to be impossible for a person to pass by,
pass over, pass under or cross the ESPE without being detected. Observe the
manual of the ESPE for the correct installation and use of the device.
Always observe the valid applicable local, regional and national regulations and
standards applying to your application. Ensure that your application conforms to an
appropriate risk analysis and avoidance strategy.
Muting may never be used to transport a person into the hazardous area.
Mount the control devices for resetting and overriding outside the hazardous area
so that they cannot be actuated by a person located in the hazardous area.
Furthermore, when operating a control device, the operator must have full visual
command of the hazardous area.
The muting sensors have to be located in such a way that the hazardous area can
only then be accessed after an intervention in the protective field, if the dangerous
state has been terminated before. One condition here is that the required safety
distances defined in EN/ISO 13855 are observed. At least two muting signals that
are independent of each other are required.
Muting may only be activated for the period in which the object that triggered the
muting condition blocks access to the hazardous area.
The area between the ESPE and the muting sensors must be protected against
standing behind:
– For Parallel muting between ESPE and sensors A1/A2 and between ESPE and
sensors B1/B2 (see Figure 200).
– For Sequential muting between ESPE and sensor A2 and between ESPE and
sensor B1 (see Figure 203).
– For Cross muting between ESPE and sensor A1 and between ESPE and sensor
A2 (see Figure 206)
Muting has to be carried out automatically, but may not depend on a single
electrical signal.
The material to be transported has to be detected along the entire length, meaning
that an interruption of the output signals may not occur (see Suppression of sensor
signal gaps).
Muting must be triggered by at least two independently wired signals (e.g. by
muting sensors) and may not depend completely on software signals (e.g. from a
programmable controller).
The muting condition has to be terminated immediately after the passage of the
object so that the protective device returns to its normal state that was bypassed by
muting (i.e. so that it comes back into force).
The muting sensors have to be positioned in such a way that muting cannot be
triggered unintentionally by anyone (see Figure 196).
ATTENTION
Summary of Contents for SW1DNN-WS0ADR-B
Page 2: ......
Page 288: ...Chapter 15 285 Annex ...
Page 289: ...Chapter 15 286 Annex ...
Page 290: ...Chapter 15 287 Annex ...
Page 291: ...Chapter 15 288 Annex ...
Page 292: ...Chapter 15 289 Annex ...
Page 293: ...Chapter 15 290 Annex ...
Page 294: ...Chapter 15 291 Annex ...
Page 295: ...Chapter 15 292 Annex ...
Page 296: ...Chapter 15 293 Annex ...
Page 297: ...Chapter 15 294 Annex ...
Page 298: ...Chapter 15 295 Annex 15 1 2 Example application Wood scanner ...
Page 299: ...Chapter 15 296 Annex ...
Page 300: ...Chapter 15 297 Annex ...
Page 301: ...Chapter 15 298 Annex ...
Page 302: ...Chapter 15 299 Annex ...
Page 303: ...Chapter 15 300 Annex ...
Page 304: ...Chapter 15 301 Annex ...
Page 305: ...Chapter 15 302 Annex ...
Page 306: ...Chapter 15 303 Annex ...
Page 307: ...Chapter 15 304 Annex 15 1 3 Example application Ramp down detection ...
Page 308: ...Chapter 15 305 Annex ...
Page 309: ...Chapter 15 306 Annex ...
Page 310: ...Chapter 15 307 Annex ...
Page 311: ...Chapter 15 308 Annex ...
Page 312: ...Chapter 15 309 Annex ...
Page 313: ...Chapter 15 310 Annex ...
Page 314: ...Chapter 15 311 Annex ...
Page 321: ......